Installation Manual for PV Link and SnapRS

15

2017 and 2020 NEC Compliant Sys

-

tems

For NEC 2017 and 2020 NEC compliant sys

-

tems,  connect  the  string  PV  modules  in  a

series using one SnapRS device per module.

Installing SnapRS Devices

NOTE: 

Pre-install  SnapRS  devices  to  PV

modules to ensure a 1:1 ratio.
When installing SnapRS devices consider the

following: 

• Each  PV  Link  can  control  a  connected

string  of PV  modules with a  string  voltage

between  60–420  VDC.  For  string  sizing

guidance,  see 

Installation  Design  Work

-

sheet

.  

• The  positive  (+)  end  of  one  (1)  SnapRS

device must be installed to the negative (-)

lead of each PV module in the array.

• PV modules require Staubli (Multi-Contact)

MC4 connectors. Brands other than Staubli

MC4 connectors are not recommended.

NOTE: 

MC  connectors  are  not  watertight

unless  mated.  Never  leave  this  system  par

-

tially assembled.
• See 

Figure 5-4

. PV modules are installed in

series  with  SnapRS  devices  connected

inline between each module.

• See 

Figure 5-5

. High-voltage modules can

be configured in parallel strings. 

NOTE: 

Install SnapRS devices prior to secur

-

ing PV modules to the racking.

To install SnapRS devices:

1. See 

Figure 5-4

. For each PV module in the

PV string, connect the positive (+)  end of

one SnapRS device (C) to the negative (-)

whip of the PV Module (D).

2. Connect  the  negative  (-)  end  of  each

SnapRS device to the positive (+) whip of

the next PV module in the series.

3. Connect the PV string positive lead to PV

Link  (B)  at  the  location  marked  PV  Sub

-

string  Input  +  (F).  See 

Component Loca

-

tions

 for more information. 

4. Connect  the  PV  string  negative lead  with

its  connected  SnapRS  device  to  PV  Link

(B)  at  the  location  marked  PV  Substring

Input - (E). See 

Component Locations

 for

more information. 

5. Secure the SnapRS devices to the racking

or module frame using zip ties or a similar

fastener.

NOTE: 

When connecting the PV string to the

PV Link, the PV Link MC4 connector labeling

will indicate the same polarity as the PV string

connector  (ex.  PV  Link  positive  (+)  will  con

-

nect to the (+) whip of the first PV module in

the string). This will also be true with SnapRS

installed on the negative (-) whip. This is inten

-

tional and differs from the connection method

for  combining  PV  modules  together  with

SnapRS..
6. Make a string map using the PV Link peel-

and-stick  serial  number  stickers  and

record  in 

Table 1:  PV  Link  and  SnapRS

Important Information

  the  following  infor

-

mation:

– Each PV Link serial number

– Each PV Link RCP number

– Number of parallel strings

– SnapRS devices per string

– SnapRS date of manufacture.

Figure 5-4. Single-String PV Array with SnapRS Device 

A

PWRcell Inverter

D

PV module

B

PV Link

E

PV Substring Input -

C

SnapRS Device

F

PV Substring Input +

C

A

E

F

B

D

C

Содержание PV Link

Страница 1: ...d in a critical life support application Failure to adhere to this warning could result in death or serious injury Register your Generac product at https pwrfleet generac com 1 888 GENERAC 888 436 372...

Страница 2: ...ty to perform all safety checks to verify that all maintenance for safe operation is performed promptly and to have the equipment checked periodically by an ASD Normal maintenance service and replacem...

Страница 3: ...t Locations 7 Section 3 Installation Design 9 Installation Design Worksheet 9 Section 4 PVRSS Compliance Guidelines 11 Section 5 Mounting and Connecting 13 Installation Guidelines 13 Attachment and Gr...

Страница 4: ...erating technique that the manufacturer does not specifically recommend verify that it is safe for others and does not render the equipment unsafe Throughout this publication and on tags and decals af...

Страница 5: ...completed PV system meets the rapid shutdown functional requirements This equip ment must be installed according to the manu facturer s installation instructions 000191 DANGER Automatic start up Disco...

Страница 6: ...s injury equipment and property damage DANGER 000152 DANGER Electrocution Verify electrical system is properly grounded before applying power Failure to do so will result in death or serious injury 00...

Страница 7: ...4 Installation Manual for PV Link and SnapRS This page is intentionally left blank...

Страница 8: ...te maximum Maximum input current operating A F C 13 122 50 Maximum input current short circuit A 18 Maximum output current fault A 10 Maximum output voltage VDC 420 open circuit Nominal output REbus D...

Страница 9: ...rtant Information Figure 2 1 Serial Number Location SnapRS Date of Manufacture Refer to Figure 2 2 to locate the unit date of manufacture Record this information in Table 1 PV Link and SnapRS Importan...

Страница 10: ...The PV Link meets the ground fault protection requirements in NEC Article 690 41 B AFCI Information The PV Link is a Photovoltaic DC Arc Fault Circuit Protection Type 1 device that incorpo rates an in...

Страница 11: ...8 Installation Manual for PV Link and SnapRS SnapRS Component Locations Figure 2 6 Component Locations A Positive PV Connector B Negative PV Connector A B 010050...

Страница 12: ...ge limit 3 Divide the PV Link VMP Voltage at Maxi mum Power by the panel VMP and round down to determine the number of panels that can be connected in series to the PV Link without exceeding maximum p...

Страница 13: ...10 Installation Manual for PV Link and SnapRS This page is intentionally left blank...

Страница 14: ...eet 2017 and 2020 compliance 1 The 2017 and 2020 NEC requires the PVRSS initiator be located at a readily accessible location outside the building The DC disconnect under the PWRcell inverter cover la...

Страница 15: ...12 Installation Manual for PV Link and SnapRS This page is intentionally left blank...

Страница 16: ...TRIC SHOCK HAZARD DC OUTPUT CONDUCTORS MAY BE ENERGIZED REGARDLESS OF SUN EXPOSURE CAUTION RISK OF ELECTRIC SHOCK WHENTHE PHOTOVOLTAIC ARRAY IS EXPOSEDTO LIGHT IT SUPPLIES A DCVOLTAGETO EQUIPMENT COVE...

Страница 17: ...connections due to poor wiring practices 2014 NEC and Earlier Editions For NEC 2014 compliant systems connect the substring PV modules in series To install PV modules in series to PV Link 1 Connect t...

Страница 18: ...to the negative whip of the PV Module D 2 Connect the negative end of each SnapRS device to the positive whip of the next PV module in the series 3 Connect the PV string positive lead to PV Link B at...

Страница 19: ...ed in parallel each string must use the same number of the same type of PV modules and there must be one SnapRS device for each module in the array Figure 5 5 Parallel Input PV Array with SnapRS Devic...

Страница 20: ...ee the Generac PWRcell Inverter Installation Manual for instructions on commissioning the REbus system PVRSS Commissioning with SnapRS Devices To enable PV Link to work as a PVRSS with SnapRS devices...

Страница 21: ...high input The voltage detected with SnapRS devices disabled is higher than expected Verify the SnapRS devices are installed correctly Run the PVRSS self test SnapRS devices have not been installed or...

Страница 22: ...fault is detected the status message reads Arc Fault To conduct an AFD test 1 On the PWRcell inverter control panel use the left or right arrows to scroll to the page for the desired PV Link 2 Press t...

Страница 23: ...20 Installation Manual for PV Link and SnapRS This page is intentionally left blank...

Страница 24: ...ice If the PV Link is not operating as expected or if a PV Link error message appears on the Generac PWRcell Inverter control panel LCD display contact the nearest Independent Authorized Service Deale...

Страница 25: ...22 Installation Manual for PV Link and SnapRS This page is intentionally left blank...

Страница 26: ...the general health of a SnapRS device DMM Red to SnapRS DMM Black to SnapRS Resistance reads 300 k to 350 k Diode check reads 0 50 V to 0 55 V DMM Red to SnapRS DMM Black to SnapRS Resistance reads 1...