AIR HEATER PELLET STOVE BY GEKASMETAL 

                                                                                  

 

Page 20

 

 

 

 

<CONSTANT HOLD> 

When the area temperature equals the one requested (or slightly higher than 0,5

ο

 

C), then the appliance enters 

<CONSTANT HOLD> 

phase for a few minutes. This happens 

because  a  solid  fuel  system  has  not  the  same  ignition flexibility  as  a liquid or  gas  fuel  system.  Therefore,  a  common  practice  is  the  attempt  for  reduction  of  ignitions.  To 
achieve  this,  the  control  system,  after  disabling  the  operation  orders,  enters  a  hold  phase  during  which  it  preserves  the  flame,  so  that  the  return  in 

<OPERATION>

  phase 

would be instant, as soon as an order appears. During this phase  the 

fume inhibitor

*

 is enabled  from 

<OPERATION> 

phase. The supplier and the combustion fan function 

according to electric power of that period. Then it moves to the next phase.  

 

*

 Fume inhibitor

 

The electric power of the system in this phase, whether setted automatically or manually, is affected by the fume temperature signal, if it is enabled. In this case there is a 
system  which  protects  from  very  high  or  low  fume  temperatures.  This  system  is  called  fume  inhibitor.  These  settings  concern  some  temperature  limits  which,  if  the  fume 
temperature signal exceed, the control system starts increasing or decreasing its power in order to reset the fume temperature within the limits. This operation may better be 
explained through an example. 
 

<FINAL CLEANING> 

During this phase the control system cleans the combustion chamber, in order to be empty for the next ignition.  
The control system remains in this phase for a specific time period. If, during this time period, the fume temperature drops below the 

deactivation temperature

, then the 

phase is being terminated and the controller moves to 

<INERTIA>

 phase. 

The combustion fans, during the entrance of the control system in this phase and for a small period of time, preserve their former speed. After this period of time and for the 
rest of the phase the combustion fan functions with maximum speed. The supplier is being disabled.  

 

 

7.

 

ERRORS 

 

Error codes 

 

 

Description  

Cause  

Function  

E01 

Memory failure  

Malfunction of the control system. 

 

• 

The system fails to start up and all functions remain disabled. 

 

• 

This error CANNOT be disabled.

 

 

• 

If the error is not permanent, the controller restarts after reset 

of voltage supply. 

Ε05

 

External error 

The entry signal contact 

external error

 

has been opened. 

 

• The boiler is being deactivated

 

• 

The exit functions remain activated. 

 

 The entry signals remain activated. 

 

• The

 system does not return in function if the error has not been 

removed by the user. 

Ε11

 

Area Sensor 1 

 Area temperature 1

 sensor is 

disconnected, shorted or open. 

 

• The boiler is being deactivated

 

• 

The exit functions remain activated. 

 

• The 

remaining exit functions are being disabled.  

 

• 

The entry signals remain activated. 

 

• The

 system does not return in function if the error has not been 

removed by the user. 

Ε13

 

Fume Sensor 

Fume temperature

 sensor is 

disconnected, shorted or open.  

 

 The boiler is being deactivated. 

 

• 

The exit functions remain activated. 

 

• The 

remaining exit functions are being disabled.  

 

• 

The entry signals remain activated. 

 

• 

The system does not return in function if the error has not been 

removed by the user. 

Ε15

 

Speeds sensor 

The 

combustion fan

 does not function or 

the speeds sensor presents failure.   

 

• The boiler is being deactivated

 

• 

The exit functions remain activated. 

 

 The remaining exit functions are being disabled. 

 

• 

The entry signals remain activated. 

 

• The

 system does not return in function if the error has not been 

removed by the user. 

Ε20

 

Startup Failure 

During 

<FLAME HOLD> 

phase 

fume 

temperature

 failed to be increased as 

much as needed, within the time limits of 

 

• The boiler is being deactivated

 

• 

The exit functions remain activated. 

 

 The entry signals remain activated. 

Содержание AMANDA

Страница 1: ...AIR HEATER PELLET STOVE BY GEKASMETAL Page 1 AMANDA 9KW Manual...

Страница 2: ...METAL The pellet stove is an ideal heating solution It uses advanced technology and it has been constructed according the highest standards with modern design that allows you to enjoy your heat with...

Страница 3: ...r operator of the appliance should read and fully comprehend the content of this manual before attempting any use of it Mistakes or incorrect adjustments may cause dangerous conditions or and poor fun...

Страница 4: ...ext ignition Do not clean the product with water Water could leak into the appliance and destroy the electric insulation causing electrocution Do not stand in front of the appliance for a long time Av...

Страница 5: ...th the appliance The term guarantee refers to the free of charge replacement or repair of the parts of the appliance which are admitted as defective by construction RESTRICTIONS The above mentioned gu...

Страница 6: ...the European market and guarantee that the following characteristics are being retained Thermal value 4 9 kWh kg Humidity max 10 of its weight Ash percentage max 0 5 of its weight Diameter 5 6 mm Len...

Страница 7: ...here should be an ventilation opening The air pipes should comply with following requirements Be protected with racks metal nets etc without reducing however the useful part Be constructed in such way...

Страница 8: ...ggested CONNECTION TO ELECTRIC NETWORK Before the connection of the appliance to electric network check if the electrical installation is equipped with ground and differential switch according to regu...

Страница 9: ...cross flammable materials the above instructions should be followed SYMBOL DESCRIPTION HEIGHT mm b Minimum distance from combustible materials from the inside of the ceiling floor wall 500 B Minimum d...

Страница 10: ...pe should allow the retrieval of soot it should be cleaned and be inspected after being dismantled or through the inspection openings if it is not accessible from the inside of the appliance ADDITIONA...

Страница 11: ...ns only with negative pressure in relation to the environment and should be according to EN 14785 2006 Flue terminals The flue terminals should comply with the following requirements They should be se...

Страница 12: ...N 14785 2006 In case of pellet appliances the fume extraction systems should have leak tightness if they use elements of double definition G and O with or without elastomeric sealing For the connectio...

Страница 13: ...to remove it The glass should be cleaned using a dry cloth If needed you can use water and a soft detergent only if the glass is cold Once in a month clean the area behind the ash tank by removing th...

Страница 14: ...that performed the actions of inspection or and maintenance along with contact information date and signature of the technician 5 TECHNICAL CHARACTERISTICS MODEL WOOD PELLET STOVE AMANDA DIMENSIONS Hx...

Страница 15: ...causes exit without recording the value During the processing of text it causes exit without recording the text Prolonged press Switches off the boiler performing all necessary actions ignition combu...

Страница 16: ...th Minus button it changes the current indications screen Main Screen Entries Screen Exits Screen 4 Minus Button Decrease and navigation button Single press Enables the screen for room temperature set...

Страница 17: ...it should firstly be activated The control system is considered activated when it is at any phase except for the phase SHUTDOWN If it is deactivated the indication on the screen is SHUTDOWN If it is a...

Страница 18: ...re then the controller moves to the INERTIA phase or the SHUTDOWN phase depending on whether it was enabled or disabled before the interruption of electrical supply voltage During the first ignition i...