Geco GH10PA Скачать руководство пользователя страница 12

GH10PA USER MANUAL

 

PAGE 

12

 

PPUH “GECO” Sp. z o.o. [Ltd.]                           Issue II 

SINCE DECEMBER 2011

 

6.5.

 

Alarms 

The Controller uses 7 different alarms. In each alarm condition, the Controller displays the alarm number 

and activates the alarm sound output. In case of several alarm conditions occurring simultaneously, their 

numbers are displayed in sequence. You can exit an alarm condition only by pressing 

, except the AL12 

alarm. 

Alarms: 

 

AL1

 

 

STB activated or fuse blown 

 

AL2

 

 

Boiler water outlet temperature sensor failure 

 

AL3

 

 

Feeder temperature sensor failure 

 

AL11

 

 

Maximum feeder temperature exceeded 

 

AL12

 

 

Boiler overheating 

 

AL13

 

 

Boiler burnout 

 

AL14

 

 

Burnout when firing up 

 

6.6.

 

Power failure 

After power failure the Controller resumes operation according to the condition it was in before the 

power failure. The Controller waits 1 minute for the mains power parameters to stabilise, and then resumes 
operation with the previously entered settings.  

During the waiting period, the display shows time in seconds remaining until the end of the period, 

together with indication of its condition before the power outage:  

 

blinking “A” for AUTO mode, 

 

blinking “P” for MAINTAIN mode, 

 

blinking “r” for MANUAL mode.  

 

Respective indicators (AUTO 

 or MAINTAIN 

 ) are blinking together with the letters. 

 

6.7.

 

Boiler burnout detection 

6.7.1.

 

No fuel 

If during automatic operation the boiler outlet water temperature remains below the 

F08

 setting for a 

period of time set in the 

F09

 setting, then the Controller considers the boiler as “burned out” and enters the 

AL13

 alarm condition. 

6.7.2.

 

Sudden Drop of Outlet Water Temperature 

If during automatic operation the boiler outlet water temperature drops by 10°C, and during that 

dropping period the temperature does not rise by 4°C, then the CH pump is switched off, and the Controller 
goes into the burnout detection mode. 
 
The Controller waits for the period of time, during which it checks whether a rise of 4°C occurs.  
If YES, then the burnout detection condition is stopped, and the CH pump (if necessary) is started. 
If NOT, this means that the furnace is burned out – the Controller enters the 

AL13

 alarm condition. 

 

Содержание GH10PA

Страница 1: ...applicable Instructions before connecting and starting up any of our products Should any doubts arise please contact our Company between 8 a m and 4 p m Attention At the bottom of each page you will...

Страница 2: ...IGURATION 8 6 2 AUTOMATIC OPERATION MODE 9 6 3 MANUAL OPERATION MODE 11 6 4 VIEWING TEMPERATURES 11 6 5 ALARMS 12 6 6 POWER FAILURE 12 6 7 BOILER BURNOUT DETECTION 12 6 8 MAXIMUM FEEDER TEMPERATURE DE...

Страница 3: ...ry in described instructions to follow the sequence of carried out operations The unit may be damaged or destroyed in case of any error or proceeding in discord with the description Important This sym...

Страница 4: ...Mount Technology SMT It is designed to control the main Central Heating CH water circuit Control parameters can be adjusted to the current operating conditions and boiler type The Controller includes...

Страница 5: ...5 86 Fan 1A 200W 90 202 37 Heater 3A 600W 100 149 16 4 ELECTRICAL SYSTEM AND CONNECTION RULES Boiler room should be equipped with 230V 50Hz electrical system according to applicable regulations Electr...

Страница 6: ...I SINCE DECEMBER 2011 5 QUICK START Carry out the following operations in order to activate the GH10PA controller quickly 1 Connect the unit to the mains plug in power supply cable Switch on the contr...

Страница 7: ...g screen will appear and the controller will start automatic operation based on preset factory parameters Table 1 Factory settings chart User parameter Description Factory settings U0 Boiler preset te...

Страница 8: ...INCE DECEMBER 2011 6 OPERATION OF THE GH10PA 6 1 System configuration Fig 1 Central Heating circuit INPUT OUTPUT T1 Boiler temperature P1 Burner feeder T2 Feeder temperature P2 Fan C1 Flame sensor P3...

Страница 9: ...e Controller additionally indicates whether it activates the feeder the fan or the heater The heater activation and operation are indicated by means of a horizontal line on the left side of the displa...

Страница 10: ...e 4 6 2 4 CH pump In the AUTO mode the CH pump is activated when the temperature of the boiler water is higher or equal to the value set in the F06 service setting factory setting is 40 C The CH pump...

Страница 11: ...tivation and operation are indicated by means of a horizontal line on the left side of the display in the lower sign segment on the Controller main display screen section 1 3 page 4 6 4 Viewing temper...

Страница 12: ...the display shows time in seconds remaining until the end of the period together with indication of its condition before the power outage blinking A for AUTO mode blinking P for MAINTAIN mode blinking...

Страница 13: ...er activates for the period of time set in the F16 service setting to eject the ignited fuel from the feeder During the F16 period the fan remains inactive When the time set in F15 service setting ela...

Страница 14: ...o to U1 Set the new desired value Save the new temperature setting Move to the U2 setting 7 3 Feeder stop time U2 This is the period of time between two consecutive fuel feeds in the AUTO mode Setting...

Страница 15: ...ALS 15 AND 16 SHOULD BE SHORTED If due to boiler temperature rise the temperature limiter is activated and opens its terminals it will disable feeder and fan power supply in order to stop fuel and air...

Страница 16: ...P1 54 55 Flame sensor C1 09 N Burner feeder P1 55 56 57 Fuel level sensor C2 06 L CH pump P4 05 N CH pump P4 08 L Container feeder P5 07 N Container feeder P5 04 L Heater P3 03 N Heater P3 02 N Power...

Страница 17: ...the need for selective collection of worn out electrical and electronic equipment It means that this product should not be disposed of with other household wastes Proper disposal of aged and worn out...

Страница 18: ...ANUAL PAGE 18 PPUH GECO Sp z o o Ltd Issue II SINCE DECEMBER 2011 P P U H Geco Sp z o o Ltd Cholerzyn 376 32 060 Liszki Poland ph 48 12 636 98 11 636 12 90 fax 48 12 636 20 02 http www geco pl e mail...

Отзывы: