Owner’s Manual for Generator
Operation
Generator Output Connections
installation should be in compliance with the national
electrical code (NEC), state and local regulations.
The unit is equipped with connection lugs, located on the
lower portion of the control box behind the lug box door.
The lugs provide connection points for attachment of
external loads to the generator. A large decal on the
inside of the connection lug door details the proper
connections for selected voltages.
Connections to the lugs should be made by running the
power cables up through the opening in the bottom of the
box.
IMPORTANT NOTE: Do not make any connections
directly to the lugs without routing the cables
through the opening. Use a hex-wrench to tighten the
cable connections.
The connection lug door is equipped with safety interlock
switches that will trip the main circuit breaker and disable
the voltage regulator if the door is opened while the unit
is operating.
Figure 3-4. Generator Connection Lugs
A ground connection is located next to the connection
lugs. The unit must be connected to ground for proper
operating safety. The generator neutral is bonded to
ground when it is shipped from the factory. The bonding
plate will need to be removed when the generator is used
as a standby power source.
Fine Voltage Adjustment
Adjustment of the output voltage from the generator is
necessary to provide the correct voltage to the end of the
power line. Voltage adjustment can be carried out at any
time on the Voltage Adjust screen.
Figure 3-5. Voltage Adjust Screen
1.
With the unit running, press
.
2.
Press
. The voltages displayed will begin flashing.
3.
Use
▲
and
▼
to adjust the voltage.
4.
Press
to confirm the new voltage. The voltages
displayed will stop flashing.
(000157)
DANGER
Electrocution. Do not disable or modify the
connection box door safety switch. Doing so
will result in death or serious injury.
(000156)
DANGER
Electrocution. Before connections are made to
the unit, verify the main circuit breaker and
battery disconnect switch are OFF. Failure to do
so will result in death or serious injury.
(000237)
DANGER
Electrical backfeed. Use only approved switchgear to
isolate generator from the normal power source.
Failure to do so will result in death, serious injury,
and equipment damage.
(000155)
WARNING
Only a trained and licensed electrician should perform
wiring and connections to unit. Failure to follow proper
installation requirements could result in death, serious
injury, and damage to equipment or property.
Manual Mode
GEN
V
+ -
Voltage Adjust
- Press , voltage will begin flashing
- Use and arrows to adjust voltage
- Press to confirm new voltage. Numbers will stop flashing
V
L-N Average
L-L Average
V
480
277
002803
V
+ -