Page 14 Edition I
03.12.2012
8.
Operating system installations.
8.1
Heating installation nr 1
The following is a list specifying the parameters available to the user, and the assignment of
outputs to attached devices and inputs for temperature sensors.
Installation nr 1 – Parameters available to the user
Parameter
Range
Factory setting
U0
30 (F03) ÷ 85 (F04)
60°C
U1
25 ÷ 85
50°C
Installation nr 1 – Assignment of controller outputs
Output
Connected device
12-13
Electrode boiler
O5-O6
CH pump
O7-O8
---
Installation nr 1 – Assignment of inputs
Input
Description
50-51
Temperature sensor - water returning to boiler
52-53
Temperature sensor – water flowing from
boiler/Room temperature
54-55
---
55-56
Room temperature
58-59-60-61
GA01HC - GECO room panel dedicated for
GH07EB