42 / 56
1436 cPos eco
11 Error messages
Error
Error message
Error cause
Effect
Error clearance
No. 1
Set value > 20.5 mA Set value signal > 20.5 mA Process valve
is closed
Check set value signal
No. 2
Set value < 3.5 mA
Set value signal < 3.5mA
Process valve
is closed
Check set value signal
No. 3
Positioner not
initialised
Device was not initialised
No function
Carry out initialisation
No. 4
Positioner not
calibrated
Device faulty
No function
Send to GEMÜ for repair
No. 5
Device error
a) Pneumatic air supply
missing
b) Leakage in pneumatic
system
Initialisation
failure
Check
a) pneumatic air supply
b) pneumatic connections
Warning
Error message
Error cause
Effect
Error clearance
No. 1
Positioner works
with lower quality
During initialisation, the
internal valves could not
be measured exactly
Control is not
optimized
Check for
a) Leakage of the process valve
b) Correct function of process
valve
c) Unstable medium pressure
during initialisation (if possible
turn off media pressure)
12 Fail safe function
Fail safe function
No.
Error
Outlet A1
1
Power supply failure
vented
2
Compressed air supply failure
Single acting
This fail safe function is not a substitute for specific plant safety requirements.