EXAMPLES OF CUSTOM LINEARIZATION
Example of custom linearization: type 0
(at variable amplitude intervals, max. 32)
For positive polarization signals (ex. 0...50mV)
S.00
is the value displayed for minimum input (ex. 0mV);
if 32 intervals are set,
S.32b
is the value displayed for input =
S.32A
* (f.s. / 10000)
(ex. if
S.32A
= 10000,
S.32b
is the value displayed with input = 50mV)
For symmetrical polarization signals (ex. -25mV...+25mV)
S.00
is the value displayed for minimum input (ex. -25mV);
if 32 intervals are set,
S.32b
is the value displayed for input =
S.32A
* (f.s. / 10000)
(ex. if
S.32A
= 10000,
S.32b
is the value displayed with input = +25mV)
In case of linearization type 1, ... ,4
S.nnA
values are acquired directly by its input IN1, ... ,IN4
Example of custom linearization: type 5
(at 64 constant amplitude intervals = f.s. / 64)
For positive polarization signals (ex. 0...50mV)
S.00
is the value displayed for minimum input (ex. 0mV);
S.64
is the value displayed for maximum input (es 50mV)
For positive polarization signals (ex. -25mV...+25mV)
S.00
is the value displayed for minimum input (ex. -25mV);
S.64
is the value displayed for maximum input (ex. +25mV)
0
S.01A
1300
S.02A
4000
S.03A
7500
S.04A
8000
10000
S.00
S.01b
S.02b
S.03b
S.04b
0
6.25mV = 8* (f.s./64)
f.s. = 50mV
S.00
S.08
S.25
S.48
S.64
19.53mV
37.5mV
....
....
....
Engineering value
scale displayed
Input [1/10000] f.s.
Example of type 0 linearization with 4 intervals
Example of type 5 linearization
Ex: input 0...50mV
Engineering value
scale displayed