31
AL
TERNA
TE – CASE RECESSION LESS THAN 3" WITH SIDES AND TOP
OF W
ALL OPENING W
A
TERPROOF
, FLASHING ON BOTTOM ONL
Y
CAULK*
A
DIMENSIONS:
A. DIST
ANCE FROM GRILLE OR CASE TO OUTSIDE SURF
ACE OF W
ALL PLUS 2” TO 4”
(TO INSER
T UNDER CASE).
B. 1” DRIP LIP (MINIMUM)
C. 42” PLUS - SUFFICIENT TO FIT SNUGGL
Y UNDER AND UP AROUND THE CASE.
D. 2” MINIMUM
(CAUTION: WHEN CAULKING
DO NOT BLOCK DRAIN HOLES IN CASE OR GRILLE.
)
IF GRILLE IS TO BE MOUNTED TO W
ALL SURF
ACE A SPLITTERS MUST BE USED, SEE P
A
GE 30.
B
D
C
A
B
*Caulk around perimeter of wall case all four sides
where it joins the building - Interior and Exterior
.
DRIP
FLASHING
OUTDOOR
GRILLE
CASE
For an installation
that will provide
better protection
against water
infiltration, GE
recommends the use
of one of the deeper
RAB71 wall cases
offered as special
order items. See
page 23.
1719 Data Manual 2001 2/14/02 3:12 PM Page 31