Telaire Ventostat™ 8000 Series

CO

2

 Sensor

User Instructions

GE

Measurement & Control

T63216-006

January 2012

Page 1 of 4

Installing the Sensor

!WARNING!

Before performing service or maintenance operations on 

the systems, turn OFF main power switches to the unit. 

Electric shock can cause personal injury. Please read and 

follow the wiring instructions precisely; miswiring may 

cause permanent damage to the product

.

Basic Installation for Non-Display Units

1.

Separate the case into its front and rear sections.

2.

Secure the rear section of the case to the wall or junction box using 
the supplied screws, and make necessary wire connections.

3.

Mount the Controller on the base by aligning the top clips and then 
securing to the bottom clips. Secure the Ventostat with the supplied 
set screw. A one-minute stabilization warmup will take place.

 Internal Label for Non-Display Units

 Jumper Settings for Non-Display (a) and Display (b) 

Units 

Note:

Example b shows outputs of CO

2

 — 4-20 mA and CO

2

 — 0-10 

V, humidity— 4-20 mA, and active temperature — 0-5 V.

GE Measurement & Control 
6860 Cortona Dr., Suite B
Goleta, CA 93117
www.ge-mcs.com

Basic Installation for Display Units

1.

Separate the case into its front and rear sections.

2.

Secure the rear section of the case to the wall or junction box using 
the supplied screws, and make necessary wire connections.

3.

Mount the Controller on the base by aligning the top clips and then 
securing to the bottom clips. Secure the Ventostat with the supplied 
set screw. A one-minute stabilization warmup will take place.

4.

When fitting the T8300 (pitot tube version), complete the 
installation by screwing the tube connectors to the input ports on the 
sensor. The tubing connectors can be attached to either input port. It 
will not affect the performance of the sensor. (See page 3 for further 
instructions.)

 Internal Label for Display Units

Output

Jumper

Selections

(a)

(b)

0-10V  0-5 V

Output

Jumper

Selections

Содержание Telaire Ventostat 8000 Series

Страница 1: ...on Display Units Jumper Settings for Non Display a and Display b Units Note Example b shows outputs of CO2 4 20 mA and CO2 0 10 V humidity 4 20 mA and active temperature 0 5 V GE Measurement Control 6860 Cortona Dr Suite B Goleta CA 93117 www ge mcs com Basic Installation for Display Units 1 Separate the case into its front and rear sections 2 Secure the rear section of the case to the wall or jun...

Страница 2: ...r line to terminal number 2 of the terminal block Caution The T8100 Ventostats are either 3 wire or 4 wire type configurations powered by either AC or DC voltage They are not 2 wire or loop powered devices Wiring the units as 2 wire or loop powered devices will irreparably damage the sensors and void the warranty Note For temperature measurements Ventostat models contain a passive thermistor termi...

Страница 3: ...ithout stretching or pulling If the length is long enough to create a loop or bind in the tubing it should be shortened 8 To shorten the tubing remove the connectors that attach to the sensor and cut the tubing to length 9 Replace the tubing connectors by using a twisting or screwing motion Verify the connection is secure Note If the tubing length has been shortened be sure the in line filter is r...

Страница 4: ...pied for 4 hours or more for this self calibration system to operate properly Under these conditions ABC Logic should maintain sensor calibration over the lifetime of the sensor The ABC Logic should be turned OFF where a building is continuously occupied 24 hours per day or where there could be significant sources of non occupant related CO2 such as greenhouses breweries and other industrial and f...

Отзывы: