80290C_MHW_2400_0908_ENG
OUT 1
Attribute reference signal
0
0 v
v t
t
Setting Outputs
This menu lets you configure the output parameters.
Function
0
OFF
1
AL1 – alarm 1
2
AL2 – alarm 2
3
AL3 – alarm 3
5
Repeat logic input 1
6
Repeat logic input 2
7
Repeat but 1 key
8
AL1 or AL2
9
AL1 or AL2 or AL3
10
AL1 And AL2
11
AL1 and AL2 and AL3
16
or AL3 ... AL10
17
and AL3 ... AL10
18
AL 4 – alarm 4
19
AL4 or AL5
20
AL4 or AL5 or AL6
21
AL4 or AL5 or AL6 or AL7
22
AL4 and AL5
23
AL4 and AL5 and AL6
24
AL4 and AL5 and AL6 and AL7
25
AL8 or AL9
26
AL8 or AL9 or AL10
27
AL8 and AL9
28
AL8 and AL9 and AL10
Add +32 to the values indicated in the table to obtain the denied
logic level in output, or reverse for CO1, CO2.
OUT 2
Attribute reference signal
OUT 3 (*)
Attribute reference signal
OUT 4 (*)
Attribute reference signal
(*) available only without MD8 expansion
The 8 outputs available by means of the MD8
expansion assume the state of alarms
AL3,...,AL10
OUT W Retransmission Output Type
0
Output disabled
1
0...10V
2
2...10V
3
0...20mA
4
4...20mA
5
±10V
Reference quantity
0
IN1
1
IN2
2
IN3
3
IN4
4
Fin.A (math function A)
5
Fin.b (math function b)
12
Value acquired from serial line
13
Input 1 maximum peak
14
Input 1 minimum peak
15
Input 1 peak-peak
16
Input 2 maximum peak
17
Input 2 minimum peak
18
Input 2 peak-peak
19
AL1 (limit)
20
AL2 (limit)
21
AL3 (limit)
Attribute reference signal OUT W
+8 reverse output
MIN analog repeat output scale
[reference variable scale range]
MAX analog repeat output scale
[reference variable scale range]
Select probe power supply
0
2,5V for potentiometers
1
5V for strain gauge
2
10V for strain gauge
max. 200mA
PV
ALS
PV
xi.An
PV
Lo.An
PV
riF.An
PV
tyP.An
PV
RL.4
PV
RL.3
PV
RL.2
PV
RL.1
+32 only for riF.An = 0,1,2,3,4,5: output at max/min hard-
ware (beyond calibration limits) for input at Hi/Lo
+64 only for riF.An = 0,1,2,3,4,5: output at minimum if
input is in Err, Sbr, Ebr condition