43 / 56
1436 cPos eco
13 Technical data
0
4
0
mA
mA
V
20
20
10
15
16
7,5
10
12
5
5
8
2,5
0
75
100
50
25
Operating conditions
Ambient temperature
0 ... +60 °C
Storage temperature
0 ... +60 °C
Control medium
Quality classes to DIN ISO 8573-1
Dust content
Class 7
(max. particle size 40 µm)
(max. particle density 5 mg/m³)
Pressure dew point
Class 4
(max. pressure dew point 3 °C)
Oil concentration
Class 4
(max. oil concentration 5 mg/m³)
Air supply
1.5 to 7 bar
Air consumption
0 l/min
(when idle)
Air output:
150 l/min
Materials
Housing cover
PSU
Housing base
PP30
Electrical data
Power supply
Power supply
U
V
= 24 V DC +10%/-5%
Power consumption
for flow rate code 01
I
typ
= 100 mA (@ 24 V DC)
Input signals
Analogue inputs
Set values
4...20 mA
Input resistance
50 Ω
Initialisation input (Digital)
Voltage
24 V DC
Level “Logical 1“
14 V DC ≤ U
H
≤ 30 V DC
Level “Logical 0”
0 V DC ≤ U
L
≤ 8 V DC
Input current
I
typ
= 1.3 mA (at 24 V DC)
Analogue output
Actual value output
4 - 20 mA
Load resistor
max. 600 Ω
Electrical connection
Power supply
1 x M12 plug (A-coded)
and signal connections
(Installation: Observe operating
instructions)
Positioner data
System deviation
≤ 1%
Initialisation
Automatic via 24 V DC signal
Close tight function
CLOSED: W ≤ 0.5%;
OPEN: W ≥ 99.5%
Display elements
Status display
4 LEDs
General information
Protection class to EN 60529
IP 65
Weight
600 g
Dimensions L x W x H
see pages 7 and 8
Installation position
Optional
Directives
Low Voltage Directive
2014/35/EU
EMC Directive
2014/30/EU
Standards
Interference emission DIN EN 61000-6-3 (09/2011)
EN 61000-6-3 : 2007 + A1 2011
IEC 61000-6-3 + A1 2012
DIN EN 61326-6-1 (industry) (10/2006)
Interference resistance DIN EN 61000-6-2 (03/2006)
EN 61000-6-2 : 2005
IEC 61000-6-2 : 2005
DIN EN 61326-6-1 (industry) (7/2013)
Class B
Group 1
During initialisation the GEMÜ 1436 cPos eco positioner
automatically detects the control function of the valve:
Normally open (NO) or Normally closed (NC)
For all valves the Closed position is at 4 mA.
Control diagram
Valve opening degree
[%]
Travel sensor
integrated in directly mounted version
Linear design
Stroke
0 - 30 / 0 - 50 / 0 - 75 mm
Resistance R
3 / 5 / 5 kΩ
Minimum stroke
≥ 1 mm
Quarter turn design
Angle of rotation
0 - 93°
Resistance R
3 kΩ
Содержание 1436 cPos eco
Страница 54: ...54 56 1436 cPos eco...
Страница 55: ...55 56 1436 cPos eco...