Generac Power Systems 4678-1 Скачать руководство пользователя страница 2

Generac

®

Power Systems, Inc.

Generac cannot possibly anticipate every possible cir

cumstance that might involve a hazard. The warn-

ings in this manual, and on tags and decals 

affixed to the unit are, therefore, not all-inclusive. If

you use a procedure, work method or operating tech-

nique Generac does not specifically recommend, you

must satisfy yourself that it is safe for you and others.

You also must make sure the procedure, work

method or operating technique that you choose does

not render the transfer switch unsafe.
Throughout this publication, and on tags and 

decals affixed to the generator, DANGER, WARNING,

CAUTION and NOTE blocks are used to alert you to

special instruction about a particular operation that

may be hazardous if performed incorrectly or care-

lessly. Observe them carefully. Their definitions are

as follows:

After this heading, you can read instructions that,
if not strictly complied with, will result in personal
injury or property damage.

After this heading, you can read instructions that, 
if not strictly complied with, may result in personal
injury or property damage.

After this heading, you can read instructions that, if
not strictly complied with, could result in damage to
equipment and/or property.

NOTE:

After this heading, you can read explanatory

statements that require special emphasis.

These safety warnings cannot eliminate the hazards

that they indicate. Common sense and strict compli-

ance with the special instructions while performing the

service are essential to preventing accidents.
Four commonly used safety symbols accompany the

DANGER, WARNING and CAUTION blocks. The type

of information each indicates follows:

This symbol points out important safety informa-
tion that, if not followed, could endanger personal
safety and/or property of you and others.

This symbol points out potential explosion hazard.

This symbol points out potential fire hazard.

This symbol points out potential electrical shock
hazard.

GENERAL HAZARDS

• Any AC generator that is used for backup power if

a NORMAL (utility) power source failure occurs,

must be isolated from the NORMAL (utility) power

source by means of an approved transfer switch.

Failure to properly isolate the NORMAL and

STANDBY power sources from each other may

result in injury or death to electric utility workers,

due to backfeed of electrical energy.

• Improper or unauthorized installation, operation,

service or repair of the equipment is extremely

dangerous and may result in death, serious per-

sonal injury, or damage to equipment and/or per-

sonal property.

• Extremely high and dangerous power voltages are

present inside an installed transfer switch.  Any

contact with high voltage terminals, contacts or

wires will result in extremely hazardous, and pos-

sibly LETHAL, electric shock.  DO NOT WORK ON

THE TRANSFER SWITCH UNTIL ALL POWER

VOLTAGE SUPPLIES TO THE SWITCH HAVE

BEEN POSITIVELY TURNED OFF.

• Competent, qualified personnel should install,

operate and service this equipment.  Adhere strict-

ly to local, state and national electrical and build-

ing codes.  When using this equipment, comply

with regulations the National Electrical Code

(NEC) and Occupational Safety and Health

Administration (OSHA) have established.

• Never handle any kind of electrical device while

standing in water, while barefoot, or while hands

or feet are wet. DANGEROUS ELECTRICAL

SHOCK MAY RESULT.

!

!

!

DANGER

Important Safety Instructions

Read the following information carefully before attempting to install, operate or service this

equipment.  Also read the instructions and information on tags, decals, and labels that may

be affixed to the transfer switch.  Replace any decal or label that is no longer legible.
DANGER!  Connection of a generator to an electrical system normally supplied by an elec-

tric utility shall be by means of a double throw switch so as to isolate the electric system

from utility distribution system when the generator is operating (NEC 701).  Failure to iso-

late electric system by these means results in damage to generator and may result in injury

or death to utility workers due to backfeed of electrical energy.

!

!

!

!

Содержание 4678-1

Страница 1: ...Owner s Manual 100 Amp V Type Transfer Switch Models 9227 2 4678 1 This manual should remain with the unit...

Страница 2: ...hazard GENERAL HAZARDS Any AC generator that is used for backup power if a NORMAL utility power source failure occurs must be isolated from the NORMAL utility power source by means of an approved tran...

Страница 3: ...e insulative mats over a dry wood platform Work on this equipment only while standing on such insulative mats Never work on this equipment while physically or mentally fatigued Keep the transfer switc...

Страница 4: ...iates re transfer back to NORMAL power source After this re transfer the controller signals to open the start circuit to the generator which shuts down the engine The controller is then armed and read...

Страница 5: ...tortion level all mounting points If nec essary use washers behind mounting holes to level the unit 2 4 CONNECTING POWER SOURCE AND LOAD LINES Make sure to turn OFF both the normal Utility and standby...

Страница 6: ...rly supported of approved insulative qualities protected by approved conduit and of the correct wire gauge size in accordance with appli cable codes Tighten the wire into lugs to the following torque...

Страница 7: ...ir operation Do not attempt manual operation of the transfer switch until after all power voltage supplies to the switch have been turned off Failure to turn off power voltage supplies may result in d...

Страница 8: ...equires adjustment If no load frequen cy is correct but voltage is not the voltage regu lator may require adjustment 3 4 GENERATOR TESTS UNDER LOAD 1 Set the generator s main circuit breaker to its OF...

Страница 9: ...7 Generac Power Systems Inc Section 4 Notes Generac 100 Amp Transfer Switch...

Страница 10: ...LOSING ALL CONTACTS SHOWN WITH TRANSFER SWITCH IN UTILITY TR 194 NOTE 194 A 23 23 B VR1 C1 A XA1 B B XB1 E1 6 9 205 126 TR 1 7 N2A E2 LEGEND F2 F4 N2 T2A VR2 T1A F3 T1 T2 N2A E2 N1 N1 N2 F1 F2 T2 T1 N...

Страница 11: ...28 77052 2 LUG 0 25 TAB 10 SCREW 29 81238 1 HARNESS WIRE 30 63378 2 CABLE TIE HOLDER 31 28739 2 TIE WRAP 4 32 75353 1 DECAL UL COMPONENT RECOGNITION 33 A9517 1 DECAL MANUAL OPERATION 34 A2595 1 DECAL...

Страница 12: ...replacement part s will void the warranty in its entirety 5 Damage related to rodent infestation 6 Failures due but not limited to normal wear and tear accident misuse abuse negligence or improper in...

Отзывы: