35
80290C_MHW_2400_0908_ENG
Digital input 1 function
Digital input 2 function
By adding the following numbers to the value shown in the
table, you can enable a series of supplemental functions:
+32:
to refer to input IN2 (only for values on table
referred to IN1)
+64:
input in denied logic
+128:
force logic state 1 (ON)
D
[
xrd
]
Function
0
Disabled (no function)
2
HOLD IN1
3
Reset alarm latch
4
Alarm limit 1 from input In.3
5
Alarm limit 2 from input In.4
6
Alarm limit 1 from input In.3 and alarm limit 2
from input In.4
7
Set / Reset outputs OUT 1 ... OUT 4
8
Peak ON + (maximum) IN1
9
Peak ON - (minimum) IN1
10
Peak ON - peak
(maximum peak - minimum peak) IN1
11
Reset memory peak IN1
12
Reset memory alarms / peak IN1
13
Selection IN.1...IN/4 for visualization on display
PV (Lsb)
14
Selection IN.1...IN/4 for visualization on display
PV (msb)
15
Check calibration strain-gauge IN1
(6-wire probe)
16
Calibration strain-gauge IN1
17
Software off/on
18
Block key
19
Remoting key F
20
Remoting key INC
21
Remoting key DEC
23
Zero tare IN1
24
Zero tare IN1 / Reset alarm latch
25
Zero tare IN1 / Reset peak latch IN1
26
Zero tare IN1 / Reset alarm latch /
Reset peak latch IN1
27
Display HOLD IN1
28
FLASH IN1
29
Net / Gross (if on = Gross)
30
Change color of PV display
PV Digital Filter on PV display
[0.0 ... 9.9] scale points
Select variable displayed on PV Display in
function at level 1
Function
1
IN1
2
IN2
3
IN3
4
IN4
8
Retransmission output
9
Fin.A
10
Fin.b
12 Selection IN.1...IN.4 from digital inputs
32 Alternation of IN1, IN2 (with time approx. 1.2 sec)
64 Alternation of IN1, IN2, IN3 (with time approx. 1.2 sec)
128
Alternation of IN1, IN2, IN3, IN4 (with time approx. 1.2 sec)
+16 green PV display
+ 256 Alternating with the time 2,4sec
PV
diG.1
PV
diG.2
PV
F1d
PV
ds.SP