Generac Power Systems PV Link Скачать руководство пользователя страница 12

Installation Manual for PV Link and SnapRS

9

Section 3 Installation Design

Installation Design Worksheet

Use this worksheet to determine the maximum

number  of  PV  modules  of  a  given  type  that

can be connected to a PV Link.

NOTE: 

Fewer  PV  modules  can  be  used  as

long  as  the  minimum  MPPT  input  voltage  is

met.
1. Calculate an adjusted open circuit voltage

(VOC) for the module being installed using

the  applicable  NEC  cold  factor  from

Table 1: NEC Cold Factor

. 

NOTE: 

The  temperature  correction  factor

listed on the module nameplate can be used if

available.

2. Divide  the  PV  Link  Max  VOC  by  the

Adjusted  VOC  from  step  1  and  round

down  to  determine  the  number  of  panels

that can be connected in series to the PV

Link  without  exceeding  the  open-circuit

voltage limit.

3. Divide the PV Link VMP (Voltage at Maxi

-

mum Power) by the panel VMP and round

down  to  determine  the  number  of  panels

that can be connected in series to the PV

Link  without  exceeding  maximum  power

voltage. 

4. Compare the results from step 2 and step

3 and choose the smaller number. Round

down to the nearest integer and record it

below.  This  is  the  maximum  number  of

modules  of  this  type  that  can  be  con

-

nected to the PV Link given the specified

NEC cold factor.

Panel 

VOC

X

NEC Cold 

Factor

=

Adjusted 

VOC

PV Link 

Max VOC

÷

Adjusted

VOC

=

VOC Limit 

Result

420 V

PV Link 

Max VMP

÷

Panel 

VMP

=

VMP

Limit 

360 V

Maximum Panels per Substring

Table 1 - NEC Cold Factor

Minimum Temperature (°F)

NEC Cold 

Factor

Minimum Temperature (°C)

49 to 41

1.08

9 to 5

40 to 32

1.10

4 to 0

31 to 23

1.12

-1 to -5

22 to 14

1.14

-6 to -10

13 to 5

1.16

-11 to -15

4 to -4

1.18

-16 to -20

-5 to -13

1.20

-21 to -25

-14 to -22

1.21

-26 to -30

-23 to -31

1.23

-31 to -35

-32 and below

1.25

-36 and below

Содержание PV Link

Страница 1: ...d in a critical life support application Failure to adhere to this warning could result in death or serious injury Register your Generac product at https pwrfleet generac com 1 888 GENERAC 888 436 372...

Страница 2: ...ty to perform all safety checks to verify that all maintenance for safe operation is performed promptly and to have the equipment checked periodically by an ASD Normal maintenance service and replacem...

Страница 3: ...t Locations 7 Section 3 Installation Design 9 Installation Design Worksheet 9 Section 4 PVRSS Compliance Guidelines 11 Section 5 Mounting and Connecting 13 Installation Guidelines 13 Attachment and Gr...

Страница 4: ...erating technique that the manufacturer does not specifically recommend verify that it is safe for others and does not render the equipment unsafe Throughout this publication and on tags and decals af...

Страница 5: ...completed PV system meets the rapid shutdown functional requirements This equip ment must be installed according to the manu facturer s installation instructions 000191 DANGER Automatic start up Disco...

Страница 6: ...s injury equipment and property damage DANGER 000152 DANGER Electrocution Verify electrical system is properly grounded before applying power Failure to do so will result in death or serious injury 00...

Страница 7: ...4 Installation Manual for PV Link and SnapRS This page is intentionally left blank...

Страница 8: ...te maximum Maximum input current operating A F C 13 122 50 Maximum input current short circuit A 18 Maximum output current fault A 10 Maximum output voltage VDC 420 open circuit Nominal output REbus D...

Страница 9: ...rtant Information Figure 2 1 Serial Number Location SnapRS Date of Manufacture Refer to Figure 2 2 to locate the unit date of manufacture Record this information in Table 1 PV Link and SnapRS Importan...

Страница 10: ...The PV Link meets the ground fault protection requirements in NEC Article 690 41 B AFCI Information The PV Link is a Photovoltaic DC Arc Fault Circuit Protection Type 1 device that incorpo rates an in...

Страница 11: ...8 Installation Manual for PV Link and SnapRS SnapRS Component Locations Figure 2 6 Component Locations A Positive PV Connector B Negative PV Connector A B 010050...

Страница 12: ...ge limit 3 Divide the PV Link VMP Voltage at Maxi mum Power by the panel VMP and round down to determine the number of panels that can be connected in series to the PV Link without exceeding maximum p...

Страница 13: ...10 Installation Manual for PV Link and SnapRS This page is intentionally left blank...

Страница 14: ...eet 2017 and 2020 compliance 1 The 2017 and 2020 NEC requires the PVRSS initiator be located at a readily accessible location outside the building The DC disconnect under the PWRcell inverter cover la...

Страница 15: ...12 Installation Manual for PV Link and SnapRS This page is intentionally left blank...

Страница 16: ...TRIC SHOCK HAZARD DC OUTPUT CONDUCTORS MAY BE ENERGIZED REGARDLESS OF SUN EXPOSURE CAUTION RISK OF ELECTRIC SHOCK WHENTHE PHOTOVOLTAIC ARRAY IS EXPOSEDTO LIGHT IT SUPPLIES A DCVOLTAGETO EQUIPMENT COVE...

Страница 17: ...connections due to poor wiring practices 2014 NEC and Earlier Editions For NEC 2014 compliant systems connect the substring PV modules in series To install PV modules in series to PV Link 1 Connect t...

Страница 18: ...to the negative whip of the PV Module D 2 Connect the negative end of each SnapRS device to the positive whip of the next PV module in the series 3 Connect the PV string positive lead to PV Link B at...

Страница 19: ...ed in parallel each string must use the same number of the same type of PV modules and there must be one SnapRS device for each module in the array Figure 5 5 Parallel Input PV Array with SnapRS Devic...

Страница 20: ...ee the Generac PWRcell Inverter Installation Manual for instructions on commissioning the REbus system PVRSS Commissioning with SnapRS Devices To enable PV Link to work as a PVRSS with SnapRS devices...

Страница 21: ...high input The voltage detected with SnapRS devices disabled is higher than expected Verify the SnapRS devices are installed correctly Run the PVRSS self test SnapRS devices have not been installed or...

Страница 22: ...fault is detected the status message reads Arc Fault To conduct an AFD test 1 On the PWRcell inverter control panel use the left or right arrows to scroll to the page for the desired PV Link 2 Press t...

Страница 23: ...20 Installation Manual for PV Link and SnapRS This page is intentionally left blank...

Страница 24: ...ice If the PV Link is not operating as expected or if a PV Link error message appears on the Generac PWRcell Inverter control panel LCD display contact the nearest Independent Authorized Service Deale...

Страница 25: ...22 Installation Manual for PV Link and SnapRS This page is intentionally left blank...

Страница 26: ...the general health of a SnapRS device DMM Red to SnapRS DMM Black to SnapRS Resistance reads 300 k to 350 k Diode check reads 0 50 V to 0 55 V DMM Red to SnapRS DMM Black to SnapRS Resistance reads 1...

Страница 27: ...24 Installation Manual for PV Link and SnapRS This page is intentionally left blank...

Страница 28: ...ights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W29290...

Отзывы: