7
2.4 HOW TO USE THE GENERATOR
If there are any problems operating the generator, please call the
generator helpline at 1-888-77LOWES.
Never operate in an enclosed area or indoors!
NEVER use in the home, in a vehicle, or in
partly enclosed areas such as garages, EVEN
IF doors and windows are open! ONLY use
outdoors and far from open windows, doors,
vents, and in an area that will not accumulate
deadly exhaust.
The engine exhaust fumes contain carbon
monoxide, which you cannot see or smell.
This poisonous gas, if breathed in sufficient
concentrations, can cause unconsciousness or
even death.
Adequate, unobstructed flow of cooling and
ventilating air is critical to correct generator
operation. Do not alter the installation or permit
even partial blockage of ventilation provisions,
as this can seriously affect safe operation
of the generator. The generator MUST be
operated outdoors.
This exhaust system must be properly
maintained. Do nothing that might render the
exhaust system unsafe or in noncompliance
with any local codes and/or standards.
The manufacturer recommends installing
a battery operated carbon monoxide alarm
indoors, according to the manufacturers
instructions.
2.4.1 SYSTEM GROUND
The generator has a system ground that connects the generator
frame components to the ground terminals on the AC output
receptacles. The system ground is bonded to the AC neutral wire
in the generator control panel via a jumper wire.
Special Requirements
There may be Federal or State Occupational Safety and Health
Administration (OSHA) regulations, local codes, or ordinances that
apply to the intended use of the generator.
Please consult a qualified electrician, electrical inspector, or the
local agency having jurisdiction:
• In some areas, generators are required to be registered with
local utility companies.
• If the generator is used at a construction site, there may be
additional regulations which must be observed.
Connecting to a Building’s Electrical System
When connecting directly to a building's electrical system, it is
recommended that a manual transfer switch is used. Connections
for a portable generator to a building's electrical system must be
made by a qualified electrician and in strict compliance with all
national and local electrical codes and laws.
2.4.2 GROUNDING THE GENERATOR
The National Electrical Code requires that the
frame and external electrically conductive parts
of this generator be properly connected to an
approved earth ground.
Local electrical codes may also require proper grounding of
the unit (Figure 6). For that purpose, connecting a No. 10 AWG
(American Wire Gauge) stranded copper wire to the grounding lug
and to an earth-driven copper or brass grounding rod (electrode)
provides adequate protection against electrical shock. However,
local codes may vary widely.
Consult with a local electrician for
grounding requirements in the area.
Proper grounding of the generator will help prevent electrical
shock
in the event of a ground fault condition in the generator or in
connected electrical devices. Proper grounding also helps dissipate
static electricity, which often builds up in ungrounded devices.
Figure 6 – Generator Ground Location
XG8000
GROUND
LOCATION
Operation
Содержание XG SERIES
Страница 42: ...40 Notas ...