7
2.3.1 GROUNDING THE GENERATOR WHEN USED AS A
PORTABLE
This generator has an equipment ground that connects the
generator frame components to the ground terminals on the AC
output receptacles (see NEC 250.34 (A) for explanation). This
allows the generator to be used as a portable without grounding
the frame of the generator as specified in NEC 250.34.
Special Requirements
There may be Federal or State Occupational Safety and Health
Administration (OSHA) regulations, local codes, or ordinances that
apply to the intended use of the generator.
Please consult a qualified electrician, electrical inspector, or the
local agency having jurisdiction:
• In some areas, generators are required to be registered with
local utility companies.
• If the generator is used at a construction site, there may be
additional regulations which must be observed.
2.3.2 CONNECTING THE GENERATOR TO A BUILDING’S
ELECTRICAL SYSTEM
When connecting directly to a building’s electrical system, it is
recommended that a manual transfer switch is used. Connections
for a portable generator to a building’s electrical system must be
made by a qualified electrician and in strict compliance with all
national and local electrical codes and laws.
Grounding The Generator In A Building Standby
Application
The National Electrical Code requires that the
frame and external electrically conductive parts
of this generator be properly connected to an
approved earth ground.
Local electrical codes may also require proper grounding of
the unit (Figure 9). For that purpose, connecting a No. 10 AWG
(American Wire Gauge) stranded copper wire to the grounding lug
and to an earth-driven copper or brass grounding rod (electrode)
provides adequate protection against electrical shock. However,
local codes may vary widely.
Consult with a local electrician for
grounding requirements in the area.
Proper grounding of the generator will help prevent electrical
shock
in the event of a ground fault condition in the generator
or in connected electrical devices. Proper grounding also helps
dissipate static electricity, which often builds up in ungrounded
devices.
Figure 9 - Grounding the Generator
Grounding Lug
2.3.3 CONNECTING ELECTRICAL LOADS
DO NOT
connect 120 Volt loads to 230 Volt receptacles.
DO NOT
connect 3 phase loads to the generator.
DO NOT
connect 60 Hz
loads to the generator.
• Let engine stabilize and warm up for a few minutes after
starting.
• Plug in and turn on the desired 230 Volt AC, single phase, 50 Hz
electrical loads.
• Add up the rated watts (or amps) of all loads to be connected
at one time. This total should no be greater than (a) the rated
wattage/amperage capacity of the generator or (b) circuit
breaker rating of the receptacle supplying the power. See “Don’t
Overload the Generator.
2.4 DON’T OVERLOAD THE GENERATOR
Overloading a generator in excess of its rated wattage capacity
can result in damage to the generator and to connected electrical
devices. Observe the following to prevent overloading the unit:
• Add up the total wattage of all electrical devices to be connected
at one time. This total should NOT be greater than the
generator's wattage capacity.
• The rated wattage of lights can be taken from light bulbs. The
rated wattage of tools, appliances and motors can usually be
found on a data label or decal affixed to the device.
Operation
Содержание 006000-1
Страница 17: ...Notes 15 ...
Страница 18: ...Manual Part No 0K2011 Rev C 06 12 14 Printed in China ...
Страница 35: ...Notas 33 ...
Страница 36: ...Nº de parte del Manual 0K2011 Rev C 12 06 14 Impreso en China ...