1.17 THE BATTERY

Servicing of the battery is to be performed or super-

vised by personnel knowledgeable of batteries and

the required precautions. Keep unauthorized person-

nel away from batteries.
When replacing the battery, use the following type of

battery: Group 26/26R 12-volt battery with a rating of

350 cold-cranking amps at -17.8º C (0º F) minimum.

When using a maintenance-free battery, it is not nec-

essary to check the specific gravity or electrolyte level.

Have these procedures performed at the intervals

specified in the 

Owner’s Manual

“Service Schedule.”

A negative ground system is used. Battery connec-

tions are shown on the wiring diagrams. Make sure

the battery is correctly connected and terminals are

tight. Observe battery polarity when connecting the

battery to the generator set.

NOTE:

Damage will result if the battery connections are
made in reverse.

Your generator is equipped with a battery trickle
charger that is active when your unit is set up for
automatic operation. The trickle charger is
designed to help extend the life of your battery by
maintaining the battery when the unit is 
not running.

Do not dispose of the battery in a fire. The 
battery is capable of exploding.

A battery presents a risk of electrical shock 
and high short circuit current. The following
precautions are to be observed when working
on batteries:

• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the 

battery; and

• Disconnect charging source prior to connecting or dis-

connecting battery terminals.

Do not open or mutilate the battery. Released
electrolyte has been known to be harmful to
the skin and eyes, and to be toxic.

The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically
conductive and corrosive. The following 
procedures are to be observed:

• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off

immediately with water;

• Where electrolyte contacts the eyes, flush 

thoroughly and immediately with water and seek
medical attention; and

• Spilled electrolyte is to be washed down with an

acid neutralizing agent. A common practice is to
use a solution of 1 pound (500 grams) bicarbonate
of soda to 1 gallon (4 liters) or water. The bicar-
bonate of soda solution is to be added until the
evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.

Lead-acid batteries present a risk of fire
because they generate hydrogen gas. The 
following procedures are to be followed:

• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from your body before

touching the battery by first touching a grounded
metal surface.

Be sure the Auto/Off/Manual switch is set to
the OFF position before connecting the battery
cables. If the switch is set to AUTO or MANUAL,
the generator can crank and start as soon as
the battery cables are connected.

Be sure the utility power supply is turned off,
or sparking may occur at the battery posts as
you attach the cables and cause an explosion.

Section 1 — Installation

Guardian Air-cooled Generators

Содержание 04077-01, 04109-1, 04079-1, 00

Страница 1: ...ustment Manual Air cooled Prepackaged Standby Generators Models Nonsound Attenuated Non SA 04077 1 6 kW 04109 1 8 kW 04079 1 10 kW Sound Attenuated SA 00789 1 8 kW 00844 1 8 kW ONLY QUALIFIED ELECTRIC...

Страница 2: ...s symbol points out important safety informa tion that if not followed could endanger personal safety and or property of you and others This symbol points out potential explosion hazard This symbol po...

Страница 3: ...5 1 16 Grounding the Generator 15 1 17 The Battery 16 1 17 1 Battery Installation 17 1 18 The Fuse 17 1 19 Post Installation Inspection 17 Section 2 Operation 18 2 1 Using the Auto Off Manual Switch 1...

Страница 4: ...sufficient concentrations can cause unconsciousness or even death This exhaust sys tem must be installed properly in strict compli ance with applicable codes and standards Following installation you m...

Страница 5: ...ediate medical help Never wear jewelry when working on this equip ment Jewelry can conduct electricity resulting in electric shock or may get caught in moving com ponents causing injury FIRE HAZARDS F...

Страница 6: ...tion 85 John Street New York N Y 10038 7 AGRICULTURAL WIRING HANDBOOK available from the Food and Energy Council 909 University Avenue Columbia MO 65201 8 ASAE EP 3634 INSTALLATION AND MAINTE NANCE OF...

Страница 7: ...s it may shift on lifting pipes during transportation which may result in injury The generator was not designed to be lifted by its roof Use the lifting holes or brackets provided near the base of the...

Страница 8: ...st spark can ignite such fuels and cause an explosion No leakage of fuel is permitted Natural gas which is lighter than air tends to collect in high areas LP gas is heavier than air and tends to settl...

Страница 9: ...rete pad Remove the packing material from the unit and unbolt the two 4 inch by 4 inch wooden blocks from the underside of the mounting base Plug the holes with the plugs provided Prepare the installa...

Страница 10: ...8 Generac Power Systems Inc Figure 1 4 Generator and Transfer Switch Mounting Dimensions 6 kW 8 kW and 10 kW Non SA Section 1 Installation Guardian Air cooled Generators...

Страница 11: ...Generac Power Systems Inc 9 Figure 1 4 Continued Section 1 Installation Guardian Air cooled Generators...

Страница 12: ...10 Generac Power Systems Inc Figure 1 5 Generator Mounting Dimensions Sound Attenuated Section 1 Installation Guardian Air cooled Generators...

Страница 13: ...ty is supply ing 120 240 volt single phase electrical service 1 9 TOTAL CIRCUIT ISOLATION METHOD If essential electrical loads cannot be grouped togeth er and wired into an emergency distribution pane...

Страница 14: ...e a length of flexible conduit between the generator and any rigid conduit NOTE See also Emergency Circuit Isolation Method Section 1 8 and Total Circuit Isolation Method Section 1 9 on Page 11 1 11 1...

Страница 15: ...Section 1 Installation Guardian Air cooled Generators Figure 1 10 Interconnection Diagram for Single Phase Power System Sound Attenuated Figure 1 9 Interconnection Diagram for Single Phase Power Syste...

Страница 16: ...l module circuit board in the control panel Refer to the Operation section of this manual 1 13 CONTROL CIRCUIT INTERCONNECTIONS For 6 kw 8 kW and 10 kW units not including sound attenuated these inter...

Страница 17: ...dip switches see Figure 1 12 which may be set up differently during installation 1 Dip switch 1 When in the ON position the board requires 20 Vac from the step down transformer to the control board t...

Страница 18: ...of the battery and Disconnect charging source prior to connecting or dis connecting battery terminals Do not open or mutilate the battery Released electrolyte has been known to be harmful to the skin...

Страница 19: ...black battery cable from frame ground to the battery post indicated by a nega tive NEG or Figure 1 14 Battery Cable Connections NOTE With the battery installed and utility power source voltage availab...

Страница 20: ...el or during the normal exercise cycle To prevent possible injury that might be caused by such sudden starts always set the switch to OFF and remove the fuse before working on or around the generator...

Страница 21: ...ts timing E Retransfer Time Delay This timer runs for about 15 SA six seconds At end of a 15 second SA six second delay circuit board action de energizes transfer relay in the transfer switch Retransf...

Страница 22: ...uipped with the following systems that protect it against potentially damaging conditions 1 Low Oil Pressure Sensor 2 High Temperature Sensor 3 Overcrank 4 Overspeed On sound attenuated models there a...

Страница 23: ...should be wired to the unit by a qualified electrician or Generac Guardian Authorized Dealer 2 Remote Common Alarm This allows for an alarm light horn etc to activate when any fault has occurred Lines...

Страница 24: ...r switch and load circuit rat ings turn OFF the utility power supply to the transfer switch 5 Set the generator s main circuit breaker to its OFF or open position Initial tests will be con ducted at n...

Страница 25: ...ing the means provided such as a util ity main line circuit breaker 4 Set the Auto Off Manual switch to AUTO The sys tem is now ready for automatic operation 5 Turn OFF the utility power supply to the...

Страница 26: ...t to obtain 62 Hertz at no load 7 When frequency is correct at no load check the AC voltage reading If voltage is incorrect the volt age regulator may require adjustment Figure 3 1 6 kW Engine Governo...

Страница 27: ...emove the roof to adjust the voltage regulator on nonsound attenuated units Figure 3 4 Voltage Adjustment Potentiometer NOTE The voltage regulator is housed in the generator s control panel The regula...

Страница 28: ...s disconnected and then reconnected The exerciser WILL NOT work if dip switch 2 Remote Not Auto is ON 3 10 2 SOUND ATTENUATED UNITS The generator will start and exercise once every seven days During t...

Страница 29: ...4 Replace control board The Auto Off Manual switch 1 Defective Auto Off Manual 1 Replace switch is set to OFF but the engine switch continues to run 2 Auto Off Manual switch 2 Check wiring and connect...

Страница 30: ...LECTRICAL CONNECTIONS Complies with local code requirements and all National Electrical Codes Utility is connected and present Transfer switch is connected All wires running outside of the generator a...

Страница 31: ...Generac Power Systems Inc 29 Section 5 Notes Guardian Air cooled Generators...

Страница 32: ...Part No C4219 GENERAC POWER SYSTEMS INC P O BOX 8 WAUKESHA WI 53187 Revision 12 13 99 Printed in U S A...

Отзывы: