Oil Filter Heater Kit

Model G0071020

Intended for HSB units 2013–Present

Two lead wires deliver 240V electrical power to the heater from
the N1 and N2 terminals at the customer connection panel.  A
Y-harness, supplied with the heater, provides a second
connection point for an optional battery heater.

IMPORTANT NOTE: 

The engine must be filled with synthetic

5W-30 engine oil before installing cold weather heating
accessories. Replace the engine oil if necessary before
proceeding.

NOTE: 

It is acceptable to operate the engine with synthetic oil

during the 25 hour break-in period if cold weather accessories
are being installed at the time of generator installation.

Preparing for Installation

Before performing any maintenance, prevent the generator
from accidental startup:

1.

Lift the lid, turn the generator OFF, and allow the unit to
cool completely.

2.

Verify that the unit is placed in OFF mode.

3.

Turn off the normal utility power supply to the transfer switch.
• In service rated transfer switches, turn the main breaker OFF.
• In non-service-rated switches, turn power feeder breaker OFF.

NOTE: 

The T1, N1 and N2 fuses could be removed from the

transfer switch by an electrical contractor instead of turning off
the normal power circuit breaker.

4.

With the generator shut down, remove controller fascia
(2013–2015 units) or intake side panel (2016 and newer
units), front panel, and 7.5A DC fuse.

5.

Move the main line circuit breaker (generator disconnect)
to the OFF (open) position.

6.

Remove the 7.5 amp fuse from the control panel.

7.

See 

Figure 1 or Figure 2. 

Remove the customer

connection panel cover (A).

Figure 1.  Removing Customer Connection Panel Cover 

(2016–Present)

(000100a)

WARNING

Consult Manual. Read and understand manual
completely before using product. Failure to 
completely understand manual and product
could result in death or serious injury.

(000182a)

WARNING

Equipment damage. Only qualified service personnel may 
install, operate, and maintain this equipment. Failure to follow 
proper installation requirements could result in death, serious 
injury, and equipment or property damage.

(000139)

WARNING

Risk of burns. Allow engine to cool before 
draining oil or coolant. Failure to do so could 
result in death or serious injury.

(000210)

WARNING

Skin irritation. Avoid prolonged or repeated contact with  
used motor oil. Used motor oil has been shown to cause  
skin cancer in laboratory animals. Thoroughly wash  
exposed areas with soap and water.

Automatic start-up. Disconnect normal power source 
and render unit inoperable before working on unit. 
Failure to do so will result in death or serious injury.

(000236)

DANGER

002917

A

Содержание G0071020

Страница 1: ...r instead of turning off the normal power circuit breaker 4 With the generator shut down remove controller fascia 2013 2015 units or intake side panel 2016 and newer units front panel and 7 5A DC fuse...

Страница 2: ...grommet D If the empty Y harness socket E will not be connected to a battery heater coil the wires and secure with a plastic wire tie Secure all wires with plastic wire ties at least 0 5 in 1 cm away...

Страница 3: ...mage Use tie wraps where necessary 2 Install customer connection panel cover 3 Return the utility power supply to the transfer switch For service rated transfer switches turn the main breaker ON For n...

Страница 4: ...star en OFF el disyuntor de alimentaci n normal 4 Con el generador apagado quite la fascia del controlador unidades fabricadas entre 2013 y 2015 o el panel de entrada de aire lateral unidades fabricad...

Страница 5: ...e D Si el z calo vac o del arn s en Y E no se conectar a un calentador de bater a enrolle los cables y f jelos con un amarre de cables de pl stico Fije todos los cables con amarres de cables de pl sti...

Страница 6: ...2 Instale la cubierta del panel de conexiones del cliente 3 Devuelva el suministro de alimentaci n del servicio p blico al interruptor de transferencia En los interruptores de transferencia para acome...

Страница 7: ...s le g n rateur l arr t d posez la b che de protection du contr leur sur les appareils fabriqu s entre 2013 et 2015 ou le panneau lat ral d admission sur les appareils fabriqu s depuis 2016 le panneau...

Страница 8: ...nts du client D Si aucun chauffe batterie ne sera branch sur la prise non utilis e du faisceau de fils en Y E roulez les fils et fixez les l aide d un fil d attache en plastique Fixez tous les fils av...

Страница 9: ...t en place 3 R tablissez l alimentation du r seau public au commutateur de transfert Si vous utilisez des commutateurs de transfert automatiques cot s pour entr e de service placez le disjoncteur prin...

Страница 10: ...1 G0071020 HSB 2013 240 N1 N2 Y 5W 30 25 1 2 OFF 3 T1 N1 N2 4 2013 2015 2016 7 5 A 5 OFF 6 7 5 7 1 2 A 1 2016 000100a 000182a 000139 000210 000236 002917...

Страница 11: ...2 2 2013 2015 9 1 2 3 3 9 3 Y B 4 4 Y C 4 9 5 5 D Y E 1 0 5 5 9 6 11 22 1 2 6 6 11 22 3 Y B 4 7 Y C 002916 002774 B 002775 C 002776 D E 002779 B...

Страница 12: ...10 N1 N2 1 2 3 4 T1 N1 N2 5 2013 2015 2016 7 5 6 7 ON 8 AUTO 002826 C 002780 D E 002781 000135 10000003502 B 14 07 2017 Generac Power Systems Inc 2016 Generac Power Systems Inc Generac Power Systems I...

Отзывы: