3.5 VENTILATION AND COOLING
Fig. 3.5-1 Installation on plain floor
Fig. 3.5-2 Installation on raised floor
The heat produced by the UPS is transferred to the environment by its ventilation.
Air inlets for UPS ventilation are located on the front of the UPS, while air outlets are on top of the
cabinet.
UPS produces maximum heat dissipation while operating in Double Conversion Mode, design ventilation
or cooling system to meet heat dissipation for this operating mode. Install suitable ventilation or cooling
system to extract the heat from the UPS room.
NOTE !
Do not put anything on the top of the cabinet.
Air filtration systems could be required when the UPS operates in a dirty environment.
Contact your
Dealer
or the nearest
Service Center
for appropriate solutions.
In order to prevent overheating of the UPS, the available air intake flow rate must exceed the total air
exhaust flow rate requirement of the UPS system.
The below table indicates the heat dissipation at full load at
PF = 0.9
lag. and charged battery, up to
3,280 ft
(1,000 m) altitude, for cooling air
77°F
(25°C) to
86°F
(30°C).
Losses
Cooling air flow
UPS rating with options
BTU / hr
kW
CFM
m
3
/ h
SG Series 400 with 5
th
filter
78,499 23.0 3,949 6,709
SG Series 400 with 5
th
& 11
th
filter
79,864 23.4 4,018 6,825
SG Series 400 in eBoost™ Operation Mode
13,652 4.0 687 1,167
SG Series 500 with 5
th
filter
99,659 29.2 5,013 8,517
SG Series 500 with 5
th
& 11
th
filter
101,366 29.7 5,099 8,663
SG Series 500 in eBoost™ Operation Mode
17,065 5.0 859 1,459
Modifications reserved
Page 15/41
OPM_SGS_ISG_M40_M50_2US_V021.doc
User Manual
SG Series 400 & 500 UL S2