General Information

Automatic Transfer Switch Owner’s Manual

7

Smart A/C Module (SACM)

See 

Figure 2-2

. Up to four air conditioner loads can be

managed by the SACM. The SACM manages, or
temporarily disconnects, the connected loads in the
event of a drop in generator frequency (overload). Loads
to be managed are in 4 priority levels on the module. 
Priorities A/C 1-4 (A) have connections for an air
conditioner. To control an air conditioner, no additional
equipment is required. Internal normally closed relays
interrupt the 24 VAC thermostat control signal to disable
the air conditioner load.
Four LEDs, located on the SACM (B), illuminate when a
load is connected and powered.
The SACM has a test button used to simulate an
overload condition. This button operates even when the
transfer signal is inactive.

Figure 2-2. Smart A/C Module (SACM)

Smart Management Module (SMM)
(Sold Separately)

See 

Figure 2-3

Any loads, including central air

conditioners, can be managed using a SMM. The system
can accommodate up to eight individual SMMs.

NOTE: 

SMMs are self-contained and have individual

built-in controllers.

Figure 2-3. Smart Management Module (SMM)

Application Considerations

Generator overload condition is determined by generator
frequency. Loads are shed when frequency is less than
58 Hz for three seconds or less than 50 Hz for one-half
second (for 60 Hz systems).
The SACM can be used in conjunction with individual
SMMs to manage a combined total of 12 loads: eight
SMMs and four SACMs. 

Use Priorities A/C 1–4 on the SACM as the top
priorities, then up to four SMMs as Priorities 5–8.

Use only select A/C priorities on the SACM as the top
priorities, then use additional SMMs as the remaining
priorities.

A SMM can share a priority with an A/C priority on
the SACM provided the generator is sized to handle
the combined surge load from both appliances.
Sharing priorities can allow up to 12 loads to be
managed in a properly sized system.

In any combination of modules, the recovery times after a
loss of utility power or shutdown due to overload are
shown in Table 1.

Refer to the SMM Owner’s/Installation Manual for
detailed characteristics and specifications of that product.

0 GROUND

194 +12V

23 TRANSFER

A/C 1

A/C 2

A/C 3

A/C 4

A/C 1

A/C 2

A/C 3

A/C 4

T1

NEUTRAL

000802

B

A

Table 1. Priority Settings

Priority

Recovery Time

Smart A/C 

Module

Smart 

Management 

Module

1

5 minutes

Yes

Yes

2

5 minutes 15 seconds

Yes

Yes

3

5 minutes 30 seconds

Yes

Yes

4

5 minutes 45 seconds

Yes

Yes

5

6 minutes 

NA

Yes

6

6 minutes 15 seconds

NA

Yes

7

6 minutes 30 seconds

NA

Yes

8

6 minutes 45 seconds

NA

Yes

000106

Содержание RTG24SHA1

Страница 1: ...1 100A RTG42SHA1 200A Register your Generac product at WWW GENERAC COM 888 436 3722 Para espa ol visita http www generac com service support product support lookup SAVE THIS MANUAL FOR FUTURE REFERENC...

Страница 2: ...contains or emits chemicals known to the state of California to cause cancer birth defects and other reproductive harm 000004 WARNING California Proposition 65 Engine exhaust and some of its constitue...

Страница 3: ...y Source Side 13 Close to Generator Source Side 14 Return to Utility Source Side 14 Voltage Checks 14 Utility Voltage Checks 14 Generator Voltage Checks 14 Generator Tests Under Load 14 Checking Autom...

Страница 4: ...Table of Contents iv Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 5: ...ible circumstance that might involve a hazard The warnings in this manual and on tags and decals affixed to the unit are therefore not all inclusive If using a procedure work method or operating techn...

Страница 6: ...connections of the transfer switch Failure to do so will result in death or serious injury 000157 DANGER Electrocution Do not disable or modify the connection box door safety switch Doing so will res...

Страница 7: ...ch Failure to do so will result in death or serious injury 000104 DANGER Electrocution Water contact with a power source if not avoided will result in death or serious injury 000188 DANGER Electrocuti...

Страница 8: ...Introduction and Safety 4 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 9: ...standby electric system installations The transfer switch consists of a transfer mechanism utility service disconnect circuit breaker a control relay fuses terminal strip and fuse holder for connecti...

Страница 10: ...Code UL 1008 STANDARD FOR SAFETY AUTOMATIC TRANSFER SWITCHES UL 67 Panelboards Marking and Application Guide NOTE It is essential to use the latest version of any standard to ensure correct and curre...

Страница 11: ...termined by generator frequency Loads are shed when frequency is less than 58 Hz for three seconds or less than 50 Hz for one half second for 60 Hz systems The SACM can be used in conjunction with ind...

Страница 12: ...General Information 8 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 13: ...onvenience and proximity to the utility supply and load center Install the transfer switch as close as possible to the electrical loads that are to be connected to it Mount the switch vertically to a...

Страница 14: ...NEC Article 210 4 Connecting Power Source and Generator Power Supply Installation and interconnection diagrams are provided in this manual NOTE All installations must comply with national state and l...

Страница 15: ...wiring connection details Recommended wire gauge sizes for this wiring depends on the length of the wire as recommended in the following chart Exception Conductors of AC and DC circuits rated 1000 vol...

Страница 16: ...is in utility mode The contacts will open when the transfer switch is in the standby power mode Figure 3 5 Auxiliary Contact NOTE Auxiliary Contact is rated 10 amps at 125 or 250 volts AC and 0 6 amp...

Страница 17: ...sm main contacts by observing the movable contact carrier arm This can be viewed through the long narrow slot in the inside cover of the ATS The top of the movable contact carrier arm is yellow to be...

Страница 18: ...nsfer switch ratings turn OFF the generator supply to the transfer switch 6 On the generator panel select the OFF mode to shut down the generator NOTE Do NOT proceed until generator AC output voltage...

Страница 19: ...utility power source Approximately one minute after re transfer the engine should shut down With the generator in the AUTOMATIC mode the system is now set for fully automatic operation Installation S...

Страница 20: ...Operation 16 Automatic Transfer Switch Owner s Manual Testing The Smart Management Module Refer to the SMM Owner s Installation Manual for testing that product...

Страница 21: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 17 Section 5 Drawings and Diagrams Installation Drawings Installation Drawing No 10000005900 100A 2 of 2...

Страница 22: ...Drawings and Diagrams 18 Automatic Transfer Switch Owner s Manual Installation Drawing No 10000005900 200A 1 of 2...

Страница 23: ...Transfer Switch Owner s Manual 19 Interconnection Drawings Interconnection Drawing 10000005901 Air Cooled 100A Generator page 1 of 2 INTERCONNECTION DRAWING AIR COOLED GENERATOR RTG24SHA1 DRAWING 1000...

Страница 24: ...s 20 Automatic Transfer Switch Owner s Manual Interconnection Drawing 10000005901 Air Cooled 100A Generator page 2 of 2 INTERCONNECTION DRAWING AIR COOLED GENERATOR RTG24SHA1 DRAWING 10000005901 REVIS...

Страница 25: ...s Automatic Transfer Switch Owner s Manual 21 Interconnection Drawing 10000005901 Air Cooled 200A Generator page 1 of 2 INTERCONNECTION DRAWING AIR COOLED GENERATOR RTG42SHA1 DRAWING 10000005901 REVIS...

Страница 26: ...ms 22 Automatic Transfer Switch Owner s Manual Interconnection Drawing 10000005901 Air Cooled 200A Generator page 2 of 2 INTERCONNECTION DRAWING AIR COOLED GENERATOR RTG42SHA1 DRAWING 10000005901 REVI...

Страница 27: ...utomatic Transfer Switch Owner s Manual 23 Interconnection Drawing 10000005855 Liquid Cooled 100A Generator page 1 of 2 INTERCONNECTION DRAWING LIQUID COOLED GENERATOR RTG24SHA1 DRAWING 10000005855 RE...

Страница 28: ...4 Automatic Transfer Switch Owner s Manual Interconnection Drawing 10000005855 Liquid Cooled 100A Generator page 2 of 2 INTERCONNECTION DRAWING LIQUID COOLED GENERATOR RTG24SHA1 DRAWING 10000005855 RE...

Страница 29: ...utomatic Transfer Switch Owner s Manual 25 Interconnection Drawing 10000005855 Liquid Cooled 200A Generator page 1 of 2 INTERCONNECTION DRAWING LIQUID COOLED GENERATOR RTG42SHA1 DRAWING 10000005855 RE...

Страница 30: ...6 Automatic Transfer Switch Owner s Manual Interconnection Drawing 10000005855 Liquid Cooled 200A Generator page 2 of 2 INTERCONNECTION DRAWING LIQUID COOLED GENERATOR RTG42SHA1 DRAWING 10000005855 RE...

Страница 31: ......

Страница 32: ...rights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W2929...

Отзывы: