This QAA70 room sensor provides the following
functions:

- compensation for ambient conditions,

- the ability to programme three daily periods for

heating or hot water,

- a easy programme override to switch the system

off either momentarily or for longer periods (e.g.
holidays),

- an ambient temperature setting for each pro-

grammed period,

- a setting for the hot water temperature,

- a display showing the time, the outside tempera-

ture, the ambient temperature, the boiler tempe-
rature, the hot water temperature and indicating
the presence of any faults on the boiler system,

- the ability to anticipate and defer water heating:

the hot water tank will start being fed with hot wa-
ter one hour before the heating period and this
will continue until 10 minutes after the end of this
period. When a demand for domestic hot water is
made during a period of reduced heating, the boi-
ler systematically ensures that the water is at the
hot water temperature setting.

  $GMXVWPHQWV

Fitting the QAA70 module on the boiler cancels the
functions of the heating and hot water temperature
knobs on the boiler control panel. The expected
temperatures must be set on the QAA70 sensor
(see seperate technical instructions).

  :LQWHUVXPPHUVZLWFK

When the winter/summer is switch set to the winter
position, the boiler can switch automatically from
winter to summer operation. Summer operation is
active when the outside temperature measured over
the previous 24 hours exceeds the set point by 1 °C,
i.e. it reaches 20 °C. 

When summer operation is active it can be overrid-
den temporarily by pressing simultaneously the 
and  

  buttons on the QAA70.

The system also automatically returns to summer
operation, this time when the outside temperature
measured over the previous 24 hours is at least 1 °C
less than the set point, i.e. below 18 °C. The 19 °C
set point can only be changed by using the AZW75
interface.

When the winter/summer switch is set to the sum-
mer position, the regulator provides hot water only
(if the boiler has a hot water tank).

Buttons A, B and C operate on the integrated regu-
lator and are used to access special functions com-
mon to all versions.

  $PELHQWFRQGLWLRQVFRPSHQVDWLRQ

IXQFWLRQ

This function can be used to correct the boiler flow
temperature according to the real ambient tempera-
ture measured by the QAA70 sensor. The function
should be activated or deactivated when the boiler
is commissioned depending on the position of the
sensor. The function should be inactive if any of the
following apply: if the QAA70 is placed outside the
heated space or in a room with another heating sys-
tem, or if it is exposed to sunshine, or if thermostatic
valves are set on the radiators in the room where the
QAA70 is fitted. When the ambient conditions com-
pensation function is inactive, the QAA70 becomes
a remote control acting on the heat curve to cater for
the drop in temperature from daytime to night-time.

 $FWLYDWLQJWKHDPELHQWFRQGLWLRQVFRPSHQVDWLRQ

IXQFWLRQ

press buttons 

$

 and 

&

 simultaneously for 5 se-

conds until the 

 symbol appears on the dis-

play.

 'HDFWLYDWLQJWKHDPELHQWFRQGLWLRQVFRPSHQVD

WLRQIXQFWLRQ

press buttons 

$

 and 

&

 simultaneously for 5 se-

conds until the 

 symbol appears on the dis-

play.

  $XWRDGDSWIXQFWLRQ

This function automatically corrects the heating cur-
ve based on a measurement of the real ambient
temperature.

The corrected loss can be read via the AZW75 “ap-
prentice parameters” interface.

The function should not be active in the installation
situations described above for the ambient condi-
tions compensation.

 $FWLYDWLQJDXWRDGDSW

press buttons 

%

 and 

&

 simultaneously for 5 se-

conds until the 

 symbol appears on the dis-

play.

 'HDFWLYDWLQJDXWRDGDSW

press buttons 

%

 and 

&

 simultaneously for 5 se-

conds until the 

 symbol appears on the dis-

play.

Содержание THR 2-13 M75

Страница 1: ...7 1 1 6 7 5 8 High fidelity heat 7 2 1 6 7 5 0 7 5 0 T30 18305 03...

Страница 2: ...11 2 3 THR with outside temperature sensor and room sensor 12 3 FUNCTIONS COMMON TO THE DIFFERENT VERSIONS 14 3 1 Antifreeze function with QAC31 or and QAA70 14 3 2 Anti legionella function 14 3 3 Pum...

Страница 3: ...n using standard flue model B23 24 5 2 Evacuation using balanced flue 25 6 GAS CONNECTIONS 30 7 ELECTRICAL CONNECTIONS 30 7 1 Connecting QAC31 outside sensor and QAA70 room sensor options 30 7 2 Addit...

Страница 4: ...he correct mixture across the full opera ting range A cover with a calm restrained styling contains the following components a high performance condensing heat exchanger made from tubular fins a varia...

Страница 5: ...rate combustion products min max kg h 4 5 25 0 9 0 44 1 Admissible back pressure B23 combustion products C13 C33 max Pa 0 100 NOx mg kWh 60 Blue Angel Label CO mg kWh 50 Blue Angel Label Heating wate...

Страница 6: ...ater inlet hot water outlet pouce 3 4 Condensate drain mm 25 Pressure relief valve drain mm 27 1 82 5 540 1500 600 672 65 91 4 49 2 140 8 66 55 6 24 4 47 6 2 7 3 4 5 6 8 467 6 95 4 44 Vue du dessous V...

Страница 7: ...WXEH DV VXSSO 0LFURSURFHVVRU EDVHG FRQWURO SDQHO 6LSKRQ WUDS LQQHG WXEH KHDW H FKDQJHU LU YHQW HDWLQJ UHWXUQ PDQLIROG ZLWK VHOHFWRU YDOYH 9 VSHHG FLUFXODWLQJ SXPS 3UHVVXUH UHOLHI YDOYH EDU DWHU SUHVVX...

Страница 8: ...VXSSO 0LFURSURFHVVRU EDVHG FRQWURO SDQHO 6LSKRQ WUDS LQQHG WXEH KHDW H FKDQJHU LU YHQW HDWLQJ UHWXUQ PDQLIROG ZLWK VHOHFWRU YDOYH 9 VSHHG FLUFXODWLQJ SXPS 3UHVVXUH UHOLHI YDOYH EDU DWHU SUHVVXUH VHQVR...

Страница 9: ...VHQVRU KDSWHU 23 5 7 21 LQWHU VXPPHU VZLWFK ZLQWHU KHDWLQJ KRW ZDWHU VXPPHU KRW ZDWHU RQO RQ WKH GXDO IXQFWLRQ PRGHO RQO VHTXHQFH GLVSOD IODPH LQGLFDWRU ODPS IDXOW LQGLFDWRU ODPS 7KUHH EXWWRQV DQG UH...

Страница 10: ...d for hot wa ter display 6 or heating display 7 3KDVH 6KXW GRZQ the change of operating position to standby is re ferred to as a shut down and occurs when the demand for heat disappears The gas valve...

Страница 11: ...egulator defines the heat output requi red to achieve the heating and hot water settings en tered by the user These are set using temperature knobs for the boiler flow and hot water settings A winter...

Страница 12: ...justing in order to obtain a higher or lower level of heating This involves modifying the heating curve parameters see 2 2 2 3 Chapter III OPE RATION 0RGLI LQJ SDUDPHWHUV Adjust the heating knob to th...

Страница 13: ...n the set point i e below 18 C The 19 C set point can only be changed by using the AZW75 interface When the winter summer switch is set to the sum mer position the regulator provides hot water only if...

Страница 14: ...s valve remains in the domestic hot water feed position SDVV YDOYH DQG SXPS NLFN If during shut downs either the heating circuit has not operated or the bypass valve has not been swit ched for more th...

Страница 15: ...a ter cooled combustion chamber in its upper part combines the functions of a heat exchanger and condenser Condensation occurs on the tube walls where the temperature is below the dew point for the co...

Страница 16: ...F IORZ UDWH D 5HKHDWLQJ WLPH DW E RDG WLPH DW 9ROXPH GUDZQ DW LQ PLQ 9ROXPH GUDZQ DW LQ KRXU 6WRUDJH N O PLQ O PLQ PLQ PLQ OLWUHV OLWUHV 0 9 23 3 11 15 16 10 17 155 712 0 13 4 6 41 11 5 18 30 112 432...

Страница 17: ...ilation 9 Return to initial position reinitialise gas control box parameters fan off LVSOD 0HDQLQJ 3ULRULW 1 Boiler potentiometer setting absent 1 2 Hot water potentiometer setting absent 1 4 T V func...

Страница 18: ...former HT lead or HT electrode The flame only appears for 3 seconds Live neutral reversed defective ionisation probe or ionisation probe lead 5 Incorrect fan speed at maximum load Check parameter DA4...

Страница 19: ...that it cannot be tou ched by a person using the bath or shower Where installation will be in an unusual location special procedures may be necessary and BS 6798 gives detailed guidance on this subjec...

Страница 20: ...guidance in this subject The central heating system should be in accordance with the relevant recommendations given in BS 6798 and in addition for small bore and micro bore systems BS 5449 1 The domes...

Страница 21: ...17 9 56 216 Those brackets enable hydraulic connection as well as the installation of the boiler on a light partition fix the brackets on the wall install the boiler on the brackets 7 5 0 FKHFN WKH VT...

Страница 22: ...that the boiler and installation are pro perly purged by increasing the water pressure to at least 1 bar manometer Check that it is fully purged again a few days after commissionning DWHU IORZ UDWH W...

Страница 23: ...fitted for use in a floor heating system unless it is installed with an in dependant electronic control 7 5 ZLWK RXWVLGH VHQVRU RQO To operate the THR with outside sensor as part of a floor system the...

Страница 24: ...to be fitted 20 867 21 352 8 7 8 1 7KH IOXH V VWHPV SUHVHQWHG LQ WKLV WHFKQLFDO GRFXPHQW DUH WKRVH XVXDOO XVHG RQ WKH XURSHDQ PDUNHW RZH YHU VRPH RI WKHP PD QRW EH XVDEOH LQ DOO FRXQWULHV W LV WKH UH...

Страница 25: ...alled when the wall adjoining the water heater gives onto the outside in a well ventilated location Two concentric tubes supply air to the burner and evacuate the combustion products The conduits can...

Страница 26: ...4 to 9 need to be ordered specifically LJ Max lenght P with two 45 bend pieces RLOHU FRYHU EHQG SLHFH SRO SURS OHQH 33 EHQG SLHFH SRO SURS OHQH 33 HDWLQJ XQLW 3RO SURS OHQH WXEH 33 PP GDSWHU SLHFH 8...

Страница 27: ...least 0 4 m from any opening window and 0 6 m from any air ventilation opening see regulations Two balan ced flue outlets from two distinct adjacent THR units must be at least 0 6 m apart The flue ga...

Страница 28: ...arious seals in good condition cover flue box etc Replace if necessary the various elbows and con nection pieces located on the flue gas exhaust route and on the air intake must be fitted in a leaktig...

Страница 29: ...Flue 0 60 0 40 Air vent Opening light ventlight window E Si E 0 30 m 1 80 The appliance must be approved with its extension Flue Flue Case Case Flue on a balcony or under a roof A public or private h...

Страница 30: ...ressure drop of more than 1 mbar 10 mmWG Example natural gas type H G20 20 mbar for 10 metres of pipe with 4 bend pieces 1 bend pie ce roughly equivalent to 0 5 metres minimum diameter 20 22 75 211 7...

Страница 31: ...U U R Q Y H U W M D X Q H E O D X Z H L V V E U D X Q J U X Q J H O E E O X H Z K L W H E U R Z Q J U H H Q H O O R Z O L P H Q W D W L R Q 1 H W V S D Q Q X Q J 3 R Z H U V X S S O P E O E O E O E E...

Страница 32: ...1 Open the hand operated valve on the gas supply Switch on the main heating switch The regulator undergoes a self test sequence displaying codes L P C 6 and 5 in turn The dis play then shows 9 and fi...

Страница 33: ...l gas H mm 16 5 29 Gas flow 15 C 1013 mbar Natural gas G20 m3 h 0 27 1 48 0 53 2 59 Gas Pressure Po gas valve burner Natural gas H mbar 0 15 5 30 0 15 1 80 Servo air pressure PL Pa 30 720 25 370 CO2 N...

Страница 34: ...rofessional equipped with a calibrated combustion analyzer V K Boss up Flange side Burner THR 2 13 X00 21867 Fan Gas reducer 4 40 Boss up Gas valve Ionisation probe Pi Po Ignition Electrode O ring Gas...

Страница 35: ...a steady flame Then check the CO2 CO rate against the table 3 Chapter V COMMISSIONING the gas flow is increased by turning and vice versa Set the potentiometer item 1 fig 4 to the left hand stop point...

Страница 36: ...FLUFXLW LV VOLJKWO SUHVVXULVHG R QRW SLHUFH WKH FLUFXLW ZLWKRXW VXEVHTXHQWO VHDOLQJ RII WKH KROH PDGH 3 Check the flame monitor by disconnecting the io nisation probe safety shut off after two attempt...

Страница 37: ...5 7 TEST LABORATORY HAFENSTRASSE 101 45356 ESSEN EC DIRECTIVES 90 396CEE 92 42CEE 73 23CEE 89 336CEE BASIS OF EXAMINATION EN 437 PREN 483 PREN 677 EN 60335 1 EN 55014 EN55104 SURVEILLANCE PROCEDURE 0...

Страница 38: ...GEMINOX SA 16 rue des Ecoles BP 1 29410 SAINT THEGONNEC FRANCE T l 02 98 79 40 22 T l copie 02 98 79 47 57 Internet http www Geminox fr JULY 2000...

Отзывы: