CALIBRATION PROCEDURE OF THE INPUT SIGNAL

FACEPLATE DESCRIPTION

g

c

b

f

e

d

a

Green LED (power on), 

Red LED (GT running)

Red LED (thermal alarm), yellow LED

(load interrupt alarm, HB option)

Monorev trimmer for calibration of load

interrupt (HB) alarm limit 

Monorev trimmer for minimum

calibration of input signal 

Monorev trimmer for maximum
calibration of load signal 

Dip switch for selection of input signal
(S1, S2, S3)

LINE connection 

LOAD connection 

Reference connection of 230V line voltage 

(HB option with 150V to 300V load)

Reference connection of 480V line voltage (HB option
with 300V to 530V load)

Alarm output 

(solid state relay, HB option)

Synchronism signal for

Master/Slave connection

- control signal

+ control signal 

Reference voltage for potentiometer power supply (+ 10V)

24 Vac 50/60 Hz power terminal 

The solid-state power unit, Gt, is supplied factory calibrated for 0..5V, 0..10V, 0..20mA, 4..20mA, 10Kohm potentiometer.
Minimum and maximum values are adjusted with two monorev trimmers (d,e). 
Input signal type is selected with the adjustment f dip switches (S1,S2,S3).

125

100K

100K

d

4%

T

18%

V/mA

e

In

82%

96%

0-10V

4-20mA

0-20mA

f

S1-S3

0-5V

V/mA

In

Rin

On

Off

125

Control signal

Dip Switch Position

S1

S2

S3

0...5Vdc

OFF

OFF

ON

0...10Vdc

ON

OFF

ON

0...20mA

OFF

ON

ON

4...20mA

OFF

ON

OFF

Minimum adjustment trimmer (d) turned fully counterclockwise sets the start conducting limit at 4% of the signal; turned fully

clockwise, the minimum conducting limit is set at 18% of the input signal. 

Maximum adjustment trimmer (e) turned fully clockwise sets the full conducting limit at 96% of the signal; turned fully

counterclockwise, the full conducting limit is set at 82% of the input signal.

Содержание GT 120A

Страница 1: ...ermediate values The units offer optional accessoires for panel mounting fuses and fuseholders current transformer isolation transformers Use the rel with an opportune heatsink see section accessories...

Страница 2: ...h junction ambient 12 K W Solid State Relay Dissipated Power Calculation Singol phase static relay Pds 1 4 IRMS W IRMS singol phase load current Heatsink thermal resistance Calculation Rth 90 C T amb...

Страница 3: ...ifferent cycle times 100msec and 40msec respectively V V Example of input at 20 2V IN 0 10V or 4mA IN 0 20mA V Voltage across load Example of input at 50 5V IN 0 10V or 10mA IN 0 20mA V Voltage across...

Страница 4: ...ge for potentiometer power supply 10V 24 Vac 50 60 Hz power terminal The solid state power unit Gt is supplied factory calibrated for 0 5V 0 10V 0 20mA 4 20mA 10Kohm potentiometer Minimum and maximum...

Страница 5: ...ther 1 10 of a turn 1 notch on the scale In this way the alarm limit is set below 10 of the rated load current N B the partial load break alarm function operates with power partialization exceeding 15...

Страница 6: ...PLES L2 h L1 i Master AL PWR Line 230 V GT 25A 480 Vac e Max Adj d Min Adj c Reset Alarm f Input selection g Alarm Adj Line 30 Vdc ac ON 2 Out Alarm 1 Slave 3 Line 480 V 0 10V 0 20mA 4 20mA 0 5V AC1 5...

Страница 7: ...6 7 8 10 Vdc 24 Vac Supply Out Input Analog 1 2 3 Out 30 Vdc ac Alarm Master Slave ON PWR AL 4 20mA d Min Adj AC1 50 60 Hz GT 25A 480 Vac 0 20mA c Reset Alarm L1 h i L2 0 5V 0 10V Load Line 480 V f In...

Страница 8: ...th neutral Controller Relay output Alarm solid state relay Digital output 0 20mA 4 20mA 0 10Vdc 0 5Vdc Three phase connection triangle or star without neutral with control of two phases using one GT i...

Страница 9: ...es thermostats current transformers and isolation transformers To choose accessories see the section Solid state relays Accessories Fuse Fuse Fuse TABLE OF TERMINALS AND CONDUCTORS 25 40A 6 3x9 Eye fo...

Страница 10: ...y from dust humidity corrosive gases and heat sources The connection cable must be shorter than 3 meters if the current transformer is used Maintenance Check the correct operation of the cooling fans...

Отзывы: