8
D
GB
F
E
96459-08.2018-DGb
The compressors are filled at the factory with the following oil type:
Compressor version
ML
and
S: GEA C85E
Compressor version
SH:
GEA C150E
(only this oils may be used)
3.1 Refrigerants
•
CO
2
: R744 (Recommendation CO
2
quality 4.5 (< 5 ppm H
2
O))
3.2 Oil charge
ATTENTION Compressor operation is possible within the operating limits
shown in the diagrams. Please note the significance of the
shaded areas. Thresholds should not be selected as design or
continuous operation points.
- Permissible ambient temperature (-20 °C) - (+60 °C).
- Max. permissible discharge end temperature 160 °C.
- Min. discharge end temperature
≥
50 °C.
- Min. oil temperature
≥
30 °C.
- Max. permissible switching frequency 12x /h.
- A minimum running time of 3 min. steady-state condition
(continuous operation) must be achieved.
Avoid continuous operation in limit range.
For operation with frequency converter:
- Frequency range 20 - 70 Hz.
- The maximum current and power consumption must not be
exceeded. In the case of operation above the mains frequency,
the application limit can therefore be limited.
3.3 Limits of application
ATTENTION Property damage possible.
The oil level must be in the
visible part of the sight glass;
damage to the compressor
is possible if overfilled or
underfilled!
Fig. 4
Max.
Min.
0.9 Ltr.
Oil level
~
~
3
|
Areas of application