Installation

Automatic Transfer Switch Owner’s Manual

11

Conductor sizes must be adequate to handle the
maximum current to which they will be subjected, based
on the 75°C column of tables, charts, etc. used to size
conductors. The installation must comply fully with all
applicable codes, standards and regulations.
All power cables can enter the enclosure through the
provided knockouts. Additional knockouts into the
enclosure can be made in the field as needed.

NOTE: 

Cover and protect the transfer switch and

breakers while removing knockout slugs. Avoid dropping
slugs or metal chips into the enclosure.

Conduit entry shall maintain the proper wire bending
spaces required by Tables 312.6 (A) and (B) in the NEC.
Conduits should be arranged to provide separation
between the Utility and Generator supply conductors
inside the enclosure.

NOTE: 

If aluminum conductors are used, apply corrosion

inhibitor to conductors. After tightening terminal lugs,
carefully wipe away any excess corrosion inhibitor.

Tighten terminal lugs to the torque values as noted on the
decal located on the inside of the door. After tightening
terminal lugs, carefully wipe away any excess corrosion
inhibitor. 

Connecting Start Circuit Wires

Control system interconnections may consist of N1, N2,
and T1, and leads 23 and 194. The generator control
wiring is a Class 1 signaling circuit. Reference instruction
manual of specific engine generator for wiring connection
details. Recommended wire gauge sizes for this wiring
depends on the length of the wire, as recommended in
the following chart:

 

Exception: 

Conductors of AC and DC circuits, rated

1000 volts nominal, or less, shall be permitted to occupy
the same equipment, cable, or conduit. All conductors
shall have an insulation rating equal to at least the
maximum circuit voltage applied to any conductor within
the equipment, cable, or conduit. See NEC 300.3(C)(1).

Connecting Smart A/C Module 

(SACM)

See 

Figure 3-4

. The Smart A/C Module (SACM) can

control an air conditioner (24 VAC) directly. 

Control of Air Conditioner Load

1.

Route the thermostat cable (from the furnace/
thermostat to the outdoor air conditioner unit) to the
transfer switch.

2.

Connect the wire to the terminal strip terminals (A/C
1) on the SACM as shown in 

Figure 3-4

. These are

normally closed contacts which open upon load shed
conditions. Route thermostat wire away from high
voltage wires.

3.

If required, connect additional air conditioners to
the terminal strip terminals (A/C 2-4).

NOTE: 

These instructions are for a typical air conditioner

installation. Control of certain heat pumps and 2-stage air
conditioners may require special connections or the use
of SMMs to control the loads.

Maximum Wire Length

Recommended Wire Size

1–115 ft (1–35 m)

No. 18 AWG

116–185 ft (36–56 m)

No. 16 AWG

186–295 ft (57–89 m)

No. 14 AWG

296–460 ft (90–140 m)

No. 12 AWG

(000120)

CAUTION

Equipment damage. Verify all conductors are 
tightened to the factory specified torque value. 
Failure to do so could result in damage 
to the switch base.

 

Contact Ratings

A/C 1-4 

24 VAC, 1.0 Amp Max

Содержание RTG24SHA1

Страница 1: ...1 100A RTG42SHA1 200A Register your Generac product at WWW GENERAC COM 888 436 3722 Para espa ol visita http www generac com service support product support lookup SAVE THIS MANUAL FOR FUTURE REFERENC...

Страница 2: ...contains or emits chemicals known to the state of California to cause cancer birth defects and other reproductive harm 000004 WARNING California Proposition 65 Engine exhaust and some of its constitue...

Страница 3: ...y Source Side 13 Close to Generator Source Side 14 Return to Utility Source Side 14 Voltage Checks 14 Utility Voltage Checks 14 Generator Voltage Checks 14 Generator Tests Under Load 14 Checking Autom...

Страница 4: ...Table of Contents iv Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 5: ...ible circumstance that might involve a hazard The warnings in this manual and on tags and decals affixed to the unit are therefore not all inclusive If using a procedure work method or operating techn...

Страница 6: ...connections of the transfer switch Failure to do so will result in death or serious injury 000157 DANGER Electrocution Do not disable or modify the connection box door safety switch Doing so will res...

Страница 7: ...ch Failure to do so will result in death or serious injury 000104 DANGER Electrocution Water contact with a power source if not avoided will result in death or serious injury 000188 DANGER Electrocuti...

Страница 8: ...Introduction and Safety 4 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 9: ...standby electric system installations The transfer switch consists of a transfer mechanism utility service disconnect circuit breaker a control relay fuses terminal strip and fuse holder for connecti...

Страница 10: ...Code UL 1008 STANDARD FOR SAFETY AUTOMATIC TRANSFER SWITCHES UL 67 Panelboards Marking and Application Guide NOTE It is essential to use the latest version of any standard to ensure correct and curre...

Страница 11: ...termined by generator frequency Loads are shed when frequency is less than 58 Hz for three seconds or less than 50 Hz for one half second for 60 Hz systems The SACM can be used in conjunction with ind...

Страница 12: ...General Information 8 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 13: ...onvenience and proximity to the utility supply and load center Install the transfer switch as close as possible to the electrical loads that are to be connected to it Mount the switch vertically to a...

Страница 14: ...NEC Article 210 4 Connecting Power Source and Generator Power Supply Installation and interconnection diagrams are provided in this manual NOTE All installations must comply with national state and l...

Страница 15: ...wiring connection details Recommended wire gauge sizes for this wiring depends on the length of the wire as recommended in the following chart Exception Conductors of AC and DC circuits rated 1000 vol...

Страница 16: ...is in utility mode The contacts will open when the transfer switch is in the standby power mode Figure 3 5 Auxiliary Contact NOTE Auxiliary Contact is rated 10 amps at 125 or 250 volts AC and 0 6 amp...

Страница 17: ...sm main contacts by observing the movable contact carrier arm This can be viewed through the long narrow slot in the inside cover of the ATS The top of the movable contact carrier arm is yellow to be...

Страница 18: ...nsfer switch ratings turn OFF the generator supply to the transfer switch 6 On the generator panel select the OFF mode to shut down the generator NOTE Do NOT proceed until generator AC output voltage...

Страница 19: ...utility power source Approximately one minute after re transfer the engine should shut down With the generator in the AUTOMATIC mode the system is now set for fully automatic operation Installation S...

Страница 20: ...Operation 16 Automatic Transfer Switch Owner s Manual Testing The Smart Management Module Refer to the SMM Owner s Installation Manual for testing that product...

Страница 21: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 17 Section 5 Drawings and Diagrams Installation Drawings Installation Drawing No 10000005900 100A 2 of 2...

Страница 22: ...Drawings and Diagrams 18 Automatic Transfer Switch Owner s Manual Installation Drawing No 10000005900 200A 1 of 2...

Страница 23: ...Transfer Switch Owner s Manual 19 Interconnection Drawings Interconnection Drawing 10000005901 Air Cooled 100A Generator page 1 of 2 INTERCONNECTION DRAWING AIR COOLED GENERATOR RTG24SHA1 DRAWING 1000...

Страница 24: ...s 20 Automatic Transfer Switch Owner s Manual Interconnection Drawing 10000005901 Air Cooled 100A Generator page 2 of 2 INTERCONNECTION DRAWING AIR COOLED GENERATOR RTG24SHA1 DRAWING 10000005901 REVIS...

Страница 25: ...s Automatic Transfer Switch Owner s Manual 21 Interconnection Drawing 10000005901 Air Cooled 200A Generator page 1 of 2 INTERCONNECTION DRAWING AIR COOLED GENERATOR RTG42SHA1 DRAWING 10000005901 REVIS...

Страница 26: ...ms 22 Automatic Transfer Switch Owner s Manual Interconnection Drawing 10000005901 Air Cooled 200A Generator page 2 of 2 INTERCONNECTION DRAWING AIR COOLED GENERATOR RTG42SHA1 DRAWING 10000005901 REVI...

Страница 27: ...utomatic Transfer Switch Owner s Manual 23 Interconnection Drawing 10000005855 Liquid Cooled 100A Generator page 1 of 2 INTERCONNECTION DRAWING LIQUID COOLED GENERATOR RTG24SHA1 DRAWING 10000005855 RE...

Страница 28: ...4 Automatic Transfer Switch Owner s Manual Interconnection Drawing 10000005855 Liquid Cooled 100A Generator page 2 of 2 INTERCONNECTION DRAWING LIQUID COOLED GENERATOR RTG24SHA1 DRAWING 10000005855 RE...

Страница 29: ...utomatic Transfer Switch Owner s Manual 25 Interconnection Drawing 10000005855 Liquid Cooled 200A Generator page 1 of 2 INTERCONNECTION DRAWING LIQUID COOLED GENERATOR RTG42SHA1 DRAWING 10000005855 RE...

Страница 30: ...6 Automatic Transfer Switch Owner s Manual Interconnection Drawing 10000005855 Liquid Cooled 200A Generator page 2 of 2 INTERCONNECTION DRAWING LIQUID COOLED GENERATOR RTG42SHA1 DRAWING 10000005855 RE...

Страница 31: ......

Страница 32: ...rights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W2929...

Отзывы: