![GE V7768 Скачать руководство пользователя страница 50](http://html.mh-extra.com/html/ge/v7768/v7768_hardware-reference-manual_129567050.webp)
50 V7768/V7769 Hardware Reference Manual
When either field is read, the current count value is latched and returned. There
are two modes that determine how the count is latched depending on the setting
of the “Read Latch Select” bit in the Control Status Register (TCSR2). See the
TCSR2 register description for more information on these two modes.
3.3.7 Timer 3 Current Count Register (TMRCCR3)
The current count of Timer 3 may be read via the Timer 3 Current Count Register
(TMRCCR3), located at offset 0x24 from the address in BAR2. The mapping of bits
in this register is shown in Table 3-9.
When this field is read, the current count value is latched and returned. There are
two modes that determine how the count is latched depending on the setting of
the “Read Latch Select” bit in the Control Status Register (TCSR2). See the TCSR2
register description for more information on these two modes.
3.3.8 Timer 4 Current Count Register (TMRCCR4)
The current count of Timer 4 may be read via the Timer 4 Current Count Register
(TMRCCR4), located at offset 0x28 from the address in BAR2. The mapping of bits
in this register is shown in Table 3-10.
When this field is read, the current count value is latched and returned. There are
two modes that determine how the count is latched depending on the setting of
the “Read Latch Select” bit in the Control Status Register (TCSR2). See the TCSR2
register description for more information on these two modes.
3.3.9 Timer 1 IRQ Clear (T1IC)
The Timer 1 IRQ Clear (T1IC) register is used to clear an interrupt caused by
Timer 1. Writing to this register, located at offset 0x30 from the address in BAR2,
causes the interrupt from Timer 1 to be cleared. This can also be done by writing a
“0” to the appropriate “Timer x Caused IRQ” field of the timer Control Status
Register (TCSR1). This register is write only and the data written is irrelevant.
3.3.10 Timer 2 IRQ Clear (T2IC)
The Timer 2 IRQ Clear (T2IC) register is used to clear an interrupt caused by
Timer 2. Writing to this register, located at offset 0x34 from the address in BAR2,
causes the interrupt from Timer 2 to be cleared. This can also be done by writing a
Table 3-8 TMRCCR12 Bit Mapping
Field
Bits
Read or Write
Timer 2 Count
TMRCCR12[31..16]
Read Only
Timer 1 Count
TMRCCR12[15..0]
Read Only
Table 3-9 TMRCCR3 Bit Mapping
Field
Bits
Read or Write
Timer 3 Count
TMRCCR3[31..0]
Read Only
Table 3-10 TMRCCR4 Bit Mapping
Field
Bits
Read or Write
Timer 4 Count
TMRCCR4[31..0]
Read Only
Содержание V7768
Страница 13: ...Overview 13 Figure 2 Illustration of V7768 ...
Страница 15: ...Overview 15 Figure 4 Illustration of V7769 ...
Страница 28: ...28 V7768 V7769 Hardware Reference Manual Figure 1 4 Installing the PMC Card on the V7768 V7769 ...
Страница 29: ...Installation and Setup 29 Figure 1 5 Backside Mounting for the PMC Card Back ofV7768 SBC Solder Side ...