background image

24

Sub-Base (Cont.)

There are separate internal compartments to permit
separation of low voltage (Class 2) connections from line
voltage connections as required by NEC. Conduit containing
building wiring enters the sub-base through knockouts
located in the rear or bottom of the sub-base  and is not
accessible when the wall case is installed.

The sub-base attaches to the RAB71 wall case with  two clips
(field assembled) that are screwed into pre-drilled holes in
the bottom front flange of the wall case. It attaches to the
RAB77 wall case with clips that fit over molded ribs without
requiring the use of screws into the wall case. See page 33
for illustration. Since the sub-base extends under the wall
case, clearance from the inner edge of the wall case to the
finished wall must be 2-3/8" or greater. The sub-base has 4
leveling legs and adjustable side channels to enable the area
under the wall case to be enclosed. Clearance from the
bottom edge of the wall case to the finished floor must be
between 3" and 5".

The sub-base may be used as support for the chassis and wall
case in installations where the wall is of insufficient thickness
to provide secure mounting of the wall case.

Wall Case Installation Data

General 

Generally, Zoneline units are installed 3" to 5" above the
floor (flush to finished floor installation is possible) as near
to the center of the room as possible; underneath a window
or a glass panel is typical. Normal installation of the wall case
allows installation flexibility; from flush with the finished
interior wall to a minimum of 1/4" of the wall case
extending beyond the finished exterior of the building.
Special consideration must be given to installations where
the wall case does not extend a minimum of 1/4" beyond
the finished exterior wall. See pages 30 and 31 for
information on this type of installation. The unit may be
installed high in the wall and these installations usually
require a remote thermostat and are discussed on 
pages 17 and 18.

Regardless of the installation, there are several things to
consider when selecting a location for installing the unit. For
instance, drapery location could interfere with air discharge,
and placement of furniture may have an impact on the
performance of the unit. The following information is
intended to minimize installation problems and assure you
of trouble-free installation.

Refer to page 22 for required wall opening dimensions.
Minimum recommended interior and exterior case
projection for standard wall thicknesses are shown in the
drawings in this manual. The case may be installed flush
with the finished indoor wall. Special attention must be paid
to room-side case projection when the unit is installed in a
ducted application as shown on page 39.

In walls thicker than 13 1/2" for line cord connected units
and 11 1/8" for sub-base installations, it may be necessary to
install a field fabricated case extension or use one of the
special order RAB71 deep wall cases. If you are unable to
locate a local source for case extensions please contact your
salesperson for a possible supplier. Such extension must be
carefully flashed and sealed both to the wall case and to the
wall to insure water integrity. This is necessary to insure that 

any water entering the wall case, either from operation of
the unit or from other sources, such as rain storms or from
washing the exterior of the building, will drain from the case
without the possibility of capillary action drawing the water
into either the room or the wall cavity.  In an installation
where the case is recessed less than 3" from the outside
surface, flashing and sealing may be all the modificaton
necessary. In such an installation, the sides and top of the
wall opening must be waterproof to prevent moisture from
seeping into and damaging the walls. See Pages 30 and 31
for suggested detail. Since the installation of a case
extension requires a considerable amount of attention, we
recommend using one of the deep wall cases if the standard
case is not of sufficient depth.

Mounting an outdoor grille or louver section to the building
face may cause a space between the outdoor coil and the
louver section. Air splitters, aligned with the ends of the
outdoor coil, must be installed between the outdoor coil
inlet and outlet air streams. Gaps between the outdoor coil
and the louver section may allow condenser air recirculation
and affect the operation of the unit. See page 40 for
requirements for custom louver sections.

The wall case should be level from side to side and from
level to 1/4 bubble tilt to the outdoors. The condensate
disposal system in the unit is designed to dissipate the
condensate water generated during cooling operation in
accordance with ARI standards and actually uses this
water for maximum unit efficiency. A level unit will also
insure proper performance of the Internal Condensate
Removal (ICR) system optional on heat pump units.

For new construction, early planning with the architect is
necessary. Unit location, electrical connection locations, and
wall openings of the proper dimensions are essential to
avoid the necessity of rework, fillers, framing, moving
electrical outlets, and other expensive modifications. 

For existing construction it is important that carpentry,
masonry and electrical work be performed by competent,
qualified personnel. 

Since installations in existing

construction may involve removal of building material from
the structure, locating the wall case must be done correctly.

Window, Curtain and Panel Wall Construction

With this type of construction, provision for support of the
unit, other than by the wall itself, is often required. Such
support may be in the form of wood or metallic material of
the proper thickness to maintain a level case. This additional
support should be located both near the wall and at the
front of the wall case. Sub-base (RAK204 Series) with four
leveling legs provides an excellent support for the unit in
this type of installation. See page 28 for details of this type of
installation.

In existing construction, common practice is to remove a
pane of glass, metal, wood, or other construction material
and build  a frame around the wall case. Similar filler panel
material may be installed around the case for appearance
and weather seal.

1719 Data Manual 2001  2/14/02  3:12 PM  Page 24

Содержание Zoneline 5500

Страница 1: ...Architects and Engineers Design Data Manual Featuring The NEW 5500 Series Z O N E L I N E PA C K A G E D T E R M I N A L A I R C O N D I T I O N E R S We bring good things to life ...

Страница 2: ...Heater Heat Protection Btuh Watts Amps Amps AZ35H07D2 7100 6900 600 585 11 8 11 8 6400 6200 3 5 3 5 8600 7100 2550 2090 11 0 10 0 15 AZ35H07D3 7100 6900 600 585 11 8 11 8 6400 6200 3 5 3 5 11700 9600 3450 2820 15 0 13 6 20 AZ35H09D2 9000 8800 785 765 11 5 11 5 8400 8200 3 5 3 5 8600 7100 2550 2090 11 0 10 0 15 AZ35H09D3 9000 8800 785 765 11 5 11 5 8400 8200 3 5 3 5 11700 9600 3450 2820 15 0 13 6 2...

Страница 3: ...ling capacity electrical information and optional features included on the unit When specifying or ordering the Zoneline chassis use of this nomenclature will assure receiving the correct unit Example A Z 2 5 E 0 9 E 4 P A Z 5 5 H 1 2 D A D Zoneline Packaged Terminal Chassis Chassis Series 25 Deluxe Line Cool Electric Heat 35 Deluxe Line Heat Pump 55 Premium Line Heat Pump Unit Type E Cooling with...

Страница 4: ...s Removes 25 More Moisture GE Dry Air 25 GE 2500 Series Zoneline Amana Carrier The Deluxe 2500 Series Zoneline Models Includes The Dry Air 25 Models Which Remove 25 More Moisture Than Other Zoneline Models Deluxe Dry Air 25 Models Cooling With Resistance Heat Removes 25 More Moisture than other Zoneline Models up to 2 7 Additional Gallons Per Day Cool and Dry Air in Less Time than Standard Zonelin...

Страница 5: ... 41 43 Maximum Connected Load 44 Cooling Heat Pump Performance Data 45 Latent System Capacity 46 Normal Yearly Operating Data 47 Schematics 48 50 Product Specifications Suggested Bid Form Specifications 51 53 Specifications 54 55 Complete Accessory List 56 General Suggestions 57 58 Alphabetical Index 59 Back Cover Warranty 60 Important Notice Equipment used as a primary source for heating or cooli...

Страница 6: ...e Simultaneous Heat Pump and Resistance Heat Operation when needed Exclusive Reverse Cycle Defrost to Increase Heat Pump savings Touch Pad Controls with Digital Temperature Readout Advantages of the GE Zoneline System Flexible Application May be installed flush to finished floor to 3 from the ceiling 7 100 to 14 700 BTUH units in same physical size Deluxe 2500 and 3500 Series may be ducted to cond...

Страница 7: ...ne can result in unsatisfactory operation and can be the cause of failure not covered by the warranty Components of the Zoneline System Room Cabinet Chassis Wall Case RAB71 Steel Insulated RAB77 SMC Molded Wall Case Options See page 23 RAG67 shown Grill Options See page 40 Deluxe Series shown Power Connection Kit not shown required on Premium Series See pages 42 43 Typical Installation Optional Ac...

Страница 8: ...ections AUTO HIGH Standard Standard Standard Fan Only Setting HIGH LOW Standard Standard Standard Fan Cycle Switch Smart Fan Smart Fan Smart Fan Rotary Compressor Standard Standard Standard Automatic Compressor Restart Delay Standard Standard Standard Power Connection Cord Included Included UPC Freeze SentinelTM Standard Standard Standard Indoor Coil Frost Control Standard Standard Standard Transf...

Страница 9: ...the outdoor temperature is above 45 F during normal operation The resistance heat is used in the Quick Heat Recovery feature Automatic Emergency Heat Heat Pump Defrost Systems See pages 19 and 20 for discussion of heat pump operation and defrost systems High Temperature Heat Pump Operation Protection Automatically protects the compressor if heat pump is operated with high outdoor temperatures Shut...

Страница 10: ...mage by freezing temperature in the room Heater automatically turns on at 41 F warms indoor thermistor temperature to 46 F and shuts off Freeze Sentinel may be turned off by dip switch on auxiliary control Indoor Coil Frost Control Prevents indoor coil from freezing and causing complaints due to lack of cooling Frost can form on the indoor coil when the unit is operated in cooling when outdoor tem...

Страница 11: ...osion protected chassis is standard on Dry Air 25 models Heat Pump units with ICR are not available with corrosion protection and should not be installed in seacoast or corrosive environment Units installed in corrosive areas should be examined and cleaned more frequently than normal installations Internal Condensate Removal ICR See page 34 for a discussion of the Internal Condensate Removal syste...

Страница 12: ...nit Up Fan under Smart Fan settings 6 FREEZ S Freeze Sentinel Override Down Freeze Sentinel ON Up Freeze Sentinel OFF 7 CONST FAN Constant Fan Fan runs when unit is in STOP mode 8 OCCUPIED Occupancy Sensor Mode Down Unit Control Up Occupancy Sensor Connected Temp L1 Temp L3 Cooling temperature limiting See table at bottom of page Temp L4 Temp L6 Heating temperature limiting See table at bottom of ...

Страница 13: ... Sentinel OFF 7 CONST FAN Constant Fan Fan runs when unit is in STOP mode 8 OCCUPIED Occupancy Sensor Mode Down Unit Control Up Occupancy Sensor Connected Temp L1 Temp L3 Cooling temperature limiting See table at bottom of page Temp L4 Temp L6 Heating temperature limiting See table at bottom of page BOOST Turns on supplemental heater with heat pump when outdoor temperature is below 45 F DIAGNOS Us...

Страница 14: ...C interface that permits the unit to be connected to most energy management systems The devices connected to the Zoneline units require no power supply or transformers external to the unit Important CDC Comments all series applicable 1 When the switching device closes the circuit of the CDC conductors the unit operation stops 2 Do not use a common buss at the unit or at the switch panel in the wir...

Страница 15: ...tion wires RAK163P1 a solid state digital programmable auto changeover thermostat requiring 5 connection wires The Class 2 Mode Switch dip switch 12 on the auxiliary control board must be set to the ON UP mode to enable remote thermostat control Refer to installation instructions packaged with the chassis Please see page 57 for installation recommendations for the remote thermostat wiring Compatib...

Страница 16: ...ts RAK147 mechanical manual changeover thermostat requiring 6 connection wires RAK147D1 solid state digital manual changeover thermostat requiring 6 connection wires RAK147P1 solid state digital programmable auto changeover thermostat requiring 6 connection wires Please see page 57 for installation recommendations for the remote thermostat wiring Compatibility of other thermostats considered for u...

Страница 17: ...2500 RAK163D1 Digital Cooling and Heating 5 RAK163P1 Digital Programmable 5 RAK147 Mechanical Single Stage 6 3500 and RAK147D1 Digital Cooling 6 5500 RAK147P1 Digital Programmable 2 Stage Heating 6 Thermostat wire size up to 60 feet AWG20 up to 66 feet AWG18 Feature 3500 Series 5500 Series Indoor Frost Control Yes Yes Freeze Sentinel Yes Yes Auto Fan Speed No No Electronic Temperature Limiting No ...

Страница 18: ...stat Controlling Three Zoneline Units Resistance Heat Zoneline 2500 Series Units Not Applicable on Heat Pump Units Remote Thermostat Control Multiple Units Connected to One Remote Thermostat 2500 Series One remote control thermostat may be used to control multiple resistance heat Zoneline units however the units may not be wired direct Since each Zoneline unit has an integral transformer direct wi...

Страница 19: ...ngs This determination of the heat source based on the indoor temperature helps provide a more comfortable room Heat Pump Operation Zoneline 3500 Series Switchover to resistance heat is determined by indoor temperature differential and outdoor coil temperature The Zoneline 3500 Series heat pumps are Standard Microprocessor controlled units A solid state thermostat control is used to measure the ro...

Страница 20: ...e Zoneline 5500 Series Heat Source Logic shown in the chart above For more information about the Quick Heat Recovery Feature see page 9 The full heat output of the resistance heater is dependent upon circuit amperage and the power connection kit used See pages 42 43 for information on the power connection kits and available heater capacities A heat pump override switch is provided in the auxiliary...

Страница 21: ...and mildew growth in hot humid climates Air Infiltration Excessive air infiltration can magnify problems associated with undersizing or oversizing of an air conditioner unit and can be the root cause of insufficient cooling dehumidification or heating Some sources of air infiltration include vents gaps around windows and doors and improperly sealed floor ceiling and wall joints Recommendation For ...

Страница 22: ...AB7116 16 RAB7124 24 RAB7128 28 RAB7131 31 42 13 3 4 16 1 1 2 TYP 1 2 6 21 36 A 1 2 SQ HOLE 2 REQ D 1 2 DIA HOLE 3 REQ D 2 3 4 5 5 8 4 6 19 36 16 1 4 13 7 8 1 1 2 42 1 8 1 2 SQ HOLE 2 REQ D 9 16 2 7 8 5 5 8 4 1 2 DIA 3 REQ D RAB71 42 RAB77 42 1 8 RAB71 13 3 4 RAB77 13 7 8 42 TOP VIEW GRILLE ROOM CABINET INSIDE ROOM CABINET SIDE VIEW RAB71 20 7 8 RAB77 21 OUTSIDE RAB71 16 RAB77 16 1 4 GRILLE 7 1 8 ...

Страница 23: ...iring and installations must conform to any and all local electrical codes and regulations Permanent Connection generally means wiring between the building wiring and the unit must be contained in an enclosed chaseway where access to the wiring connections is more restrictive than a normal line cord plugged into a receptacle NEC requirements may be met by using flexible or rigid conduit to contain...

Страница 24: ...contact your salesperson for a possible supplier Such extension must be carefully flashed and sealed both to the wall case and to the wall to insure water integrity This is necessary to insure that any water entering the wall case either from operation of the unit or from other sources such as rain storms or from washing the exterior of the building will drain from the case without the possibility...

Страница 25: ... side and from level to 1 4 bubble tilt to the outdoors The condensate disposal system in the unit is designed to dissipate the condensate water generated during cooling operation in accordance with ARI standards and actually uses this water for maximum unit efficiency A level unit will also insure proper performance of the Internal Condensate Removal ICR system optional on heat pump units 2 The w...

Страница 26: ...led MAIN STUDS JACK STUD HEADER MOUNTING SCREW HOLE LINTEL Framing detail for this construction is as shown in Figure 1 Note use of lintel under first course of brick above the Zoneline case Do not use the case as a lintel Mounting screw holes shown are to be made by the installer NO HOLES PERMITTED IN BOTTOM OF CASE EXCEPTION RAD10 DRAIN KIT Choice of attachment devices through both ends of case ...

Страница 27: ...T WALL RECEPTACLE BY OTHERS FINISHED FLOOR OR TOP OF CARPET Caulk around perimeter of wall case all four sides where it joins the building Interior and Exterior CAULK 1 4 CAULK LINTEL RAB71 13 3 4 RAB77 13 7 8 20 7 8 RAB71 21 RAB77 ROOM CABINET 2 MIN MOUNTING SCREWS BY INSTALLER RAB71 16 RAB77 16 1 4 WALL CASE OUTDOOR GRILLE SIDE CHANNEL 3 MIN 5 MAX 1 5 16 FINISHED FLOOR OR TOP OF CARPET SUB BASE ...

Страница 28: ...our sides where it joins the building CASE ANGLE FIELD SUPPLIED RAB71 22 1 4 RAB77 22 3 8 WITH RAG61 66 RAB71 21 1 8 RAB77 21 1 4 WITH RAG60 RAB71 16 RAB77 16 1 4 RECEPTACLE BY OTHERS MIN 2 SUPPORTS FIELD SUPPLIED FLOOR USE NO SCREWS IN BOTTOM OF CASE 16 ROOM CABINET WALL CASE OUTDOOR GRILLE CASE ANGLE FIELD SUPPLIED RAB71 22 1 4 RAB77 22 3 8 WITH RAG61 66 RAB71 21 1 8 RAB77 21 1 4 WITH RAG60 RAB7...

Страница 29: ...2 1 8 FINISHED EXTERIOR WALL ROOM CABINET RAB71 13 3 4 RAB77 13 7 8 ADJACENT WALL ADJACENT WALL D A C D 27 1 4 TOP VIEW 2 1 2 Caulk around perimeter of wall case all four sides where it joins the building Interior and Exterior ROOM CABINET LINTEL FRONT VIEW ELECTRICAL RECEPTACLE BY OTHERS FLUSH MOUNTED WALL OPENING 16 1 4 x 42 1 4 MIN FOR RAB71 16 1 2 x 42 3 8 MIN FOR RAB77 See page 42 for line co...

Страница 30: ...ts be additionally sealed with a quality grade sealant 2 The wall case and extension should be connected prior to installation in the wall opening A quality grade sealant should be applied to all four 4 butting flanges Use bolts and nuts or oversized self tapping screws driven from the wall case to the extension to attach the two assemblies Clean all drain holes of excess sealant The assembly must...

Страница 31: ... THE CASE D 2 MINIMUM CAUTION WHEN CAULKING DO NOT BLOCK DRAIN HOLES IN CASE OR GRILLE IF GRILLE IS TO BE MOUNTED TO WALL SURFACE A SPLITTERS MUST BE USED SEE PAGE 30 B D C A B Caulk around perimeter of wall case all four sides where it joins the building Interior and Exterior DRIP FLASHING OUTDOOR GRILLE CASE For an installation that will provide better protection against water infiltration GE re...

Страница 32: ... NOTE LEFT SIDE INTERIOR ADJACENT WALL 12 3 4 12 7 8 13 LEVELING SCREW KNOCKOUT SIZE LARGE 1 1 8 DIA SMALL 7 8 DIA KNOCKOUTS ENCLOSURE 4 REAR 4 BOTTOM SHOWN WITH ACCESS COVERS REMOVED NOTE CAUTION REMOVE KNOCKOUTS FROM INSIDE OUT SIDE VIEW WITH WALL CASE SHOWN IN PLACE FINISHED FLOOR 3 MIN ADJUSTABLE TO 5 1 5 16 2 3 8 INTERIOR WALL RAB71 16 RAB77 16 1 4 7 8 1 1 2 FINISHED FLOOR RAB71 16 RAB77 16 1...

Страница 33: ...G TYPE A SCREWS 6 TYPE A SCREW TYPE C SCREW ACCESS PLATES TYPE C SCREW TYPE B SCREW SIDE CHANNELS ARE ADJUSTABLE FROM 13 3 4 TO 2 3 8 IN LENGTH BY BREAKING OFF SECTIONS OF SIDE CHANNELS NOTE IF METAL CASE DOES NOT HAVE SCREW HOLES 5 32 DIA HOLES MUST BE DRILLED 6 FROM EACH SIDE IN FRONT FLANGE SEE INSERT Electrical wiring may enter the sub base through any of the knockout holes provided in the sub...

Страница 34: ... the dew point is humidity as well as temperature related there may be more condensate on days when the relative humidity is high Heat Pump Condensate Disposal Since the outdoor coil is cold during heat pump operation the condensate water cannot be deposited on the outdoor coil as the water would cause frost to form on the coil This frost would block the air flow through the coil and greatly dimin...

Страница 35: ...ter or precipitation to flow into the wall case and drain through two drain holes in the rear of the wall case If there is more water in the wall case than can be drained through these holes it will drain through the three overflow drain holes These drain holes must not be blocked when mounting or caulking the wall case For those installations where water draining from the drain holes is objection...

Страница 36: ...E BOTTOM OF THE WALL CASE PRIOR TO INSTALLATION OF THE CASE IN THE WALL IT MAY BE LOCATED ANYWHERE ON THE ROOM SIDE PORTION EXCEPT FOR SUB BASE INSTALLATIONS FOR THESE THE DRAIN SHOULD BE AT LEAST 3 FROM THE INDOOR EDGE OF THE CASE SO AS TO ADEQUATELY CLEAR THE SUB BASE 3 A TEMPLATE IS FURNISHED WITH THE KIT FOR LOCATING THE NECESSARY 3 HOLES IN THE CASE BOTTOM TWO TO PROVIDE A SECURING MEANS AND ...

Страница 37: ...ns providing the sum of the two duct lengths necessary do not exceed the 44 length Even in single applications the mounting flange must be cut off one end of the duct to accept the collar and supply register Mounting Collar and Supply Register RAK602 These components are included in the Duct Extension Kit RAK601 They may be ordered separately for installations where two duct extensions are made fr...

Страница 38: ...ille mounting collar and discharge grille Duct extension must be cut to required length Two ducted installations may be made from one kit if the combined ducted length is less than 44 RAK602 kit contains mounting collar discharge grille and mounting hardware necessary for second installation 5 Filler strip field supplied actual width depends upon wall case projection into room A flush installation...

Страница 39: ...ATIONS CAULK RAG60 1 4 RAG61 66 1 3 8 Caulk around perimeter of wall case all four sides where it joins the building Interior and Exterior 1 4 MIN 2 29 32 2 3 8 min when installed with RAK204 RAG60 1 4 RAG61 66 1 3 8 3 11 16 RAK 204 3 MIN 5 MAX FINISHED FLOOR 16 1 8 TRANSITION ROOM CABINET WALL CASE Caulk around perimeter of wall case all four sides where it joins the building Interior and Exterio...

Страница 40: ...ies GE Zoneline units The RAK40 contains air deflectors and gaskets that mount to the chassis to direct the hot exhaust air away from the air intake to allow the unit to function properly All grilles used with GE Zoneline units must comply with requirements of Exterior Architectural Treatments and Special Outdoor Grilles as follows Exterior Architectural Treatments and Special Outdoor Grilles The ...

Страница 41: ...ors and an in line connector is included with the RAK4002A The factory installed line cord must be cut off approximately 8 from where it comes through the barrier or bulkhead of the unit Strip insulation off 3 4 of each conductor to expose wire for field connection These wires are then connected to the building wiring by field supplied connectors 265 or 277 Volt Unit Installation Permanent Connect...

Страница 42: ... current requirements when it is plugged into the Zoneline chassis Permanent Connection is accomplished by ordering the correct ampacity electrical sub base to match the Power Cord Kit being used See page 23 Sub Base for description There may be special requirements by some sites that rigid or flexible conduit be used Such as the wall case must be installed flush to finished floor and there is no ...

Страница 43: ... including installation of receptacle must conform to local electrical regulations and codes Replacement of Existing Chassis 230 208 Volt and 265 Volt Units There have been changes to NEC and improvements and modifications to the Zoneline chassis and sub bases since the unit was first introduced Some of these changes require alterations to be made when replacing an older unit with a new chassis Li...

Страница 44: ...25E12E4 3770 14 3 AZ25E12E5 5070 19 2 AZ25E15E3 2630 9 9 AZ25E15E4 3780 14 3 AZ25E15E5 5080 19 2 AZ35H07E3 2600 9 8 AZ35H07E4 3750 14 3 AZ35H09E3 2610 9 9 AZ35H09E4 3760 14 3 AZ35H09E5 5060 19 2 AZ35H12E3 2620 9 9 AZ35H12E4 3770 14 3 AZ35H12E5 5070 19 2 AZ35H15E3 2630 9 9 AZ35H15E4 3780 14 3 AZ35H15E5 5080 19 2 Maximum Connected Load For Premium Series 5500 230 208 V Model With RAK3152 With RAK320...

Страница 45: ...12D AZ35H15D Outdoor AZ35H07E AZ35H09E AZ35H12E AZ35H15E Temperature F BTUH COP BTUH COP BTUH COP BTUH COP 65 7200 3 75 10000 3 75 13050 3 55 15950 3 35 60 7000 3 70 9600 3 70 12550 3 50 15300 3 30 55 6800 3 65 9100 3 65 11950 3 45 14650 3 25 50 6600 3 55 8700 3 55 11350 3 35 13850 3 15 47 6400 3 50 8400 3 50 10900 3 30 13400 3 10 45 6250 3 45 8200 3 45 10600 3 25 13050 3 05 40 5950 3 35 7700 3 30...

Страница 46: ...eing considered and refer to the appropriate chart Next locate the indoor dry bulb temperature under consideration across the horizontal axis of the chart and draw a line straight up until it touches the line representing the indoor wet bulb temperature of the area from this point draw a horizontal straight line to the vertical axis The point where the line touches the axis represents the latent p...

Страница 47: ...Boston 5 634 500 MICHIGAN Detroit 6 293 590 Flint 7 377 440 Grand Rapids 6 894 530 MINNESOTA Duluth 10 000 200 Minneapolis 8 382 550 MISSISSIPPI Jackson 2 239 1 560 MISSOURI Columbia 5 046 960 Kansas City 4 711 1 210 Springfield 4 900 970 St Louis 4 900 1 080 MONTANA Billings 7 049 520 Glasgow 8 996 410 Great Falls 7 750 420 Missoula 8 125 350 NEBRASKA Grand Island 6 530 770 Omaha 6 612 750 NEVADA...

Страница 48: ...GE RD RED WH WHITE YL YELLOW WH O L P COMP MOTOR RUNNING CAPACITOR C S R HEATER PROTECTOR HEATER UNIT FUSE RY102 RY101 RY103 OUTDOOR FAN MOTOR INDOOR FAN MOTOR FAN MOTOR CAPACITOR FAN MOTOR CAPACITOR CN102 CN101 RY106 RY107 RY104 RY105 CN8 CN103 Varistor NR101 Capacitor C101 C102 FUSE FU101 DRIVE BOARD UNIT REGULATOR TR1 TRANSFORMER CN3 MAIN BOARD UNIT DECODER SELECT SW HEAT H HEAT A OFF FAN L FAN...

Страница 49: ... CN106 RD RD OPTIONAL ICR BR RD 1 RED 208 230V BLUE 265V O L P COMP MOTOR RUNNING CAPACITOR C S R HEATER PROTECTOR HEATER UNIT FUSE RY102 RY101 RY103 OUTDOOR FAN MOTOR INDOOR FAN MOTOR FAN MOTOR CAPACITOR FAN MOTOR CAPACITOR CN102 CN101 RY106 RY107 RY104 RY105 CN8 CN103 Varistor NR101 Capacitor C101 C102 FUSE FU101 DRIVE BOARD UNIT REGULATOR TR1 TRANSFORMER CN3 MAIN BOARD UNIT DECODER SELECT SW HE...

Страница 50: ...65V 208 230V COLOR BK BLACK BL BLUE BR BROWN GR GREEN GY GRAY OR ORANGE RD RED WH WHITE YL YELLOW RD 1 RED 208 230V BLUE 265V WH O L P COMP MOTOR RUNNING CAPACITOR C S R HEATER PROTECTOR RY102 RY109 RY103 OUTDOOR FAN MOTOR INDOOR FAN MOTOR FAN MOTOR CAPACITOR FAN MOTOR CAPACITOR CN102 CN101 RY106 RY107 RY104 RY105 CN8 CN103 Varistor NR101 Capacitor C101 C102 FUSE FU101 DRIVE BOARD UNIT REGULATOR T...

Страница 51: ...tion independently selectable for heating and cooling operation A positive cooling condensate disposal system which meets the test requirements of applicable A R I Standard 310 93 for Packaged Terminal Air Conditioners and 380 93 for Packaged Terminal Heat Pump 80 F dry bulb 75 F wet bulb 80 relative humidity Condenser and evaporator coils to be constructed of copper tubing and aluminum plate fins...

Страница 52: ...tdoor temperature is below 45 F Selection of A or B operation is made by means of a selector switch concealed from room occupant In either A or B operation the unit will switch to full resistance heat if room temperature continues to decline or the outdoor temperature falls below 25 F If the outdoor temperature is above 46 F unit will lock out electric resistance heat and operate on heat pump only...

Страница 53: ...sub base shall have side panels adjustable from a minimum of 2 3 8 to a maximum of 13 3 4 to enclose the area under the wall case Weather Resistance Complete unit including outside louver shall be submitted to an independent agency for weather resistance and water infiltration tests Air infiltration test to be conducted in accordance with ASTM E283 91 With static air pressure differential of 1 57 ...

Страница 54: ...000 Heater Table 2500 Series Units Dry Air 25 230 208V Models AZ25E07D AZ25E09D AZ25E12D AZ25E15D AZ25E07D P AZ25E09D P AZ25E12D P Capacity Cooling BTUH 7 100 6 900 9 000 8 800 11 700 11 500 14 600 14 300 6 800 6 600 8 600 8 400 11 200 11 000 EER BTU Watt 11 8 11 8 11 5 11 5 10 9 10 9 9 6 9 6 11 1 11 1 10 8 10 8 10 2 10 2 Dehumidification Pts Hr 1 7 2 7 3 6 4 5 2 2 3 4 4 5 Sensible Heat Ratio 230 ...

Страница 55: ...AZ55H09D AZ55H12D AZ55H15D Capacity Cooling BTUH 7 100 6 900 9 000 8 800 11 700 11 500 14 600 14 300 7 100 6 800 9 000 8 800 11 800 11 600 14 700 14 400 EER BTU Watt 11 8 11 8 11 5 11 5 10 9 10 9 9 6 9 6 12 0 12 0 11 5 11 5 10 9 10 9 10 0 10 0 Dehumidification Pts Hr 1 7 2 7 3 6 4 5 1 7 2 8 3 6 4 8 Sensible Heat Ratio 230 Volts 75 68 67 67 75 67 68 65 CFM Indoor Fan High 250 260 280 310 240 290 33...

Страница 56: ... 23 RAK204D30 Sub base 208 230 Volt with NEMA 6 30R 30 Amp Receptacle Chaseway Included 23 RAK204E15 Sub base 265 Volt with NEMA 7 15R 15 Amp Receptacle Chaseway Included 23 RAK204E20 Sub base 265 Volt with NEMA 7 20R 20 Amp Receptacle Chaseway Included 23 RAK204E30 Sub base 265 Volt with NEMA 7 30R 30 Amp Receptacle Chaseway Included 23 RAK204U Sub base non electrical Chaseway not Included 23 RAK...

Страница 57: ...run through the sub base entering the rear and exiting through one of the front panels When the room cabinet is in place the CDC or remote thermostat wiring is usually not visible to someone standing or sitting in the room Do not run the low voltage wiring in conduits with line voltage wiring or near uninsulated line voltage wiring since induced current can interrupt the low voltage controls Consu...

Страница 58: ...n off the existing installation and used on the RAK7012 duct adapter The wall case mounting brackets screws discharge grille damper and end cap will need to be retained If the chassis is a slope front discharge and the duct dimensions are 8 3 8 high by 6 1 2 wide then the chassis has already been replaced and the purchase of a new duct adapter is not required The only piece that needs to be replac...

Страница 59: ...enefits 9 11 Features Table 8 General Suggestions 57 58 Heat Pumps Energy Savings 19 20 Introduction to Installation 21 Introduction to Zoneline 6 Latent System Capacity 46 Maximum Connected Load 44 Mini Specs 2500 2 Mini Specs 3500 2 Mini Specs 5500 3 Multiple Unit Remote Control 18 Nomenclature 3 Normal Yearly Operating Data 47 Remote Thermostat Control 15 17 Schematics 48 50 Specifications 54 5...

Страница 60: ...cian Failure of the product resulting from modifications to the product or due to unreasonable use including failure to provide reasonable and necessary maintenance Failure or damage resulting from corrosion due to installation in an environment containing corrosive chemicals Failure or damage resulting from corrosion due to installation in a coastal environment except for models treated with spec...

Отзывы: