![Generac Power Systems PV Link Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/generac-power-systems/pv-link/pv-link_installation-manual_2208946010.webp)
Installation Manual for PV Link and SnapRS
7
About PV Link
The PV Link is a nonisolated, interleaved DC-
DC converter that boosts PV input to a higher
voltage and outputs it to Rebus™, Generac’s
regulated 380 VDC bus. The PV Link provides
droop-mode power management, enabling
multiple optimizers to connect in parallel on a
common bus, and its DC output carries a bidi
-
rectional power line communication (PLC)
protocol for communicating with inverters and
other devices on REbus.
The PV Link is sealed in a type 3R enclosure
at the factory and is designed for attachment
to standard PV racking. Safety features
include ground fault detection, arc fault detec
-
tion, and rapid shutdown capability.
About Generac SnapRS
SnapRS is an inline PV rapid-shut down
device that satisfies 2017 and 2020 NEC
690.12 PV rapid shutdown system (PVRSS)
requirements. When used with PV Link,
SnapRS devices limit all controlled conductors
within an array’s 1 ft (305 mm) boundary to 80
VDC or less within 30 seconds of rapid shut
-
down initiation.
GFCI Information
The PV Link’s internal ground-fault circuit
interrupter (GFCI) is designed to trip at 240
mA (± 40 mA) of PV DC voltage ground cur
-
rent. Ground faults are displayed on the PWR
-
cell inverter control panel. The PV Link meets
the ground-fault protection requirements in
NEC Article 690.41(B).
AFCI Information
The PV Link is a Photovoltaic DC Arc-Fault
Circuit Protection Type 1 device that incorpo
-
rates an internal arc fault circuit interrupter
(AFCI) and meets the Arc-Fault circuit protec
-
tion requirement in NEC Article 690.11.
PVRSS Information
PV rapid shutdown system (PVRSS) require
-
ments have evolved over time and are defined
by the National Electrical Code (NEC) in con
-
junction with UL 1741. Determine what level of
rapid PV shutdown is required for your juris
-
diction.
• The 2011 NEC and older editions do not
require PVRSS capability.
• The 2014 NEC requires rapid shutdown
only on the conductors leaving the PV
array.
• The 2017 and 2020 NEC require rapid
shutdown at the PV module level and on
the conductors leaving array.
PV Link is a PV rapid shutdown system equip
-
ment (PVRSE) component within a PVRSS. It
only provides rapid shutdown for the conduc
-
tors leaving the array. SnapRS devices are
required for PV module level rapid shutdown.
See
information.
Component Locations
PV Link Component Locations
Figure 2-5. Component Locations
A
Attachment Flange Slots
B
Grounding Terminals (sized for 1/4 in hard
-
ware)
C
REBus DC Nanogrid Output Negative (-)
Lead
D
REBus DC Nanogrid Output Positive (+)
Lead
E
PV Substring Input Negative (-) Lead
F
PV Substring Input Positive (+) Lead
G
MC4 Connectors
E
C
F
D
A
B
G
010023
Содержание PV Link
Страница 7: ...4 Installation Manual for PV Link and SnapRS This page is intentionally left blank...
Страница 13: ...10 Installation Manual for PV Link and SnapRS This page is intentionally left blank...
Страница 15: ...12 Installation Manual for PV Link and SnapRS This page is intentionally left blank...
Страница 23: ...20 Installation Manual for PV Link and SnapRS This page is intentionally left blank...
Страница 25: ...22 Installation Manual for PV Link and SnapRS This page is intentionally left blank...
Страница 27: ...24 Installation Manual for PV Link and SnapRS This page is intentionally left blank...