Section 4 — Troubleshooting
Guardian Air-cooled Generators
4.2 INSTALLATION
CHECKLIST
BATTERY INSTALLATION
❏
Battery is connected properly.
❏
Recommended battery is installed.
❏
Cables are clean and tight.
❏
Terminals are coated with anti-corrosion grease,
and terminal covers are positioned.
FUEL SYSTEM
❏
Complies with local and NFPA codes.
❏
Fuel is connected and checked for leaks.
❏
Correct fuel pressure (11-14 inches of water
(0.6 psi) at all load ranges).
❏
Load block adjusted for maximum power for
natural gas fuel.
LOCATION
❏
Unit is fastened to the appropriate mounting pad.
❏
Louvers are free from obstruction.
❏
Exhaust is clear of flammable objects and debris.
ELECTRICAL CONNECTIONS
❏
Complies with local code requirements and all
National Electrical Codes.
❏
Utility is connected and present.
❏
Transfer switch is connected.
❏
All wires running outside of the generator are in
NEC-approved conduit. *Note: Utility wires and
transfer switch control wires must be in separate
conduit.
❏
Unit is grounded to an approved earth ground.
COOLING AND VENTILATING
❏
All inlets and outlets are free from obstruction.
See Figure 1.4 and Figure 1.5.
OTHER
❏
Verify that the unit is filled to the proper level with
the proper break-in oil. Adjust as required.
❏
Notify owner that the “Break-in Procedure” should
be performed. Refer the owner to the
Owner’s
Manual
shipped with the unit.
OPTIONS AND ACCESSORIES
❏
Control board is configured properly. See
Section 1.15.
❏
Remote alarm is installed if desired. See
Section 2.6.
❏
Remote start is installed if desired. See
Section 2.6.
◆
◆
◆
◆
◆
◆
◆