Section 3 — Operation
PM-GC
High Oil Temperature (Deg. F)
Warning
Alarm
Units
Comment
Setpoint
Shutdown
N
Y
Dialout
N
Y
Common alarm
Y
Y
Alarm log
N
Y
Sensor failure detection
Y
Y
Shutdown on sensor failure
Y
Y
Delay
0
0
seconds
Active
Hold of
Hold off
Hysteresis
2
2
Deg. F
High Coolant Temperature (Deg. F)
Setpoint
Shutdown
N
Y
Dialout
N
Y
Common alarm
Y
Y
Alarm log
N
Y
Sensor failure detection
Y
Y
Shutdown on sensor failure
Y
Y
Delay
0
0
seconds
Active
Hold off
Hold off
Hysteresis
2
2
Deg. F
Low Coolant Temperature (Deg. F)
Setpoint
Shutdown
N
Dialout
N
Common alarm
Y
Alarm log
N
Sensor failure detection
Y
Shutdown on sensor failure
Y
Delay
0
seconds
Active
Hold off
Hysteresis
2
2
Deg. F
Low Oil Pressure (psi)
Setpoint
Shutdown
N
Y
Dialout
N
Y
Common alarm
Y
Y
Alarm log
N
Y
Sensor failure detection
Y
Y
Shutdown on sensor failure
Y
Y
Delay
0
0
seconds
Active
Hold off
Hold off
Hysteresis
3
3
PSI
Low Coolant Level
Setpoint
Shutdown
Y
Dialout
Y
Common alarm
Y
Alarm log
Y
Sensor failure detection
Y
Shutdown on sensor failure
Y
Delay
0
Active
Always
Hysteresis
30