- 12 -
AM DIP switches (fig.
)
Table 2: AM DIP switches
Function
DIP switch On
DIP switch Off
4. How to signal
AM or TF output
Relay
Relay
AM
Alarm
AM
Alarm
AM
-
TF
-
-
3. Reset AM or TF
After walk test
Authorised reset
2. AM sensitivity
High
Standard
1. When to signal
Day mode only
Day/Night mode
AM or TF output
AM DIP switch settings:
1.
When to signal AM (anti-masking) or TF (technical fault)
output
On
: Signals AM or TF only when the system is in Day mode. EN 50131-2-2
compliant.
Off
: Always signal AM or TF.
CAUTION!
To prevent AM alarms during Night mode, the
following DIP switch settings are recommended:
4: Off
3: Off
2: Off
1: On
AM alarms are now only signaled to the control panel during
Day mode by the AM relay. The LEDs are controlled by Day/
Night and Walk Test inputs. Resetting the AM alarm can only
be done in walk test mode.
Never show the detector state to the intruder via the LEDs.
2. AM sensitivity
On:
Selects a higher level of AM sensitivity. AM relay reacts within 6
seconds.
Off:
Selects the standard AM sensitivity. AM relay reacts within 12
seconds.
(ex-factory)
1 2 3
4 5
12
3
4
ON
12
3
4
ON