Section 7: Control Panel/Start-up/Testing
Installation Guidelines For 60 Hz Air-cooled Generators
27
shutoff valves in the fuel supply lines must be
open.
During initial start up only, the generator may exceed the
normal number of start attempts and experience an
“OVERCRANK” fault. This is due to accumulated air in
the fuel system during installation. Reset the control
board by pushing the OFF button and ENTER key, and
restart up to two more times if necessary. If unit fails to
start, contact an Independent Authorized Service Dealer
for assistance.
Check Manual Transfer Switch
Operation
Refer to the “Manual Transfer Operation” section of the
Owner’s Manual for procedures.
Figure 7-2. Installation Wizard Menu Map
(000132)
DANGER
Electrocution. Do not manually transfer under load.
Disconnect transfer switch from all power sources
prior to manual transfer. Failure to do so will result
in death or serious injury, and equipment damage.
UP ARROW =
+
DOWN ARROW =
-
SYSTEM
BAT-
DATE/TIME
SUB MENUS
Language
+ English -
+ Espanol -
+ Francais -
+ Portuguese -
Install Wizard
Set Exercise
Install Wizard
Power Up Unit
Select Hour (0-23)
- 14 +
Select Min (0-59)
- 0 +
ENTER
ENTER
ENTER
ENTER
ENTER
Select Hour (0-23)
- 14 +
Select Min (0-59)
- 0 +
ENTER
ENTER
Select Month (1-12)
- 2 +
ENTER
Select Date (1-31)
- 13 +
ENTER
Select Year (0-99)
- 13 +
ENTER
FIRMWARE V 1.01
HARDWARE V 1.05
* Holding the Up or Down arrow
button for 2 seconds will speed dial
through the selections
Defaults to English
if not selected.
Note: If language was previously programmed this goes directly to “Select Hour”
Use UP and DOWN
arrows to select fuel
type then press
“ENTER”
*
*
*
*
*
*
*
*
Switched to “OFF”
Hours of Protection
0 (H)
Select Day
- Wednesday +
Fuel Selection
+ NG or LP -
Select Frequency
- WEEKLY +
- BIWEEKLY +
- M
Cold Smart Start?
YES or NO
ENTER
ESC
Cold Smart Start?
- YES or NO +
000622