Fuel Conversion/Gas Connections
Installation Guidelines for 60 Hz PowerPact™
19
Fuel Line Sizing
Selecting the correct size fuel line is crucial to the proper
operation of the unit.
For further information on LP and NG installation
requirements, refer to NFPA 54 or ICC IFGC.
Measure the distance from the generator to the gas source.
IMPORTANT NOTE:
The generator should be plumbed
directly from the source, not off the end of an existing low
pressure system.
NOTE:
When measuring the pipe length, add 2.5 ft (0.76
m) for every angle or bend in the pipe to the overall
required length of pipe needed.
Natural Gas Pipe Sizing
See
. To determine correct NG pipe size, find
the desired pipe size in the first row of the table. The
number below is the maximum length, or run, (measured
in meters/feet) allowed for the selected pipe size. The
pipe sizes are measured by inside diameter (ID) to
include any fittings, valves (must be full flow), elbows,
tees or angles.
LP Vapor Pipe Sizing
IMPORTANT NOTE: The generator inlet size does not
dictate the size of gas pipe to be used!
See
. To determine correct LP Vapor pipe size,
find the desired pipe size in the first row of the table. The
number below is the maximum length, or run, (measured
in meters/feet) allowed for the selected pipe size.
The pipe sizes are measured by inside diameter (ID) to
include any fittings, valves (must be full flow), elbows,
tees or angles.
NOTE:
Pipe sizes are using a second stage regulator.
NOTE:
Consult with the LP fuel provider to determine
the minimum tank size required for the installation.
Vertical tanks, which are measured in pounds (or
kilograms), will not usually meet the minimum tank size
requirement. A 1050 lb (476 kg) vertical tank size
minimum is required
.
Summary
Incorrect gas pipe sizing is one of the most commonly
made mistakes. A properly sized gas pipe is critical to the
proper operation of the generator. Generator inlet size
cannot compensate for improper gas pipe size.
The gas supply and pipe MUST be sized at 100% Load
BTU / megajoule rating.
Table 5-1. Natural Gas Pipe Sizing
NG Pipe Size: 7.5 kW Units
Pipe Size
0.5 in (13 mm)
0.75 in (19 mm)
1 in (25 mm)
1.25 in (32 mm)
1.5 in (38 mm)
Maximum Run
10 ft. (3 m)
60 ft. (15 m)
200 ft. (16 m)
750 ft. (183 m)
—
For 5–7 in. of water column (9–13 mm mercury).
Table 5-2. LP Vapor Pipe Sizing
LP Vapor Pipe Size: 7.5 kW Units
Pipe Size
0.5 in (13 mm)
0.75 in (19 mm)
1 in (25 mm)
1.25 in (32 mm)
1.5 in (38 mm)
Maximum Run
35 ft. (11 m)
175 ft. (53 m)
600 ft. (183 m)
—
—
Содержание PowerPact 7.5 kW
Страница 14: ...Unpacking and Inspection 10 Installation Guidelines for 60 Hz PowerPact This page intentionally left blank ...
Страница 20: ...Generator Placement 16 Installation Guidelines for 60 Hz PowerPact This page intentionally left blank ...
Страница 40: ...Troubleshooting 36 Installation Guidelines for 60 Hz PowerPact This page intentionally left blank ...
Страница 44: ...Accessories 40 Installation Guidelines for 60 Hz PowerPact This page intentionally left blank ...
Страница 51: ......