6.8.
Maximum feeder temperature detection
The GH10PA Controller is equipped with an additional option protecting it from fuel feeder temperature
rise above the permissible value to prevent backfires into the fuel feeder.
The detection is active in the automatic boiler operation mode (AUTO, MAINTAIN, ALARM).
When the measured temperature exceeds the value set in the
F14
service setting, the fuel feeder activates for
the period of time set in the
F16
service setting to eject the ignited fuel from the feeder. During the
F16
period the fan remains inactive.
When the time set in
F15
service setting elapses, the Controller restores the maximum feeder temperature
detection process.
When the feeder T exceeds 90°C the fan is deactivated, the fuel feeder is activated for a period of 2x
F16
, and
the display indicates the alarm condition
AL11 – “Maximum feeder temperature exceeded”
.
(
section 6.5
page 12).
The Controller remains in the alarm condition until user response.
IF F14=0, THEN FEEDER SENSOR OPERATION IS DISABLED AND THE
MAXIMUM FEEDER TEMPERATURE DETECTION FUNCTION IS NOT
ACTIVE.