Before connecting wiring cables to terminals, remove

any surface oxides from the cable ends with a wire

brush.  If ALUMINUM conductors are used, apply joint

compound to conductors.  After tightening terminal

lugs, carefully wipe away any excess joint compound.
All power cables should enter the switch next to trans-

fer mechanism terminals.
Connect power source load conductors to clearly

marked transfer mechanism terminal lugs as follows

(Figure 2.3).
1. Connect NORMAL (utility) power source cables to

switch terminals N1 and N2.

2. Connect STANDBY source power cables to transfer

switch terminals E1 and E2.

3. Connect customer LOAD leads to switch terminals

T1 and T2.

Conductors must be properly supported, of approved

insulative qualities, protected by approved conduit, and

of the correct wire gauge size in accordance with appli-

cable codes.
Tighten the wire into lugs to the following torque:
• 100 Amp Switch:  50 Inch-Pounds
Make sure to maintain proper electrical 1/2 inch clear-

ance between live metal parts and grounded metal.

2.5 CONNECTING 

START 

CIRCUIT

WIRES

Control system interconnections (Figure 2.3) consist of

UTILITY 1 and 2. LOAD 1 and 2; and leads 23 and 194.

Control system interconnection leads must be run in a

conduit that is separate from the AC power lead.

Recommended wire gauge sizes for this wiring depends

on the length of the wire, as recommended below:

Section 2 — Installation

Generac 100 Amp Transfer Switch

Figure 2.3 — Transfer Switch Interconnections (Drawing No. C3921)

MAXIMUM WIRE LENGTH

RECOMMENDED WIRE

SIZE

460 feet (140m)

No. 18 AWG.

730 feet (223m)

No. 16 AWG.

1,160 feet (354m)

No. 14 AWG.

Содержание 4678-1

Страница 1: ...Owner s Manual 100 Amp V Type Transfer Switch Models 9227 2 4678 1 This manual should remain with the unit...

Страница 2: ...hazard GENERAL HAZARDS Any AC generator that is used for backup power if a NORMAL utility power source failure occurs must be isolated from the NORMAL utility power source by means of an approved tran...

Страница 3: ...e insulative mats over a dry wood platform Work on this equipment only while standing on such insulative mats Never work on this equipment while physically or mentally fatigued Keep the transfer switc...

Страница 4: ...iates re transfer back to NORMAL power source After this re transfer the controller signals to open the start circuit to the generator which shuts down the engine The controller is then armed and read...

Страница 5: ...tortion level all mounting points If nec essary use washers behind mounting holes to level the unit 2 4 CONNECTING POWER SOURCE AND LOAD LINES Make sure to turn OFF both the normal Utility and standby...

Страница 6: ...rly supported of approved insulative qualities protected by approved conduit and of the correct wire gauge size in accordance with appli cable codes Tighten the wire into lugs to the following torque...

Страница 7: ...ir operation Do not attempt manual operation of the transfer switch until after all power voltage supplies to the switch have been turned off Failure to turn off power voltage supplies may result in d...

Страница 8: ...equires adjustment If no load frequen cy is correct but voltage is not the voltage regu lator may require adjustment 3 4 GENERATOR TESTS UNDER LOAD 1 Set the generator s main circuit breaker to its OF...

Страница 9: ...7 Generac Power Systems Inc Section 4 Notes Generac 100 Amp Transfer Switch...

Страница 10: ...LOSING ALL CONTACTS SHOWN WITH TRANSFER SWITCH IN UTILITY TR 194 NOTE 194 A 23 23 B VR1 C1 A XA1 B B XB1 E1 6 9 205 126 TR 1 7 N2A E2 LEGEND F2 F4 N2 T2A VR2 T1A F3 T1 T2 N2A E2 N1 N1 N2 F1 F2 T2 T1 N...

Страница 11: ...28 77052 2 LUG 0 25 TAB 10 SCREW 29 81238 1 HARNESS WIRE 30 63378 2 CABLE TIE HOLDER 31 28739 2 TIE WRAP 4 32 75353 1 DECAL UL COMPONENT RECOGNITION 33 A9517 1 DECAL MANUAL OPERATION 34 A2595 1 DECAL...

Страница 12: ...replacement part s will void the warranty in its entirety 5 Damage related to rodent infestation 6 Failures due but not limited to normal wear and tear accident misuse abuse negligence or improper in...

Отзывы: