background image

VersaMax* Analog Input, 16-Bit Thermocouple Module 

IC200ALG630 

October 2016 

 

GFK-1700L 

 

 

When 45 or more faults are sent to a GBC70 within a single Genius 
scan, a few faults or fault contacts may not be reported by the 
GBC70. This is most likely to be caused by the sudden loss of 
numerous blocks at each bus controller in the system. The 
resulting PLC diagnostics and diagnostic contacts may be 
incorrect. 

Operational Notes  

 

If hot insertion of a module is done improperly, the operation of 
other modules on the same backplane may be disrupted. See

 

Installing a Module on a Carrier 

in the

 VersaMax Modules Manual, 

GFK-1504. 

 

Clarification of Default/Hold Last State configurations: 
If there is an error on a specific input channel, the modules will 
always report the Channel Default value from the Input Parameters 
tab of the module configuration. 

When a Loss of I/O Module fault is logged for a module, the CPU 
or NIU will use the Default/Hold Last State setting from the Module 
Parameters tab of the module configuration to determine what 
value should be reported to the reference tables. 

 

After an Open Circuit fault 

condition

 is corrected, the module takes 

a few seconds to return to normal operation.  During this time, the 
module continues reporting the channel default input value. After 
the module has recovered from the Open Circuit fault, it returns to 
normal inputs and normal operation. 

 

If there is a very large change in an input (for example, an input 
quickly goes from 50mV to 400mV), the module may briefly report 
an Over-range fault on that circuit even though the circuit is not 
actually over its configured upper range limit. This is only 
temporary. 

 

When IC200ALG630 or IC200ALG620 modules are present in 
GNIU or PNIU rack and a 'Clear all' command is issued from 
Machine Edition software, Machine Edition may get disconnected, 
displaying timeout error "error 8097 - host disconnect has 
occurred". When this error is logged, the Configuration is still 
cleared. To avoid this error, the 

“Request Timeout” value in 

“Additional Configuration” in “Target Properties” should be 
increased to 30s or more. 

 

When all the channels of IC200ALG630 are set inactive 

and

 the 

Reference Junction Type parameter is not set to "local", VersaMax 
CPUs / NIUs will report a 

“Loss of IO modules” fault, that points to 

the IC200ALG630 itself.  

To avoid this fault, either configure at least one thermocouple 
channel to active or set reference junction type parameter to 
“local”.  

 

Configuration  

The default parameters of the Thermocouple Input module can be used 
in many applications.  The module can be software-configured when it is 
installed in a PLC system, or an I/O Station controlled by an NIU that 
supports software configuration. 

Parameter 

Default 

Choices 

Analog Input Data Length 

1 to 7 

Analog Input Data 

Reference 

 

user selectable 

Analog Output Data 

Length 

0 to 7 

Analog Output Data 

Reference 

 

user selectable 

Line Frequency 

60 Hz 

50 Hz, 60 Hz 

Suppress Open 

Thermocouple  

No 

Yes, No 

Channel Active 

Active 

Inactive (off), Active (on) 

Engineering Units 

1/10 

degrees C 

Millivolts, 1/10 degrees C, 1/10 degrees F 

Thermocouple Type 

None, J, K, T, S, R 

Range 

625 

19.53, 39.06, 78.125, 156.25, 312.5, 625. 

R J Type 

Local 

Local, Remote, Fixed, None 

Alarm Low 

–2000 

–32,768 to +32,767 

Alarm High 

8000 

–32,768 to +32,767 

Reference Junction Value 

250 

–32,768 to +32,767 

Correction Factor 

–32,768 to +32,767 

Channel Default Input 

+32,767 

Cold Junction Default 

250 

+32,767 

Configurable Features  

Channel Active

: Each channel can be configured as either active or 

inactive. If a channel is inactive, the filtering, scaling, calibration, and 
alarm checks are omitted for that channel, and a value of 0 is returned 
for the channel.  The reference parameter for the analog input data 
returns the byte length and is independent of the number of active 
channels.  

Low Alarm Limit and High Alarm Limit:  

Each input channel can have 

a low alarm limit and a high alarm limit.  If an input reaches one of its 
limits, the module reports the actual value and sends the appropriate 
diagnostic input bit.  Alarms do not stop the process or change the value 
of the input.  Alarm limits can be set anywhere over the dynamic range 
of the signal. The range for each is 

–32,768 to +32,767. The high alarm 

limit must be greater than the low alarm limit. If alarm reporting is not 
wanted, alarm limits can be set beyond the dynamic range of the signal 
so they will never be activated.  

Thermocouple Limits

:  The table below lists millivolt and temperature 

limits for applicable thermocouple types. 

TC  Type 

Low mV 

Limit 

High mV 

Limit 

Low 

Temperature 

Limit (C) 

High 

Temperature 

Limit (C) 

–8.0960 

57.9420 

–210.00 

1000.00 

–5.8910 

54.8069 

–200.00 

1370.00 

–5.6030 

20.2520 

–200.00 

390.00 

–0.1940 

18.5040 

–40.00 

1750.00 

–0.1880 

20.8780 

–40.00 

1750.00 

Содержание VersaMax IC200ALG630

Страница 1: ...ule If this LED is amber it indicates a module fault Module Characteristics Channels Seven thermocouple or millivolt inputs Module ID FFFF9804 Isolation User input to logic optical and to frame ground Group to group Channel to channel 250VAC continuous 1500VAC for 1 minute Not applicable None LED indicators OK LED Green indicates backplane power is present Amber indicates module fault Backplane cu...

Страница 2: ...t be used as millivolt input terminals Thermocouple or Millivolt Inputs Thermocouple or Millivolt Inputs Install Optional Thermistors Here Thermocouple Inputs Thermocouple Inputs Built In Thermistors Located Here CHS014 Installation in Hazardous Locations EQUIPMENT LABELED WITH REFERENCE TO CLASS I GROUPS A B C D DIV 2 HAZARDOUS LOCATIONS IS SUITABLE FOR USE IN CLASS I DIVISION 2 GROUPS A B C D OR...

Страница 3: ...scription IC200ALG630 KF Oct 2016 EU RoHS compliant module per directive 2011 65 EU dated 8 June 2011 No changes to features performance or compatibility IC200ALG630 JF Jan 2012 Label change No changes to features performance or compatibility IC200ALG630 HF Apr 2011 Firmware release 1 25 Resolves component obsolescence issue No change to features performance or compatibility IC200ALG630 HE Feb 201...

Страница 4: ...t that points to the IC200ALG630 itself To avoid this fault either configure at least one thermocouple channel to active or set reference junction type parameter to local Configuration The default parameters of the Thermocouple Input module can be used in many applications The module can be software configured when it is installed in a PLC system or an I O Station controlled by an NIU that support...

Страница 5: ...erposing Carrier allows the thermocouple connections to be placed farther away from the I O modules in the system which helps shield thermocouple connections from module heat If Local Cold Junction Compensation is configured and an Interposing Thermocouple Carrier is not used a separate thermistor must be installed directly at the module s I O Carrier using the Thermistor and Thermistor terminals ...

Отзывы: