VersaMax* Analog Input, 16-Bit Thermocouple Module 

IC200ALG630 

October 2016 

 

GFK-1700L 

 

Wiring Connections for Carriers with Three Rows of Terminals: 

 

1

2

3

4

5

6

7

8

9

11

12

10

A

13

14

15

16

17

18

AI 1

AI 2

AI 3

AI 5

AI 6

AI 7

Thermistor

AI 4

Note: only for thermocouple carrier

 

Cable Shield Connections  

Shielded twisted pair cable is recommended for the analog channel 
connections. If possible, the cable should be grounded at the source 
device. If that is not possible, the cable shield must be grounded at the 
I/O module. This can be done using an Auxiliary I/O Terminal strip.  

If the module is installed on a Terminal-style I/O Carrier, shield 
connections can be made on an Auxiliary I/O Terminal that is attached 
to the I/O carrier. 

If the module is installed on a Compact Terminal-style I/O Carrier, shield 
connections can be made on an Auxiliary I/O Terminal that is mounted 
near the I/O carrier. 

If the module is installed on a Connector-style I/O Carrier, the cable 
shield can be connected directly to an Interposing Terminal.  A shielded 
interposing cable (shielded cables are available separately) must be 
used between the Connector-style I/O Carrier and the Interposing 
Terminal. An Auxiliary I/O Terminal Strip can also be added to the 
Interposing Terminal if additional shield connections are required. 

Product Version Information 

Revision letters:  

KF 

Firmware version:  

1.25 

Firmware 
upgrades: 

44A750342-G05. Available as a free 
download at 

http://ge-ip.com/support

Compatibility  

Firmware version 1.25 is compatible with all hardware versions of the 
ALG630.  

This module is compatible with: 

 

PLC CPU Firmware version 1.20 or later. 

 

Ethernet NIU EBI001 all versions. 

 

Genius NIU GBI001 Firmware version 1.10 or later* 

 

Profibus NIU PBI001 Firmware version 1.10 or later* 

 

DeviceNet NIU DBI001 Firmware version 1.10 or later. The 
DeviceNet NIU does not support software configuration. Therefore, 
analog modules used with a DeviceNet NIU must be 
autoconfigured and use only their default configuration settings. 

*

 

For GBI001, NIU version 2.0 or above is required to perform software 
configuration. For PBI001, NIU version 2.01 or above is required to 
perform software configuration.

 

 

 

 

Product Revision History 

Revision 

Date 

Description 

IC200ALG630-KF 

Oct 2016 

EU RoHS compliant module per 
directive 2011/65/EU dated 8-June-
2011. No changes to features, 
performance or compatibility. 

IC200ALG630-JF 

Jan 2012 

Label change. No changes to 
features, performance or 
compatibility. 

IC200ALG630-HF 

Apr 2011 

Firmware release 1.25. Resolves 
component obsolescence issue. No 
change to features, performance or 
compatibility. 

IC200ALG630-HE 

Feb 2011 

Labeling change. No changes to 
compatibility, functionality or 
performance. 

IC200ALG630-GE 
IC200ALG630-FE 

Sept 2010 

Firmware release 1.24. Resolved 
fault reporting issue in Remote/Local 
IO configuration. 

IC200ALG630-GD 

Aug 2009 

Changed manufacturing location. No 
changes to compatibility, functionality 
or performance. 

IC200ALG630-FD 
BXIOAI7-FD 

Oct 2008 

Updated Power Supply OK signal 
circuitry. 

IC200ALG630-ED 
BXIOAI7-ED 

Sept 2007 

Firmware release 1.20. Improved I/O 
scanning. 

IC200ALG630-EC 
BXIOAI7-EC 

Apr 2005 

Plastic change on locking 
mechanism 

IC200ALG630-DC 
BXIOAI7-DC 

Feb 2005  Configurable for 50Hz line frequency 

IC200ALG630-DB 
BXIOAI7-DB 

Apr 2004 

Changed to V0 plastic for module 
housing. 

IC200ALG630-CB 
BXIOAI7-CB 

Jan 2004 

ATEX approval for Group 2 Category 
3 applications. 

IC200ALG630-BB 
BXIOAI7-BB 

Nov 2002 

Improved reporting of Open Input 
error at higher temperatures. 

IC200ALG630-AB 
BXIOAI7-AB 

June 2001 

Firmware version 1.01.  Enhanced 
Open Circuit reporting 

IC200ALG630-AA 
BXIOAI7-AA 

July 1999  Initial product release 

 

Restrictions and Open Issues 

 

Additional faults may be logged when a new configuration 
containing parameter changes such as the Alarm High limit or 
Alarm Low limit in the hardware configuration of an analog module 
is stored followed by a Clear All operation. The additional faults are 
logged against the previous configuration. This issue is observed 
when Machine Edition is connected to Versamax CPUs 
(IC200CPU001, IC200CPU002, IC200CPU005 and IC200CPUE05) 
and does not occur with Versamax NIUs (IC200GBI001, 
IC200EBI001, IC200PBI001, and IC200DBI001). 

 

When more than 20 faults are sent to a GBC70 within a single 
Genius scan, under rare conditions one fault or fault contact may 
not be reported by the GBC70. This has been observed when 
simultaneous open wire condition occurs in all eight channels of 
IC200ALG240 module or if several I/O modules in a GNIU rack 
generate multiple faults simultaneously. This issue has only been 
observed when the GBC70 was in a rack with an RX7i CPU. 

Содержание VersaMax IC200ALG630

Страница 1: ...ule If this LED is amber it indicates a module fault Module Characteristics Channels Seven thermocouple or millivolt inputs Module ID FFFF9804 Isolation User input to logic optical and to frame ground Group to group Channel to channel 250VAC continuous 1500VAC for 1 minute Not applicable None LED indicators OK LED Green indicates backplane power is present Amber indicates module fault Backplane cu...

Страница 2: ...t be used as millivolt input terminals Thermocouple or Millivolt Inputs Thermocouple or Millivolt Inputs Install Optional Thermistors Here Thermocouple Inputs Thermocouple Inputs Built In Thermistors Located Here CHS014 Installation in Hazardous Locations EQUIPMENT LABELED WITH REFERENCE TO CLASS I GROUPS A B C D DIV 2 HAZARDOUS LOCATIONS IS SUITABLE FOR USE IN CLASS I DIVISION 2 GROUPS A B C D OR...

Страница 3: ...scription IC200ALG630 KF Oct 2016 EU RoHS compliant module per directive 2011 65 EU dated 8 June 2011 No changes to features performance or compatibility IC200ALG630 JF Jan 2012 Label change No changes to features performance or compatibility IC200ALG630 HF Apr 2011 Firmware release 1 25 Resolves component obsolescence issue No change to features performance or compatibility IC200ALG630 HE Feb 201...

Страница 4: ...t that points to the IC200ALG630 itself To avoid this fault either configure at least one thermocouple channel to active or set reference junction type parameter to local Configuration The default parameters of the Thermocouple Input module can be used in many applications The module can be software configured when it is installed in a PLC system or an I O Station controlled by an NIU that support...

Страница 5: ...erposing Carrier allows the thermocouple connections to be placed farther away from the I O modules in the system which helps shield thermocouple connections from module heat If Local Cold Junction Compensation is configured and an Interposing Thermocouple Carrier is not used a separate thermistor must be installed directly at the module s I O Carrier using the Thermistor and Thermistor terminals ...

Отзывы: