12.1.2 On/Off actuator with 2 potential-free limit switches (code AE)
DANGER
Risk of electric shock
▶
Death or injuries
●
The end positions (potential-free limit switches) are set mechanically by means of
adjusting screws. To do this, disconnect the plant from the power supply. This may
only be done by qualified electricians!
NOTICE
●
Always switch the limit switch for signal so that the motor switch is actuated first.
ð
Limit switches for signal and motor are already preset.
12 V DC (code B1) / 24 V DC (code C1)
Position of the connectors
X1
X2
S1/S2 UV
Actuator version 3035, 3055
Actuator version 1006, 1015
Electrical connection
2
1
3
4
6
5
2
1
3
4
6
5
Plug assignment X1, UV
Plug assignment X2, S1/S2
Pin
Description
Pin
Description
1
Uv+, direction of travel CLOSED
1
Change-over contact limit switch CLOSED
2
Uv-, direction of travel CLOSED
2
Make contact limit switch CLOSED
3
Uv+, direction of travel OPEN
3
Break contact limit switch CLOSED
4
Uv-, direction of travel OPEN
4
Break contact limit switch OPEN
5
n. c.
5
Make contact limit switch OPEN
6
n. c.
6
Change-over contact limit switch OPEN
PE, protective earth conductor
PE, protective earth conductor
www.gemu-group.com
84 / 108
GEMÜ R478 Tugela
12 GEMÜ 9428 electrical connection