GE Power Management
SPM Synchronous Motor Protection & Control
A-
1
APPENDIX A
A.1 COMMISSIONING
A
APPENDIX A COMMISSIONINGA.1 COMMISSIONING
A.1.1 COLLECTOR-RING SETTINGS
DESCRIPTION
DEFAULT
USER VALUE
SETPOINTS
PF TRIP
–0.60
PF DELAY
1.0 s
PF SUPP
6% FLC
PF MODE
ridethru
FAR DELAY
0 s
FCX DELAY
1 s
AC CT RTG
50/5
FL AMPS
25
LR AMPS
200
SYNC SLIP
5.0%
STALL TIME
10 s
RUNTIME
1.05 x ST
DC CT PRIM
5 A
HIGH FIELD
OFF
FIELD AMPS
OFF
FLD IE DLY
N/A
FIELD VOLTS
OFF
EX VLT DELAY
N/A
INC SEQ DLY
OFF
REG PF
0.00
REG GAIN
1
STABILITY
1 cyc
REG OUTPUT
1 V
FLOOR VOLTS
0.0
CONFIGURATIONS
MOTOR
Coll-Ring
LINE FREQ
60 Hz
PF REF
internal
RTU ADDRESS
1
BAUD RATE
19.2k
PARITY
None
TURNAROUND
5
STAT
read only
PASSWORD
0000
CALIBRATION
FS EXC VOLT
FS EXC AMPS
FS MTR AMPS
DESCRIPTION
DEFAULT
USER VALUE
Содержание SPM
Страница 2: ......
Страница 4: ......
Страница 10: ...vi SPM Synchronous Motor Protection Control GE Power Management TABLE OF CONTENTS ...
Страница 74: ...6 4 SPM Synchronous Motor Protection Control GE Power Management 6 2 STATUS 6 ACTUAL VALUES 6 ...
Страница 96: ...8 6 SPM Synchronous Motor Protection Control GE Power Management 8 3 DC CURRENT TRANSFORMER 8 ACCESSORIES 8 ...
Страница 120: ...C 2 SPM Synchronous Motor Protection Control GE Power Management C 1 WARRANTY APPENDIXC C ...
Страница 124: ...iv SPM Synchronous Motor Protection Control GE Power Management INDEX ...
Страница 125: ...GE Power Management SPM Synchronous Motor Protection Control NOTES ...