Gebwell G-Power® substation installation manual 

10 

Electrification

 

Ensure that all the electrical parts are in faultless condition and are firmly fixed to the substation and 
piping. Once the pipework is finished and the water has been connected, an electrician is not necessarily 
needed for the start-up of the G-Power Easy single-family house substation. 

If you are uncertain, ask an electrician to perform the following operations: 

 

Install the outdoor temperature sensor to the north wall of the building at a height of approximately 3 
m. The sensor measures the current outside temperature (do not install the sensor near ventilation 
windows). 

 

The outdoor temperature sensor includes a wire and a plug. Connect the outdoor temperature sensor 
plug to the connector in the control box that is marked with the decal “outdoor temperature sensor 
wire”. Alternatively, the outdoor temperature sensor can already be connected directly to the 
controller.  

 

Check that all the pipes are filled with water and that the air has been bled out of them. 

 

Connect the power supply plug of the controller power supply unit and circulation pump P2 to a 
grounded wall socket with 10A/230V fuses. 

 

Wait from approx. 10s, turn on the circulation pumps P1 (domestic hot water) and P2 (heating) on the 
operating switch.  

 

Switch on the controller. See “User instructions for controllers”. 

For underfloor heating, connect a pre-wired pump stop thermostat (TS2 / TS3) to the heating supply pipe.  
The electrical connection is ready. Attach the sensor on the heating supply pipe as far as possible from the 
heat exchanger. The minimum distance is 1 m. Set the temperature to, for example, 55°C. 

5.

 

Things to note 

Differential pressure in the district heating circuit

 

The differential pressure generated by the district heating circuit pumps enables the circulation of district 
heating water in the district heating circuit and in each customer’s district heating equipment. The district 
heating circuit pressure and differential pressure can vary. For example, the pressure and differential 
pressure values are usually higher in the winter than in the summer.  

Customer’s district heating equipment is usually designed for a differential pressure of 60 kPa (0.6 bar).  

If the differential pressure in the district heating circuit is high (> 2 bar), we recommend that a differential 
pressure controller is used. 

Sound engineering practice

  

According to the Finnish Pressure Equipment Act 1144/2016, pressure equipment that is not subject to the 
essential safety requirements referred to in section 14 of the Act due to its characteristics shall be designed 
and manufactured in accordance with the sound engineering practice of a Member State in the European 
Union. 

Pressure equipment designed or manufactured in accordance with the sound engineering practice shall not 
bear the CE mark referred to in section 17 of the Act. 

G-Power substation is designed and manufactured in accordance with the sound engineering practice.  

 

 

Содержание G-Power 2/100

Страница 1: ...Installation and maintenance manual G Power small substations WWW GEBWELL COM...

Страница 2: ...strict heating substation 3 4 Installing the G Power Easy district heating substation 9 5 Things to note 10 6 General terms of warranty 11 7 G Power district heating substation dimensions and connecti...

Страница 3: ...ailable whereas the largest coastal cities use coal and the peat areas primarily use peat District heating is available throughout the year 24 hours a day Moreover the temperature of the hot water pro...

Страница 4: ...heating circuit 3 circuits G Power 3 100 domestic hot water circuit and two heating circuits Model designation 2 3 indicates the number of control circuits 100 200 indicates the power class 100 detach...

Страница 5: ...etwork control curve Changing the heating network control curve The district heating substation is delivered with underfloor heating values unless otherwise stated If the values need to be changed to...

Страница 6: ...rcuit The pump is of the wet motor structure The installation technician selects the pump pressure according to the site plan to achieve the desired flow The pump must be stopped if there is no pressu...

Страница 7: ...Use the pre charge pressure with static pressure taken into account value in the table for setting the expansion tank pre charge pressure The table below shows the expansion tank pre charge pressure...

Страница 8: ...n points back to the heat exchanger The pipe ensures that hot water is available from the utilisation points after a certain waiting period Domestic hot water circulation decreases water consumption T...

Страница 9: ...l valves It is factory adjusted to a setting of 120 kPa which is six revolutions downwards from the topmost position of the regulating wheel One revolution 360 of the regulating wheel corresponds to a...

Страница 10: ...so that the control panel faces forward Installing the G Power substation on the wall Attach the wall mounting rail carefully on to the wall Lift the district heating substation to hang from the ail a...

Страница 11: ...a pre wired pump stop thermostat TS2 TS3 to the heating supply pipe The electrical connection is ready Attach the sensor on the heating supply pipe as far as possible from the heat exchanger The mini...

Страница 12: ...e pressure peaks Outside stress temperature mechanical stress etc Repairs carried out by anyone other than a company authorised by Gebwell Ltd Poor quality water in circulation i e the water does not...

Страница 13: ...n dimensions and connections G Power 2 100 and G Power 2 150 G Power 3 100 1 TO DISTRICT HEAT NETWORK 2 FROM DISTRICT HEAT NETWORK 3 DOMESTIC HOT WATER 4 COLD WATER SUPPLY 5 DHW CIRCULATION 6 TO HEATI...

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ...t RECOMMENDATION SETTING INDICATION Lowest relative pressure curve RECOMMENDATION SETTING INDICATION Lowest constant pressure curve or Constant Pressure Auto Adapt QUICK GUIDE GRUNDFOS UPM3 PUMP SETTI...

Страница 22: ...rn it using a screw driver 2 The LED is lit Supply voltage too low Check the supply voltage 3 The LED is lit Supply voltage too low severe malfunction Check the supply voltage Replace the pump TROUBLE...

Страница 23: ...is stuck To release the axle impeller press on the screw in front of the pump and turn it using a screw driver 2 The LED is lit Supply voltage too low Check the supply voltage 3 The LED is lit Supply...

Страница 24: ...valtiossa noudatettavan hyv n konepajak yt nn n mukaisesti T llaisissa laitteissa tai laitekokonaisuuksissa ei saa olla 18 artiklassa tarkoitettua PED direktiivi koskevaa CE merkint PED2014 68 EU spec...

Страница 25: ...Gebwell Ltd Business ID 2008956 7 Patruunapolku 5 FI 79100 Lepp virta FINLAND Tel 358 20 1230 800 info gebwell www gebwell com...

Отзывы: