Switch Nº 3 and Nº 4 (combination functions):
Switch Nº 3
Switch Nº 4
Action of actuator
Off
Off
Without signal keep valve position
On
On
Without signal keep valve position
On
Off
Without signal valve position full open (N.A.)
Off
On
Without signal valve position full close (N.C.)
Note: The standard configuration for Genebre is the 4 switches in "Off"
7.3 Auto Setting
If actuator is properly mounted on application, please check the input power, input signal
and wiring are correct or not. Without input signal, put actuator 50% open by hand wheel,
push Auto Setting Button for 3 seconds (S2). Firstly, the actuator moves by itself in order
to set the close and open position automatically.
After setting, actuator stops at the position, which is correspondence with the current
input signal and transmits the output signal.
8. Signal Leds