Installation and Operating Instructions 

MANUAL TRANSFER SWITCH - MODELS 6295-6296 and 6378-6380 

 

NOTE TO INSTALLER

:  Please leave this guide with the consumer for future reference. READ THIS MANUAL IN ITS ENTIRETY BEFORE ATTEMPTING TO INSTALL THIS EQUIPMENT

WARNING: 

 Generac

®

 transfer switches should be installed by a professional electrician familiar with electrical wiring and codes, and experienced in working with generators.  Generac accepts 

no responsibility for accidents, damages or personal injury caused by incorrect installation.  This transfer switch is intended for surface mounting INDOORS only.  Our transfer switches are UL 
listed to UL Standard 1008 and meet the criteria of National Electrical code Article 702.6 for Optional Standby Systems.  

CAUTION:  

If using the generator and transfer switch for larger 

appliances, such as electric water heaters, clothes dryers, electric ranges and small air conditioners, check the labels on the appliances to be sure they do NOT exceed the rating of the 
generator.  No appliance should have an amperage rating that exceeds the individual breaker rating in the transfer switch.  

CALIFORNIA PROPOSITION 65 WARNING

:  Engine exhaust and some 

of its constituents are known to the State of California to cause cancer, birth defects and other reproductive harm.  This product may contain or emit chemicals known to cause cancer, birth 

defects and other reproductive harm. 

 

Thank you for purchasing a Generac Transfer Switch to safely connect 

a portable generator to the load center in your home or business 

(single phase only) for standby power applications.  Product features 

include: 

 

 

Generator and Utility feeds mechanically interlocked to prevent dangerous utility or 
generator back feeding – thereby avoiding property damage and serious injury to 

electrical workers. 

 

Enclosure can be flush or surface mounted indoors. 

 

Pre-assembled wire harness with all wires clearly marked for easy connection to 
the load center. 

 

Transfer switch can be expanded to up to 16 circuits using standard 
interchangeable type circuit breakers. See Step 2, Section II. 

 

Accommodates GFCI and Arc-Fault breakers to meet the latest NEC requirements. 

 

Sufficient ground and neutral termination positions for all branch circuits 

 

Subfeed lugs provided to feed additional downstream panels or to expand beyond 
16 circuits. 

 

Dual wattmeters help you monitor and balance the loads on your generator, 

prolonging generator life. 

 

Safe generator connection – Install the Power Inlet Box in a convenience location 
outside for a quick cord connection to your generator.  

 

Accepts a Switched Neutral Kit (SNK).  See Page 2 Note on Neutral Bonded 
Generators above Table 1. 

Model 6295 Kit Shown 

 

What is Included in this Carton: 

 

Manual Transfer Switch with wire harness, conduit, fittings and wire connectors (10 or 12) 

 

Wire Harness, pre-assembled 

 

30 amp or 50 amp Aluminum Power Inlet Box (Models 6295-6296 only) 

 

10 Foot Power Cord (Models 6295-6296 only) 

 

Installation Manual and Warranty Registration card 

 

Tools and Items Needed for Installation:  

 

1/4” nut driver, 2-1/8” hole saw (if flush mounting) 

 

Screwdrivers, straight blade and Phillips 

 

Electric drill, drill bits, wallboard saw 

 

Wire cutter/stripper 

 

Safety eye goggles 

 

Anchors and screws to mount transfer switch to wall/wallboard

 

 

New, 2-pole 60 Amp or 100 Amp, 240V circuit breaker to install in main load center – same manufacturer as existing load center. 

 

4 gauge building wire and conduit to connect between power inlet box and transfer switch 

 

Compatible Circuit Breaker Types: 

 

Siemens/Murray QT, QPH, HQP, QPF (GFCI), QPHF, QFP, QE, QEH, QAF (Arc Fault), QP (Surge Protector) 

 

Cutler-Hammer Series BD, BR, BQ, GFC 

 

Challenger Type A, C, HAGF 

 

Square D Series HOM (Homeline) 

 

GE Series THQL 

 

Optional Items for Installation:  

 

Arc-fault, GFCI or Surge protection circuit breakers.  If Arc-fault, GFCI or Surge protection circuit breakers are used as the branch circuit protector in the main load 
center, they MUST be used in the manual transfer switch. You may be able to re-use your existing AFCI, GFCI and Surge protection circuit breakers in the manual 
transfer switch.  See list of compatible breakers. 

 

Wire, fittings and conduit to connect the Power Inlet Box to the transfer switch. 

 

White, green, black and red THHN or MTW wire, 10 AWG, 300V rated (if breaker configuration is modified or expanded. 

 

Switched Neutral Kit (SNK). If your portable generator has the neutral bonded to the frame of the generator AND 240V “full-power” receptacle is GFCI protected, you 
will need to install a SNK accessory with your transfer switch to avoid nuisance tripping of the GFCI breaker on the generator.  
 

Содержание GenTran 6295

Страница 1: ...rmination positions for all branch circuits Subfeed lugs provided to feed additional downstream panels or to expand beyond 16 circuits Dual wattmeters help you monitor and balance the loads on your ge...

Страница 2: ...be used in the transfer switch GFCI and AFCI breakers require an isolated neutral connected from the load to the GFCI or AFCI The load neutral needs to be connected with a wire nut to a 3 6 foot piece...

Страница 3: ...ound bar on the left and install the white neutral wire into neutral bar on the right Using provided wiring connectors connect black wire from PIB to black wiring going to Meter A Repeat for red wire...

Страница 4: ...Mount the power inlet box on the outside of the building in a convenient location minimum 24 above grade using the four holes provided in the back of the enclosure Use sealant around the anchoring scr...

Страница 5: ...2 pole 100 amp Utility Main and a 2 pole 60 amp Generator Main Protected by US Patent No US 6 861 596 B2 Generac Power Systems Inc Toll Free 1 888 GENERAC www generac com 0197000SBY 2012 Generac Powe...

Страница 6: ...du circuit de service ou de la g n ratrice qui peut tre dangereuse et viter ainsi tout d g t mat riel et de graves blessures des lectriciens Le bo tier peut tre encastr ou mont en surface l int rieur...

Страница 7: ...loc neutre commut SNK avec le commutateur de transfert TABLEAU 1 CARACT RISTIQUES Mod le 6295 et 6378 6296 et 6380 Nombre de circuits disponibles sur le commutateur de transfert 10 12 Nombre maximum d...

Страница 8: ...ter de faire passer le cordon de la g n ratrice travers une porte ou une fen tre 5 D cidez l endroit o vous installerez la bo te d entr e d alimentation sur un mur ext rieur au moins 5 pieds de toute...

Страница 9: ...u commutateur de transfert et gardez les vis D fon ez les fentes de montage sur les c t s du bo tier et fixez le la charpente avec des clous ou des vis v rifiez que le bord avant du bo tier vient suff...

Страница 10: ...limentation dans la bo te d entr e d alimentation ARR TEZ tous les disjoncteurs du commutateur de transfert 3 D marrez la g n ratrice l ext rieur en suivant les proc dures d crites dans le manuel du p...

Страница 11: ...6296 et 6380 a un disjoncteur bipolaire de 100 amp res pour l installation de service principaleet un disjoncteur bipolaire de 60 amp res pour la g n ratrice Prot g par le brevet am ricain no US 6 86...

Страница 12: ...s electricistas La caja puede instalarse a ras o sobre una superficie en interiores Mazo de cables prearmado con todos los cables marcados claramente para una f cil conexi n al centro de carga El inte...

Страница 13: ...ida la garant a del generador se debe instalar un accesorio de kit neutral con interruptor SNK con su interruptor de transferencia TABLA 1 ESPECIFICACIONES Modelo 6295 y 6378 6296 y 6380 Cantidad de c...

Страница 14: ...caja de entrada de cables el ctricos Usar el cable del generador para conectar su generador a la caja de entrada de cables el ctricos en el exterior Ya sea que su centro de carga se encuentre en un s...

Страница 15: ...el centro de carga ENCIENDA todos los disyuntores de circuitos derivados en ambos paneles ENCIENDA el conducto PRINCIPAL DEL SERVICIO EL CTRICO en el interruptor de transferencia Verifique que la ele...

Страница 16: ...uctos de ventilaci n o cualquier otra abertura El Mon xido de carbono CO de un generador es mortal y puede matarlo en minutos Lea y siga todas las instrucciones del generador antes de usarlo A Pasar d...

Страница 17: ...y 6380 incluyen un conducto principal de servicio el ctrico de 2 polos y 100 amp y un conducto principal del generador de 2 polos y 60 amp Protegido por la Patente de los Estados Unidos N US 6 861 596...

Отзывы: