Site Selection and Preparation
Installation Guidelines for 60 Hz PowerPact™
11
Section 3: Site Selection and Preparation
Site Selection
Figure 3-1. Installation Clearances
3 ft (0.91 m)
5 ft (1.52 m)
5 ft (1.52 m)
3 ft*
(0.91 m)
3 ft*
(0.91 m)
A
D
D
G
F
B
B
E
B
C
001751
001789
ID
Description
Comments
A
Top of generator
—
B
Front and end
clearance
Minimum clear distances cannot include shrubs, bushes, or trees.
* See
IMPORTANT NOTE
on next page.
C
Rear clearance
18 in (45.7 cm) minimum clearance per SwRI testing, labeling, and listing, unless state or
local codes dictate otherwise.
D
Windows and
openings
No operable windows, doors, or openings in the wall are permitted within 5 ft (1.52 m) from
any point of the generator.
E
Existing wall
One-hour fire rated walls allow closer placement of the generator set. Confirm before
installation.
F
Removable fence
Removable fence panels for servicing cannot be placed less than 3 ft (0.91 m) in front of the
generator.
G
Overhead clearance
5 ft (1.52 m) minimum distance from any structure, overhang, or projections from the wall.
DO NOT install under wooden decks or structures unless this distance is maintained.
Содержание PowerPact 7.5 kW
Страница 14: ...Unpacking and Inspection 10 Installation Guidelines for 60 Hz PowerPact This page intentionally left blank ...
Страница 20: ...Generator Placement 16 Installation Guidelines for 60 Hz PowerPact This page intentionally left blank ...
Страница 40: ...Troubleshooting 36 Installation Guidelines for 60 Hz PowerPact This page intentionally left blank ...
Страница 44: ...Accessories 40 Installation Guidelines for 60 Hz PowerPact This page intentionally left blank ...
Страница 51: ......