User Instructions for GECO GH21TA controller
______________________________________________________________________________
Page 30 Edition I
19.06.2013
10. Alarms
The controller has 11 alarms, including eight which will stop the controller for safety
reasons and three that are warnings. For each alarm or notes, the number is displayed, along
with text information describing the problem, and an audible alarm will sound. When multiple
alarms occur, the details are displayed cyclically.
Exiting the alarm is only possible by pressing the button
, with the exception of alarm
AL12 (overheating boiler), which the controller automatically exits when the temperature
falls below the value set in S17, 4°C. When the user accepts conditional operations, the alarm
is swithched off but is activated again every time the controller is turned on.
Types of alarm
•
AL1
→
Blown fuse/temperature limiter tripped
•
AL2
→
Damage of water outlet boiler temperature sensor
•
AL3
→
Damage to fuel feeder temperature sensor
•
AL4
→
damage to DHW/returning water temperature sensor
•
AL9
→
Fuel feeder not turning/ damage to reed relay
•
AL11
→
Maximum fuel feeder temperature exceeded
•
AL12
→
Overheating boiler
•
AL13
→
Boiler extinguished
Type of notes (warning):
•
UW4
→
damage to DHW/returning water temperature sensor
•
UW10
→
Anti-Legionella function notexecuted
•
UW17
→
Elevated temperature in fuel feeder