Installation, Tests, & Troubleshooting

Owner’s/Installation Manual for SMM

11

NOTE: 

Use at least 167 °F (75 °C) rated wire and gauge

per installation instructions. See 

Table 3-1

 for recom-

mended wire size based on load current.

2.

Run line supply wires per applicable NEC code
articles for wiring method selected.

3.

Run load wires per applicable NEC code articles
for wiring method selected.

4.

See 

Figure 3-3

. Connect line supply wiring (A, B)

to line side of SMM contactor field terminals.
Tighten field terminals to 25 

in-lbs

 (2.8 Nm).

5.

Connect load supply wiring (C, D) to load side of
SMM contactor field terminals.

NOTE: 

If neutral (E) and ground (F) wires are included,

connect inside SMM using a listed termination device.

The unit is now ready to configure, apply power, and
perform testing.

Setting Priorities

High priority 240 VAC loads should be set to the highest
priorities so those loads recover first in the event of
generator overload. 

NOTE: 

The highest priority, and first load to activate, is

Priority 1. The last load to activate is Priority 8. 

Setting priority determines timing for three scenarios:

Order in which loads recover

Delay time until power returns during an outage

Delay time for post load shed recovery

An example configuration is shown below. Configurations
will vary depending on customer prioritization of loads:

1.

Set the priority of each SMM as desired (using the
example configuration for reference).

2.

Apply priority decal in a suitable location on electri-
cal panel to record chosen priority designations.

3.

Record priorities on decal.

Tests

Utility Test

1.

Turn utility power ON and enable all module feed-
ing circuits.

2.

Verify LED begins to flash at one second intervals.

3.

All contactors will close after five minutes. LED will
illuminate and remain ON.

NOTE: 

The five minute delay allows magnetism to dissi-

pate from the air conditioner compressor. This allows
easier starting and eliminates potential for reverse com-
pressor operation.

Installation Summary

Install cover on electrical panel.

Install covers on modules.

Table 3-1.  Recommended Wire Sizes

Temperature rating of conductor: 167 ºF (75 ºC)
Conductor types (must be copper): 
RHW, THHW, THW, THWN, XHHW, USE, ZW

Size AWG

Maximum Current Rating

14

15A

12

20A

10

30A

8

50A*

* 40A for Type NM cable

Priority 1 - Baseboard heat

Priority 5 - Non-essential circuits

Priority 2 - Air conditioner

Priority 6 - Pool pump or hot tub

Priority 3 - Range

Priority 7 - Other circuits

Priority 4 - Clothes Dryer

Priority 8 - Other circuits

Содержание G007000-0

Страница 1: ...RAC COM 1 888 GENERAC 1 888 436 3722 Para espa ol visita http www generac com service support product support lookup Pour le fran ais visiter http www generac com service support product support looku...

Страница 2: ...ii Owner s Installation Manual for SMM 000393a WARNING CANCER AND REPRODUCTIVE HARM www P65Warnings ca gov...

Страница 3: ...ation Considerations 3 Smart Management Module SMM 3 SMM and Carton Contents 4 Setting Lockout 5 Jumper Locations 5 Section 3 Installation Tests Troubleshooting Electrical Specifications 9 Enclosure S...

Страница 4: ...Table of Contents iv Owner s Installation Manual for SMM This page intentionally left blank...

Страница 5: ...es The manufacturer cannot anticipate every possible cir cumstance that might involve a hazard The alerts in this manual and on tags and decals affixed to the unit are not all inclusive If using a pro...

Страница 6: ...Introduction and Safety 2 Owner s Installation Manual for SMM This page intentionally left blank...

Страница 7: ...e SACM as the top priorities then use additional SMMs as the remaining priorities To reduce the loads returned to the generator all at once it is best to set the SMM priorities to follow after the las...

Страница 8: ...sitions are LOCKOUT LOAD ON GENER ATOR enabled and LOCKOUT DISABLED See Table 2 2 NOTE Recovery time is based on priority dial settings See Table 2 1 Test Button C Disables contactor output for a spec...

Страница 9: ...ped with two movable jumpers 2 Jumper locations are indicated on the diagram 3 Frequency Jumper default for 60 Hz 4 Mode Selector Jumper identified on control board as Lock Out Jumper position A is de...

Страница 10: ...erator mode or during a first time utility power up for five minutes of initial operation Lockout 30 minutes 3 second flash 3 On 3 Off Generator Module detected an overload while trying to recover fro...

Страница 11: ...the l oad Module now in lockout recovery NO YES Have load shed recovery time a nd module priority time elapsed 1 YES NO Was lockout recovery operation successful YES NO YES NO Notes 1 Refer to the Pr...

Страница 12: ...General Information and Setup 8 Owner s Installation Manual for SMM This page intentionally left blank...

Страница 13: ...ditional information Mounting Instructions Recommended installation is near the electrical panel or appliance load The enclosure has a NEMA 3R rating and can be mounted indoors or outdoors It provides...

Страница 14: ...rce and load lines to transfer switch and SMM NOTE Suitable conduit fittings must be installed in knockout openings when running supply and load wires Height in mm H1 6 17 156 8 H2 2 36 60 Width in mm...

Страница 15: ...ntil power returns during an outage Delay time for post load shed recovery An example configuration is shown below Configurations will vary depending on customer prioritization of loads 1 Set the prio...

Страница 16: ...time delay see Table 2 1 for unit to enable output Load not powered LED flashing 3 second interval This load overloaded the generator while attempting recovery from a shed It is in a 30 minute lockou...

Страница 17: ...Installation Tests Troubleshooting Owner s Installation Manual for SMM 13 This page intentionally left blank...

Страница 18: ...Installation Tests Troubleshooting 14 Owner s Installation Manual for SMM This page intentionally left blank...

Страница 19: ......

Страница 20: ...rights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W2929...

Отзывы: