Fig.11:
Pre-lubrication valve (P), Oil control pressure regulator (B)
Caution!
Pre-lubrication just before the first start is obligatory.
1.4.4
Initial refrigerant charge
Refrigerant charging should be done in accordance with the plant manual by
qualified refrigeration engineers.
1.4.5
Adjustment of instruments and safety devices
1.4.5.1 CONTROL DEVICES
Hint!
Refer to separate user manuals, in case an electrionic control device
is installed.
1.4.5.2 PRESSURE SETTINGS
Pressure safety limit switches
Suction pressure *
1
Setting
5
o
C below design evaporating temp.
Min.
0.3 bar(a)
Suction and
intermediate
pressure
Setting
Max.= refer to Product Information (PI)
Setting
5
o
C above design condensing temp.
Discharge pressure
Max.
24 bar(a)
Grasso V 700HS
Grasso V 1100HS
Grasso V 1400HS
Grasso V 1800HS
Lubrication oil
pressure difference
Setting
Min. =1.3 bar
1
Settings Pdischarge - Psuction must never exceed max. value as mentioned in Product Information
INSTALLATION AND PREPARATION FOR USE
PREPARATIONS FOR USE
P-NL-094_imm_VHS_English_13
26
26.07.2021