IC695PNC001-AJ PROFINET Controller Module

 

 

GFK-2573K

 

References 

For additional information, please refer to the manuals listed below. Manuals can be downloaded from the Support 

website, 

http://support.ge-ip.com.

 

GFK-2571, 

PACSystems RX3i PROFINET Controller Manual

 

GFK-2572, 

PACSystems RX3i PROFINET Controller Command Line Interface Manual

 

GFK-2721, 

VersaMax PROFINET Scanner User’s Manual

 

 

GFK-2314, 

PACSystems RX3i System Manual 

 

GFK-2222, 

PACSystems CPU Reference Manual

  

EMC Installation Requirements  

To meet EN 55011 and FCC Class A radiated emissions, the Control system in which the IC695PNC001 module is used 

shall be mounted in a metal enclosure when three or more IC695PNC001 modules are used. All surfaces of the 

enclosure must be adequately grounded to adjacent surfaces to provide electrical conductivity. Wiring external to the 

enclosure must be routed in metal conduit or the equivalent. The conduit must be mounted to the enclosure using 

standard procedures and hardware to ensure electrical conductivity between the enclosure and conduit. 
When installing, operating, or maintaining the IC695PNC001, personnel must insure any electrostatic charge is 

discharged through the use of a grounded ESD strap or other means. 

General Conditions of Safe Use 

This product is intended for use with the RX3i system. Its components are considered open equipment (having live 

electrical parts that may be accessible to users) and must be installed in an ultimate enclosure that is manufactured to 

provide safety. As a minimum, the enclosure shall provide a degree of protection against solid objects as small as 

12mm (e.g. fingers). This equates to a NEMA/UL Type 1 enclosure or an IEC60529 IP20 rating providing at least a 

pollution degree 2 environment. For details about installing RX3i rack systems, refer to GFK-2314.  

If you need technical help, contact Technical Support. For phone numbers and email addresses, see the back cover of 

this Guide.  

 

Installation in Hazardous Areas  

The following information is for products bearing the UL marking for Hazardous Areas or ATEX marking for explosive 

atmospheres:  

CLASS 1 DIVISION 2 GROUPS ABCD  

  This equipment is an open-type device and is meant to be installed in an enclosure suitable for the environment that 

is only accessible with the use of a tool.  

• 

 Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations, or nonhazardous locations only.  

Warning 

– EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, 

DIVISION 2.  

Warning 

– WHEN IN HAZARDOUS LOCATIONS, TURN OFF POWER BEFORE REPLACING OR WIRING MODULES; 

AND  

Warning 

– DO NOT CONNECT OR DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE 

AREA IS KNOWN TO BE NONHAZARDOUS.  

Warning 

– EXPLOSION HAZARD - USB PORT IS ONLY FOR USE IN NONHAZARDOUS LOCATIONS, DO NOT USE 

UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS.  

 

 

ATEX Zone 2 

This product must be mounted in an enclosure certified in accordance with EN60079-15 for use in Zone 2, Group IIC and 

rated IP54. The enclosure shall only be able to be opened with the use of a tool 

 

 

 

 

Содержание RX3i PROFINET

Страница 1: ...ation via the micro USB port or using telnet Note The USB port is for system setup and diagnostics only It is not intended for permanent connection Support for star ring and daisy chain line network t...

Страница 2: ...Control 10 100 1000 Mbps Maximum I O Memory 128 Kbytes of combined input output memory per PROFINET Controller CPU Status Bits 32 PROFINET I O Device Data Update Rates on the PROFINET LAN Configurable...

Страница 3: ...t be installed in an ultimate enclosure that is manufactured to provide safety As a minimum the enclosure shall provide a degree of protection against solid objects as small as 12mm e g fingers This e...

Страница 4: ...tion or is not operational 8 Port4 SFP OK Indicates the health of the SFP plugged in port 4 1 indicates that the SFP matches configuration and is operational 0 indicates that either the SFP does not m...

Страница 5: ...e RX3i system using a Universal Backplane such as IC695CHS007 CHS012 or CHS016 The PNC supports insertion removal while power is applied to the system hot swap This includes backplane power and field...

Страница 6: ...such as Hyperterm The PNC is provided with a driver install application that can be used to enable a computer to communicate with a PNC via its USB port For details on using the Command Line Interfac...

Страница 7: ...res and Enhancements on page 8 IC695PNC001 AF 1 23 Aug 2013 Corrects issue storing PROFINET device configuration greater than 64K bytes in size For details see GFK 2573F IC695PNC001 AE 1 22 Jul 2013 C...

Страница 8: ...0 CPE310 CPE305 Boot Firmware Release 7 10 CRU320 Primary Firmware Release 8 00 CRU320 Boot Firmware Release 5 10 Other CPU models are not supported Programmer version requirements RX3i PNC001 Release...

Страница 9: ...ware configuration or the current hardware configuration in the system is cleared prior to storing a new configuration If the controller is Faulted clear the I O Fault Table to recover Otherwise no ad...

Страница 10: ...he failover occurs It is not recommended to use the PNC reset button in a normally operating system If the reset button must be used it is recommended to first attempt a brief press and release of the...

Страница 11: ...perly and updates the maximum number of telnet connections log details command response When displaying numerous local log table entries using the log details command sometimes erroneous blank charact...

Страница 12: ...t case ring recovery time is 96ms the rate needs to be more than 96ms divided by 3 which is 32ms The next available rate after 32ms is 64ms 16ms When using an I O Update Rate of 16ms you must set the...

Страница 13: ...configurations When storing hardware configurations with more than 64 PROFINET I O Devices that include multiple PNC modules and 3rd party PROFINET I O Devices on a single network occasional Loss Add...