GH10PA USER MANUAL
PAGE
11
PPUH “GECO” Sp. z o.o. [Ltd.] Issue II
SINCE DECEMBER 2011
6.3.
Manual operation mode
Pressing
causes the Controller to switch from automatic to manual mode, and immediately
deactivates the fan, the feeder and the pump.
In this mode, you can manually and independently activate and deactivate the fuel feeder and the fan. To
do this, follow the scheme below:
In the manual operation mode, you can also activate the CH pump and the container feeder. To
activate the CH pump, press the following keys simultaneously:
+
. The CH pump activation and
operation are indicated by means of a
vertical
line on the left side of the display, in the
upper
sign segment,
on the Controller main display screen (
section 1.3 page 4).
To activate the container feeder, press the following keys simultaneously:
+
. The
container feeder activation and operation are indicated by means of a
horizontal
line on the left side of the
display, in the
lower
sign segment, on the Controller main display screen
(
section 1.3 page 4
)
.
6.4.
Viewing temperatures
After pressing
, the display shows water temperature at the boiler outlet. Viewing the feeder
temperature and flame sensor measurement is available in the AUTO and MAINTAIN modes, but only if the
feeder sensor and/or flame sensor are properly enabled.
Press
to view the feeder temperature. Press the key again to exit the view. You can also wait for
automatic exit 10s from pressing the key.
Press
to view the flame sensor measurement. Press the key again to exit the view. You can also wait for
automatic exit 10s from pressing the key.
STEP 1
STEP 2
→
Controller
indicates water
temperature
measured on the
boiler
Burner feeder
Lower
key indicator lights
up. Press the key again to
deactivate the feeder and the
indicator.
Fan
Upper
key indicator lights
up. Press the key again to
deactivate the feeder and the
indicator.