5-
4
SPM Synchronous Motor Protection & Control
GE Power Management
5.2 SETPOINTS MENU
5 SETPOINTS
5
5.2.7 AC CT PRIMARY RATING
FUNCTION:
The phase CT ratio supplied with the starter must be entered here. Enter only primary amperes. A 5 A second-
ary is assumed.
MOTOR TYPE:
Collector-Ring and Brushless
NOTE:
The value entered here affects the valid range of the motor full load current (
FL AMPS
) setpoint.
5.2.8 MOTOR FULL LOAD AMPS
FUNCTION:
This setpoint is the motor-nameplate, full load current. It is related to the
AC CT RTG
setpoint. The minimum and
maximum current is determined by the formula below. Changes to the
AC CT RTG
setpoint may cause this set-
point to become invalid (out of range).
minimum
FL AMPS
, maximum
FL AMPS
=
AC CT RTG
MOTOR TYPE:
Collector-Ring and Brushless
NOTE:
The value entered here affects the valid range of the motor locked rotor current (
LR AMPS
) setpoint.
5.2.9 MOTOR LOCKED ROTOR AMPS
FUNCTION:
This setpoint represents the motor locked rotor current and is related to the
FL AMPS
setpoint. The minimum
and maximum current is determined by the formula below. Changes to the
AC CT RTG
and/or the
FL AMPS
set-
points may cause this setpoint to become invalid (out of range).
minimum
LR AMPS
= 2
×
FL AMPS
, maximum
LR AMPS
= 12
×
FL AMPS
MOTOR TYPE:
Collector-Ring and Brushless
AC CT RTG:
50/5
ENTER to modify
Range: 5 to 2000 seconds
Step: 5
FL AMPS:
25
ENTER to modify
Range: 2 to 2000 A
Step 1
Dependent on the
AC CT RTG
setpoint
LR AMPS:
200
ENTER to modify
Range: 4 to 24000 A
Step: 1
Dependent on the
FL AMPS
setpoint
2
AC CT RTG
5
-------------------------
×
=
Содержание SPM
Страница 2: ......
Страница 4: ......
Страница 10: ...vi SPM Synchronous Motor Protection Control GE Power Management TABLE OF CONTENTS ...
Страница 74: ...6 4 SPM Synchronous Motor Protection Control GE Power Management 6 2 STATUS 6 ACTUAL VALUES 6 ...
Страница 96: ...8 6 SPM Synchronous Motor Protection Control GE Power Management 8 3 DC CURRENT TRANSFORMER 8 ACCESSORIES 8 ...
Страница 120: ...C 2 SPM Synchronous Motor Protection Control GE Power Management C 1 WARRANTY APPENDIXC C ...
Страница 124: ...iv SPM Synchronous Motor Protection Control GE Power Management INDEX ...
Страница 125: ...GE Power Management SPM Synchronous Motor Protection Control NOTES ...