Section 3 — Operation
PM-GC
Under Speed (rpm)
Warning
Alarm
Units
Comment
Setpoint
Shutdown
N
Dialout
N
Common alarm
Y
Alarm log
N
Sensor failure detection
Y
Shutdown on sensor failure
Y
Delay
0.5 seconds
seconds
Active
Hold off
Hysteresis
20
RPM
Over Frequency (1/10ths Hz)
Setpoint
1/10ths Hz
Shutdown
Y
Dialout
Y
Common alarm
Y
Alarm log
Y
Sensor failure detection
N
Shutdown on sensor failure
N
Delay
0.2 seconds
seconds
Active
Hold off
Hysteresis
5
1/10ths Hz
Under Frequency (1/10ths Hz)
Setpoint
1/10ths Hz
Shutdown
N
Dialout
N
Common alarm
Y
Alarm log
N
Sensor failure detection
N
Shutdown on sensor failure
N
Delay
0.5 seconds
seconds
Active
Hold off
Hysteresis
5
1/10ths Hz
High Fuel level (%)
Warning
Alarm
Units
Disabled unless probe fitted
Setpoint
%
Shutdown
N
Dialout
N
Common alarm
N
Alarm log
N
Sensor failure detection
N
Shutdown on sensor failure
N
Delay
2 seconds
seconds
Active
Always
Hysteresis
2
%\
Low Fuel level (%)
Warning
Alarm
Units
Disabled unless probe fitted
Setpoint
%
Shutdown
N
Dialout
N
Common alarm
N
Alarm log
N
Sensor failure detection
N
Shutdown on sensor failure
N
Delay
2 seconds
seconds
Active
Always
Hysteresis
2
%