30 / 40
ADA / ASR
Type
Connectors
ASR Single acting
2: Control medium
(open/close)
ADA Double acting
2: Control medium (open)
4: Control medium (close)
For connectors 2 / 4 see picture on page 29
12
Setting and operation
12.1 Adjusting the end positions
ADA00010:
The setting range for the end positions is
±2° (88° to 92°).
Adjusting the end position 88°:
Move the actuator to the closed position.
Loosen the lock nut
1
.
Adjust the end position via screw
2
.
Tighten the lock nut
1
.
Adjusting the end position 92°:
Move the actuator to the open position.
Loosen the lock nut
3
.
Adjust the end position via screw
4
.
Tighten the lock nut
3
.
All other actuators:
The setting range for the end positions is
±5° (85° to 95°).
Adjusting the end position 85°:
Move the actuator to the closed position.
Loosen the lock nut
1
.
Adjust the end position via screw
2
.
Tighten the lock nut
1
.
Adjusting the end position 95°:
Move the actuator to the open position.
Loosen the lock nut
3
.
Adjust the end position via screw
4
.
Tighten the lock nut
3
.
By using a stroke limiter (optional), the end
positions can be set variably between 0° and
90° (not with ADA 00010 actuator).
Adjusting the end position 0°:
Move the actuator to the closed position.
Loosen the lock nut
1
.
Adjust the end position via screw
2
.
Tighten the lock nut
1
.
Adjusting the end position 90°:
Move the actuator to the open position.
Loosen the lock nut
3
.
Adjust the end position via screw
4
.
Tighten the lock nut
3
.
12.2 Optical position indicator
Top view:
Open
Closed
ADA 00010
ADA / ASR
0020U - 0850U
ADA / ASR
1200U - 4000U
Piping axis
Содержание ADA 00010
Страница 19: ...19 40 ADA ASR 21 Konformitätserklärung ...
Страница 38: ...38 40 ADA ASR 21 Declaration of Conformity ...
Страница 39: ...39 40 ADA ASR 22 ATEX confirmation ...